10. Troubleshooting

10.1.1Power supply check

If the PWR (power) LED is not lit after power on, check the following points.

Check the power connection

Correct

Check the power voltage at the T1-16S’s terminal

Normal

Remove the programmer port connector

Still unlit

Remove the 24Vdc service power terminals if it is used

Still unlit

Remove the I/O modules.

Lit

Confirm the internal 5Vdc current consumption if I/O module is used.

Within the limit

Insert the removed option modules one by one to pinpoint the faulty card.

Connection terminals are correct. The terminal screws are not loose. The terminal block is installed securely.

85 to 132/170 to 264Vac (50/60 Hz) or 20.4 to 28.8Vdc (DC power)

If the PWR LED becomes normal, the internal 5Vdc can be shorted in the external connections of this port.

If the PWR LED becomes normal, the 24Vdc service power can be over load.

If the PWR LED is still unlit, the T1-16S basic unit may be faulty. Replace the unit.

The 5Vdc capacity for I/O modules is max. 1.5A.

(Refer to section 2.1.)

Replace the faulty I/O module.