6F3B0253

10.Troubleshooting

10.1.5Output check

If the output status monitored on the programming tool is normal but the external output device (load) is not operated normally, check the following points:

No

Is the output status LED changed ON/OFF according to the program execution ?

Yes

Check the voltage between the output terminal and its common terminal.

It should be 0V when the output is ON, and it should be the circuit voltage when the output is OFF.

If it is the circuit voltage at the output is ON, or if it is 0V at the output is OFF with the load ON, the T1-16S’s output circuit may be faulty.

If it is 0V and the load is also OFF, check the output power and the output cable connections.

Normal

Check the voltage at the load

Check whether the I/O allocation table is identical to the actual I/O configuration

If it is not normal, check the output cable connections.

If it is normal, check the specification of the load, also check environmental factors.

If identical, the T1-16S’s internal circuit or the output circuit may be faulty.

Not identical

Execute the automatic I/O allocation, and check whether the I/O allocation table is now identical to the actual I/O configuration

Still not identical

If it becomes identical, execute the EEPROM write operation.

Is the allocation mismatch for a specific I/O module?

If so, the card, module or expansion unit may be faulty. For expansion unit, check the expansion cable also.

286 T1-16S User’s Manual