6F3B0253
Basic Hardware and Function 85
6. Programming Information
Device/
register Name Function
SW41 Sub-pr ogram #1 execut ion
status Bit 0 (S410) is ON during t he sub-program #1 is
executed
SW42 Reserved
SW43 Reserved
SW44 Reserved
SW45 Reserved
SW46 Reserved
SW47 Reserved
SW48 Reserved
SW49 Reserved
SW50 Reserved
SW51 Reserved
SW52 Reserved
SW53 Reserved
SW54 Basic unit I/O LED display
mode Used to display the selected I/O module status
(0 = Basic unit, 1 to 8 = I/O module slot 0 to 7,
9 and 10 = TOSLINE-F10)
SW55 Number of EEPROM write
data Used to set the number of data registers to be s aved in
the EEPROM (0 to 2048, initial value is 2048)
SW56 RS-485 p ort operation
mode Used to set the RS-485 port operation mode
(0 = Computer link, 1 = Data link, 2 = Free A SCII,
3 = Inverter connecti on)
SW57 RS-485 port response
delay Used to set the RS-485 port response delay time
(0 to 30: 0 to 300ms)
SW58 RS-485 p ort Free ASCII
flags Used for the RS-485 port Free ASCII funct ion
SW59 Reserved
SW60 Reserved
SW61 Reserved
SW62 Reserved
SW63 Reserved
(1) For details of SW 54, refer to section 1.5.1.(2) For details of SW 55, refer to section 5.2.(3) For details of SW56 through SW58, refer to the Communicationfunction manual.
NOTE