7. Instructions

< Read command mode (Mode 2) >

When the instruction input comes ON with the operand B+1 is 2, the Read command mode (mode 2) is selected. In this mode, the T1-16S sends the user specified Read command to the Inverter specified by the operand B, and repeats.

Repeat

Sends the specified command to #n Inverter

Receives the response and stores the data into the register

The target Inverter number #n is specified by the operand B.

The scan execution status and the Inverter communication status are stored in the operand B+2 to B+7.

The command setting register and the response data storing register is indirectly specified by the operand A and A+1.

When the instruction input is reset to OFF, the operation is stopped after receiving the response from the Inverter.

Example

D1000

D1001

Data table designation

4RW200

3000RW201 RW202 RW203 RW204 RW205 RW206 RW207

Parameter & status

3

2 (mode 2)

Execution status

Comm error code

Inverter comms

status map

D1010

D1011

RS-485 port

H0030 (fixed)

0 (fixed)

When the data for each operand are set as above, the following operation condition is specified.

RW200=3 The target Inverter number is 3. Therefore T1-16S communicates with #3 Inverter.

D1000=4 & D1001=3000 D3000 is specified as the command setting register and D3001 is specified as the response data storing register.

Data table:

Register

D3000

D3001

Data contents

Command code

Response data

Signal direction

Read

Example operation:

For example, to read the output current from the #3 Inverter, set the command code HFE03 into D3000. Then the response data is stored in D3001. If the response data is 1915, it means 19.15 %. For the command code and the data format of the response, refer to your Inverter manual.

Basic Hardware and Function 251

Page 253
Image 253