TROUBLESHOOTING
FAN BLADE SETTING DIMENSIONS
Show in Figure 8 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimension below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 8
FAN BLADE SETTING DIMENSION
TABLE 5
FAN BLADE DIMENSION
Model | Dimension A |
|
|
WA121 | 1/2" |
|
|
REFRIGERANT CHARGE
The correct system
TABLE 6
SUCTION LINE TEMPERATURE
| Rated | 95o OD | 82o OD |
Model | Airflow | Temperature | Temperature |
|
|
|
|
WA121 | 400 | 54 - 56 | 65 - 67 |
|
|
|
|
The suction line temperatures in Table 6 are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.
TABLE 7
INDOOR BLOWER
PERFORMANCE
CFM @ 230V
| WA121 | ||
|
| ||
E.S.P. | 230V | ||
|
|
| |
|
|
| |
in H2O | Dry / | Wet | |
.0 | 530 | / | 500 |
.1 | 485 | / | 460 |
.2 | 440 | / | 425 |
.3 | 390 | / | 375 |
.4 | 325 | / | 300 |
|
|
|
|
TABLE 8
RATED CFM AND ESP
RECOMMENDED AIRFLOW RANGE
| Rated | Rated | Recommended |
Model | CFM* | ESP* | Airflow Range |
|
|
|
|
WA121 | 400 | .25 | 500 - 300 |
|
|
|
|
* Rated CRM and ESP on high speed tap.
TABLE 9
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Model | ESP |
|
|
.35 | |
A03 | .35 |
A05 | .35 |
|
|
.35 | |
K02 | .35 |
|
|
.35 | |
G02 | .35 |
G03 | .35 |
|
|
Values shown are for units equipped with STD 1" throwaway filters. Derate ESP by .15 for 2" pleated filters.
Manual