WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” of “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
WIRING – LOW VOLTAGE WIRING
230/208, 1 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the
240 and 208V taps are:
TAP RANGE
240 | 253 | - | 216 |
208 | 220 | - | 187 |
NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper,
TABLE 3
THERMOSTAT WIRE SIZE
Transformer |
|
| Maximum Distance |
VA | FLA | Wire Gauge | in Feet |
|
|
|
|
|
| 20 Gauge | 45 |
|
| 18 Gauge | 60 |
40 | 2.3 | 16 Gauge | 100 |
|
| 14 Gauge | 160 |
|
| 12 Gauge | 250 |
|
|
|
|
| TABLE 4 | |
| WALL THERMOSTAT | |
|
| |
Thermostat | Predominate Features | |
|
| |
1 stage Cool, 1 stage Heat | ||
Electronic | ||
TH5220D1153 | ||
| Auto or Manual changeover | |
2 stage Cool, 2 stage Heat | ||
Electronic | ||
TH5220D1151 | ||
| Auto or Manual changeover | |
| 3 stage Cool; 3 stage Heat | |
HP or Conventional | ||
| Auto or Manual changeover | |
|
|