6F3B0253

7. Instructions

FUN 111

U<>

Unsigned not equal

Expression

Input [ A U<> B ]Output

Function

When the input is ON, the data of A and the data of B are compared, and if A is not equal to B, the output is turned ON.

Execution condition

Input

 

 

Operation

Output

OFF

No execution

 

 

OFF

ON

Execution

A

B

ON

 

 

A =

B

OFF

Operand

 

Name

 

 

Device

 

 

 

 

 

 

 

Register

 

 

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

 

I

 

J

K

 

 

A

Compared

 

 

 

 

 

 

 

 

 

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Reference

 

 

 

 

 

 

 

 

 

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example

When R00C is ON, the data of D0125 is compared with the constant data 0, and if the data of D0125 is not 0, R020 is turned ON.

If the data of D0125 is 41000, the comparison result is true. Consequently, R020 is turned ON.

D0125

41000

Constant

0

 

 

R020 is ON

 

If the data of D0125 is 0, the comparison result is false. Consequently, R020 is turned OFF.

D0125

0

=Constant

0

R020 is OFF

Note

This instruction deals with the data as unsigned integer (0 to 65535).

Basic Hardware and Function 193

Page 195
Image 195
Toshiba 6F3B0253 user manual FUN Unsigned not equal