Bryant 551B installation instructions Contents, Safety Considerations, Installation

Page 1

installation, start-up and

 

551B

service instructions

 

DuraPac Plus Series

SINGLE PACKAGE ROOFTOP

Sizes 090-150

71/

to 121/ Tons

ELECTRIC COOLING UNITS

2

2

 

 

 

 

 

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-37 I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1 II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 1

III. Step 3 — Install Condensate Drain Line

and External Trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 IV. Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 2 V. Step 5 — Make Electrical Connections . . . . . . . . . . 7 VI. Step 6 — Adjust Factory-Installed Options . . . . . . 11 VII. Step 7 — Adjust Evaporator-Fan Speed . . . . . . . . 21

PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38-41

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41-45

TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .46-49

INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo- nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func- tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per- sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.

CAUTION: Ensure voltage listed on unit data plate agrees with electrical supply provided for unit.

WARNING: Before performing service or mainte- nance operations on unit, turn off main power switch to unit and install lockout tag. Electrical shock could cause personal injury.

INSTALLATION

Unit is shipped in the vertical configuration. To convert to horizontal configuration, remove side duct opening covers. Using the same screws, install covers on vertical duct open- ings with the insulation-side down. Seals around duct openings must be tight. See Fig. 1.

Cancels: II 551B-90-6

II 551B-90-7

 

10/15/05

I. STEP 1 — PROVIDE UNIT SUPPORT

A. Roof Curb

Assemble and install accessory roof curb in accordance with instructions shipped with curb. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb. If electric or control power is to be routed through the basepan, attach the accessory thru-the- bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperly applied gasket can also result in air leaks and poor unit performance.

Curb should be level. This is necessary for unit drain to func- tion properly. Unit leveling tolerances are shown in Fig. 3. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

B. Slab Mount (Horizontal Units Only)

Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of con- denser coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

C. Alternate Unit Support (Curb or Slab Mount)

A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.

II. STEP 2 — FIELD FABRICATE DUCTWORK

On vertical discharge units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. For hori- zontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external duct- work, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insu- lated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli- cable fire codes.

A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On horizontal dis- charge units, a minimum clearance of 1 in. is required for the first 12 in. of ductwork. Cabinet return-air static pressure (a negative condition) should not exceed 0.30 in. wg with EconoMi$er IV, or 0.45 in. wg without economizer.

Image 1
Contents Safety Considerations ContentsInstallation Provide Unit SupportIV. RIG and Place Unit III. Install Condensate Drain Line and External TrapPositioning Roof Curb Details Operating WeightBase Unit Dimensions Unit 551B Physical DataMake Electrical Connections Field Power SupplyIFC NECFLA MCA Mocp LRA Hacr Electrical DataVoltage Comp no Electric Heater †Used to determine minimum disconnect per NEC Electric Heater UsageHeat Anticipator Settings Field Control WiringVI. Adjust FACTORY-INSTALLED Options A. Disconnect Switch Perfect Humidity Dehumidification SystemAccessory Field-Installed Humidistat Manual Outdoor-Air Damper Convenience OutletOptional EconoMi$er Hood Box Removal EconoMi$er IV Standard SensorsOutdoor-Air Hood Construction EconoMi$er IV Sensor Usage EconoMi$er IV Control ModesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Ppm CO2 Sensor Standard SettingsUnit Heater Required Config VII. Adjust EVAPORATOR-FAN SpeedMinimum Required Airflow Exceptions UrationFan Rpm at Motor Pulley Setting* High-Static Motor/Drive Fan Rpm at Motor Pulley Setting* Standard Motor/DriveEvaporator-Fan Motor Data Standard Motor Accessory/FIOP Electric Heaters Static Pressure in. wg Accessory/FIOP EconoMi$er IV Static Pressure* in. wgEvaporator-Fan Motor Data High-Static Motors General FAN Performance NotesAirflow 866 697 1088 756 1324 832 690 1051 750 1285901 703 1125 762 1365 974 716 1204 774 1449506 629 625 688 745 489 386866 502 4241656 15671748 1844805 695 953 749 1100 799 1249 748 684 891 738 1034 789 1177865 707 760 1170 809 1323929 718 1086 771 1244 820 1401 865 707 1018 760 1170 809 13231665 1873668 1116 726 654 1040 713683 1197 739 697 1281 753596 629 802 694 1021 465 4021252 471 421882 684 1125 746 1378 823 674 1059 737 1306944 695 1194 756 1453 1009 705 1266 766 1533467 614 594 681 728 462 348868 474 3812821 27162293 996 2501 1038 2713 29301677 808 1876 855 2081 710 1482723 1577 1775 820 19781582 796 1777 1492 784 16831677 808 1876 1877781 1445 614 929 673628 997 685 791 1525VI. Refrigerant Service Ports Internal WiringPRE-START-UP START-UP Unit PreparationXI. Safety Relief Heating if Accessory Heater is InstalledIX. Cooling XII. Ventilation Continuous FANPerfect Humidity System Normal Design Cooling Operation Service Cleaning Units With Power ExhaustEvaporator Coil Condenser CoilsIV. BELT/PULLEY Adjustment III. CONDENSER-FAN Adjustment FIGECONOMI$ER IV Adjustment II. LubricationCooling Charging Charts, Standard 551B090 Unit Cooling Charging Charts, Standard 551B120 Unit VII. Replacement Parts Cooling Troubleshooting Troubleshooting Unit TroubleshootingProblem Cause Remedy Reheat Mode Will Not Energize Subcooling Mode Liquid ReheatWill Not Energize Low System CapacityII. ECONOMI$ER IV Troubleshooting EconoMi$er IV Input/Output Logic EconoMi$er IV Troubleshooting CompletionInputs Outputs Demand Control EnthalpyIndex Operating sequence Cooling EconoMi$er HeatingPage Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 170 pages 34.1 Kb Manual 61 pages 53.59 Kb

551B specifications

The Bryant 551B and 551C are two highly efficient air conditioning units designed to provide optimal comfort in residential settings. Known for their reliability and performance, these models are part of Bryant's esteemed line of heating and cooling solutions.

One of the standout features of the Bryant 551B is its two-stage cooling system, which allows for better humidity control and increased comfort. This ensures that homeowners can enjoy consistent temperatures while reducing energy consumption. The unit operates quietly, thanks to its noise-reducing technology, making it an ideal choice for bedrooms and living spaces.

On the other hand, the Bryant 551C builds upon this foundation with its variable-speed compressor. This technology allows the unit to adjust its cooling output according to the specific needs of the home. This results in seamless operation and even greater energy efficiency. Both models also incorporate Bryant's advanced control capabilities, which allow users to monitor and adjust settings remotely via smart devices, adding a layer of convenience and modernity to home climate control.

With an emphasis on durability, both the 551B and 551C feature a galvanized steel cabinet that protects against weather-related damage. The powder coat finish further enhances their resistance to rust and corrosion, ensuring a long lifespan and minimal maintenance.

Another significant characteristic of these units is their excellent Seasonal Energy Efficiency Ratio (SEER) ratings. The 551B boasts a SEER rating of up to 16, while the 551C takes it even further with ratings exceeding 20. This efficiency not only translates to lower energy bills for homeowners but also contributes to a reduced carbon footprint, making these units environmentally friendly options.

Both models are also designed to operate with eco-friendly refrigerants, aligning with modern energy standards and regulations aimed at reducing greenhouse gas emissions.

In summary, the Bryant 551B and 551C are exemplary choices for homeowners looking for reliable, efficient, and high-performing air conditioning solutions. With features such as two-stage and variable-speed compressors, advanced smart technology, and robust construction, these models stand out in the competitive HVAC market. They promise a comfortable indoor environment along with significant energy savings, making them a wise investment for the future.