6F3B0253
1. System Configuration
Memory capacity:
Program memory capacity of the T1 is 2 k steps. And that of the T1S is 8 k steps. Whole the program and a part of data registers are stored in
|
|
|
|
|
|
Memory | RAM (for execution) and EEPROM (for | ||||
Program | 2 k steps |
| 8 k steps |
|
|
capacity |
|
| (4 k mode or 8 k mode) | ||
Data capacity | Auxiliary relay: 1024 points | Auxiliary relay: | 4096 points | ||
| Timer: | 64 points | Timer: | 256 points | |
| Counter: | 64 points | Counter: | 256 points | |
| Data register: | 1024 words | Data register: | 4096 words | |
EEPROM | Program and leading 512 | Program and the user specified range of | |||
| words of Data register | Data register (0 to 2048 words) | |||
RAM | Capacitor: 6 hours or more | Capacitor: 168 hours | Capacitor: 1 hour | ||
(at 25°C) |
|
| or more |
| or more |
(at 77°F) |
|
|
|
| Battery: 2 years |
|
|
|
|
| or more |
Control functions:
In addition to the basic relay ladder functions, the T1/T1S provides functions such as data operations, arithmetic operations, various functions, etc. Furthermore, its high- speed counter functions, pulse output functions and data communication functions allow its application to a wide scope of control systems.
|
|
|
|
|
| |
Language | Ladder diagram with function block |
|
| |||
Number of | Basic: | 17 types | Basic: | 21 types | Basic: | 21 types |
instructions | Function: | 76 types | Function: | 99 types | Function: | 97 types |
Subroutines | 16 |
| 256 |
|
|
|
| (nesting not allowed) | (up to 3 levels of nesting) |
| |||
Execution speed | 1.4 ∝ s/contact, 2.3 ∝ s/coil, 4.2 ∝ s/transfer, 6.5 ∝ s/addition | |||||
| No |
| Yes (year, month, day, week, hours, | |||
clock/calendar |
|
| minutes, seconds) |
|
| |
Communication |
|
| ||||
| (programmer port) |
|
Construction:
The
Series compatibility:
Programming instructions are upward compatible in the
Basic Hardware and Function 15