6F3B0253
9.Maintenance and Checks
9.3Periodic checks
! | CAUTION | 1. Pay special attention during the maintenance work to minimize the risk | |
of electrical shock. | |||
|
|
2.Turn off power immediately if the
Check the
Item | Check | Criteria |
Power supply | Measure the power voltage at the T1- | 85 - 132/170 - 264Vac (AC PS) |
| 16S’s power terminals. | 20.4 - 28.8Vdc (DC PS) |
| Check that the terminal screw is not | Not loose |
| loose. |
|
| Check that the power cable is not | Not damaged |
| damaged. |
|
Installation | Check that the unit is installed | Not loose, no play |
condition | securely. |
|
| Check that the I/O module is inserted | Not loose, no play |
| securely. (if any) |
|
| Check that the expansion rack/unit is | Not loose, no play |
| installed securely. (if any) |
|
| Check that the expansion cable is | Not loose, not damaged |
| connected securely and the cable is |
|
| not damaged. (if any) |
|
| Check that the I/O module on the | Not loose, no play |
| expansion rack is inserted securely. (if |
|
| any) |
|
Input/output | Measure the input/output voltage at | The voltage must be within the |
| the | specified range. |
| Check the input status LEDs. | The LED must light normally. |
| Check the output status LEDs. | The LED must light normally. |
| Check that the terminal block is | Not loose, no play |
| installed securely. |
|
| Check that the terminal screw is not | Not loose, not contacting the |
| loose and the terminal has a sufficient | next terminal |
| distance to the next terminal. |
|
| Check that the each I/O wire is not | Not damaged |
| damaged. |
|