7. Instructions

< Monitor mode (Mode 1) >

When the instruction input comes ON with the operand B+1 is 1, the Monitor mode (mode 1) is selected.

In this mode, the T1-16S sends the following Read commands to the Inverters starting from #0 through the Inverter number specified by the operand B, and repeats.

 

#0 Operating frequency monitor (FD00)

 

#0 Output terminal status monitor (FE07)

Scan

#1 Operating frequency monitor (FD00)

#1 Output terminal status monitor (FE07)

 

 

:

 

 

#n

Operating frequency monitor (FD00)

 

#n

Output terminal status monitor (FE07)

The maximum Inverter number #n is specified by the operand B.

The scan execution status and the Inverter communication status are stored in the operand B+2 to B+7.

The monitor data table is specified by the operand A and A+1.

When the instruction input is reset to OFF, the operation is stopped after receiving the response from the Inverter currently communicating.

Example

D1000

D1001

Data table designation

3RW200

100RW201 RW202 RW203 RW204 RW205 RW206 RW207

Parameter & status

19

1 (mode 1)

Execution status

Comm error code

Inverter comms

status map

D1010

D1011

RS-485 port

H0030 (fixed)

0 (fixed)

When the data for each operand are set as above, the following operation condition is specified.

RW200=19 The max Inverter number is 19. Therefore T1-16S scans from #0 through #19 Inverters.

D1000=3 & D1001=100 RW100 is specified as the data table starting address.