6F3B0253

7. Instructions

Data table:

Register

D2000

D2001

D2002

D2003

D2004

D2005

D2006

D2007

D2020

D2021

D2022

D2023

Data contents

#0 Operating frequency

#0 Output terminal status

#0 Frequency reference

#0 Operation command

#1 Operating frequency

#1 Output terminal status

#1 Frequency reference

#1 Operation command

#5 Operating frequency

#5 Output terminal status

#5 Frequency reference

#5 Operation command

Signal direction

Read

Read

Write

Write Read Read

Write

Write

Read

Read

Write

Write

The data format for the operating frequency and the frequency reference registers are 0.01 Hz units. For example, if it is 60 Hz, the corresponding register data is 6000.

For the data format of the output terminal status register, refer to the Monitor mode (mode 1).

The bit assignment of the operation command register is as follows. For details, refer to your Inverter manual.

F E D C B A 9 8 7 6 5 4 3 2 1 0

Programmed speed selection 0000 = None

0001 = Speed 1

0010 = Speed 2

:

1111 = Speed 15

PI operation (0 = Normal / 1 = Off)

DC braking (0 = Off / 1 = On)

Jog operation (0 = off / 1 = On)

F/R selection (0 = Forward / 1 = Reverse)

Run/Stop (0 = Stop / 1 = Run)

Free run (0 = Normal / 1 = Free run)

Emergency stop (0 = Normal / 1 = EMS)

Reset command (0 = Normal / 1 = Reset)

Frequency enable (0 = Disable / 1 = Enable)

Command enable (0 = Disable / 1 = Enable)

Example operation:

To operate the #0 Inverter at 30 Hz forward rotation, write the value 3000 in D2002 and HC400 in D2003. (HC400 = Bits F, E, A are 1, and others are 0)

The current operating frequency and the output terminal status of the #0 Inverter are stored in D2000 and D2001 respectively.