Bard Air Conditioner and Wall Mount Troubleshooting Manual

Page 16

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Show in Figure 8 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimension below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 8

FAN BLADE SETTING DIMENSION

TABLE 5

FAN BLADE DIMENSION

Model

Dimension A

 

 

WA121

1/2"

 

 

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature 6" from compressor as shown in Table 6.

TABLE 6

SUCTION LINE TEMPERATURE

 

Rated

95o OD

82o OD

Model

Airflow

Temperature

Temperature

 

 

 

 

WA121

400

54 - 56

65 - 67

 

 

 

 

The suction line temperatures in Table 6 are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 7

INDOOR BLOWER

PERFORMANCE

CFM @ 230V

 

WA121

 

 

E.S.P.

230V

 

 

 

 

 

 

in H2O

Dry /

Wet

.0

530

/

500

.1

485

/

460

.2

440

/

425

.3

390

/

375

.4

325

/

300

 

 

 

 

TABLE 8

RATED CFM AND ESP

RECOMMENDED AIRFLOW RANGE

 

Rated

Rated

Recommended

Model

CFM*

ESP*

Airflow Range

 

 

 

 

WA121

400

.25

500 - 300

 

 

 

 

* Rated CRM and ESP on high speed tap.

TABLE 9

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

ESP

 

 

WA121-A00

.35

A03

.35

A05

.35

 

 

WA121-K00

.35

K02

.35

 

 

WA121-G00

.35

G02

.35

G03

.35

 

 

Values shown are for units equipped with STD 1" throwaway filters. Derate ESP by .15 for 2" pleated filters.

Manual 2100-234IPage 16 of 17

Image 16 Contents
Bard Manufacturing Company, Inc Bryan, OhioContents Getting Other Information and Publications Wall Mount General Information AIR Conditioner Wall Mount Model NomenclatureX X X J Electric Heat TableUnit Dimensions Factory Built AT 5 Inches Shipping Damage Electrical Heat SpecificationsGeneral Duct Work FiltersFresh AIR Intake Condensate DrainWall Mounting Information Installation InstructionsMounting the Unit Mounting Instructions Wall Mounting Instructions Common WALL-MOUNTING Installations Wiring Main Power Wiring LOW Voltage Wiring Thermostat Wire Size Wall ThermostatLOW Voltage Wiring Start UP Adjustments Pressure Service PortsAdjustable Delay on Make and Delay on Break Timer Typical Settings for Dual Unit InstallationFAN Blade Setting Dimensions TroubleshootingRefrigerant Charge Pressure Table Optional Field Installed AccessoriesWA121