6F3B0253
7. Instructions
( P )
Positive pulse coil
Expression
A
Input ( P )
Function
When the input is changed form OFF to ON, the device A is set to ON for 1 scan time. This instruction is used to detect the input changing from OFF to ON.
Execution condition
Input | Operation | Output |
OFF | Sets device A to OFF | − |
ON | When the input at last scan is OFF, sets A to ON | − |
| When the input at last scan is ON, sets A to OFF | − |
Operand
| Name |
|
| Device |
|
|
|
|
|
| Register |
|
| Constant | Index | ||||
|
| X | Y | R | S | T. | C. | XW | YW | RW | SW | T | C | D | I | J | K |
|
|
A | Device |
| √ | √ | √ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Example
R101 comes ON for only 1 scan when X000 is changed from OFF to ON.
X000
R100
1 scan time | 1 scan time |
Note
•The maximum usable number in a program is 2048.
( P N (P) (N) total)
Basic Hardware and Function 127