6F3B0253
54 T1-16S User’s Manual
4. Installation and Wiring

4.1 Environmental conditions

Do not install the T1-16S in the following locations:
Where the ambient temperature drops below 0°C or exceeds 55°C.
W h e re t h e relative humidity drops below 20% or exceeds 90%.
Where there is condensation due to sudden temperature changes.
In locations subject to vibration that exceeds tolerance.
In locations subject to shock that exceeds tolerance.
Where there are corrosive or flammable gases.
In locations subject to dust, machining debris or other particles.
In locations exposed to direct sunlight.
Observe the following precautions when installing enclosures in which the T1-16S will
be installed:
Provide the maximum possible distance from high-voltage or high-power panels.
This distance must be at least 200mm.
If installing the enclosures in the vicinity of high-frequency equipment, be sure to
correctly ground the enclosures.
When sharing the channel base with other panels, check for leakage current from
the other panels or equipment.
!
CAUTION
Excess temperature, humidity, vibration, shocks, or dusty and corrosive
gas environment can cause electrical shock, fire or malfunction.
Install and use the T1-16S and related equipment in the environment
described in this section.