7. Instructions

JCS JCR

Jump control set / reset

Expression

Input

[ JCS ]

 

[ JCR ]

 

 

Function

When the JCS input is ON, instructions between JCS and JCR are skipped (not executed). When the JCS input is OFF, ordinary operation is performed.

Execution condition

JCS

Operation

Output

input

 

 

 

 

OFF

Ordinary operation

 

 

 

 

 

 

ON

Skips until JCR

 

 

 

 

 

 

Operand

No operand is required.

Example

When X000 is ON, the rung 2 circuit is skipped, therefore Y021 is not changed its state regardless of the X001 state. When X000 is OFF, Y021 is controlled by the X001 state.

Note

JCS and JCR must be used as a pair.

Nesting is not allowed.