6F3B0253
Basic Hardware and Function 79
6. Programming Information
Special devices and registers (S/SW)
The special devices (S) and special registers (SW) are used for special purposes. See
list below.
Device/
register Name Function
S000 0: Initialization 4: HOLD mode
S001 T 1/ T1S operation mode 1: HALT mode 6: ERROR mode
S002 2: RUN mode
S003 3: RUN-F mode
S004 CPU er ror (down) ON at error state (related to SW 01)
S005 I/O error (down) ON at error state (related to SW02)
S006 Pr ogram error (down) ON at error state (related to SW03)
S007 EEPROM al arm (alarm) ON when EEPROM write exceeds 100,000 times
S008 F ixed-time scan time-ov er
(alarm) ON when actual scan time i s longer than the setting
time as fi xed-time scan
S009 Reserved
S00A Clock/calendar error
(alarm) ON when clock/calendar data is il legal
S00B Reserved
S00C Reserved
S00D TL-F10 error (alarm) ON when TOSLINE-F10 t ransmission error occurs
S00E Reserved
S00F Retentiv e data invalid
(alarm) ON when retentive data in RAM are invalid
(1) These devices are set by the T1-16S operating system. These devices
are read only for user.
(2) Devices marked as (down) are set in the ERROR mode. Therefore
these devices cannot be used in the user program.
(3) Devices marked as (alarm) are set in the normal operation mode.
These devices can be used in the user program.