Bryant 551B installation instructions EconoMi$er IV Controller Potentiometer LED Locations

Page 17

Outdoor Dry Bulb Changeover

The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor-air dampers to minimum position. If the outdoor-air temperature is below the set point, the position of the outdoor-air dampers will be controlled to provide free cool- ing using outdoor air. When in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the control. See Fig. 30. The scale on the potentiometer is A, B, C, and D. See Fig. 31 for the corre- sponding temperature changeover values.

Differential Dry Bulb Control

For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional acces- sory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. See Fig. 32. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 25.

In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower tem- perature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy set point potentiom- eter fully clockwise to the D setting. See Fig. 30.

Outdoor Enthalpy Changeover

For enthalpy control, accessory enthalpy sensor (part num- ber HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 19. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiome- ter on the EconoMi$er IV controller. The set points are A, B,

Fig. 30 — EconoMi$er IV Controller Potentiometer

and LED Locations

19

 

18

LED ON

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

LED OFF

LED ON

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mA

14

 

 

 

LED OFF

 

LED ON

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

LED OFF

LED ON

 

 

 

 

 

 

 

 

 

 

 

A

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

LED OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

100

 

40

45

50

55

60

65

70

75

80

85

90

95

 

 

 

 

 

DEGREES FAHRENHEIT

 

 

 

 

Fig. 31 — Outdoor Air Temperature Changeover Set Points

C, and D. See Fig. 33. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. See Fig. 19 and 34.

Differential Enthalpy Control

For differential enthalpy control, the EconoMi$er IV control- ler uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.

Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting loca- tion. See Fig. 19. Mount the return air enthalpy sensor in the return air duct. See Fig. 32. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 25. The outdoor

ECONOMI$ER IV

ECONOMI$ER IV

CONTROLLER

GROMMET

RETURN AIR

SENSOR

RETURN DUCT (FIELD-PROVIDED)

enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy set- point potentiometer fully clockwise to the D setting.

Fig. 32 — Return Air Temperature or Enthalpy Sensor Mounting Location

17

Image 17
Contents Safety Considerations ContentsInstallation Provide Unit SupportPositioning III. Install Condensate Drain Line and External TrapIV. RIG and Place Unit Roof Curb Details Operating WeightBase Unit Dimensions Unit 551B Physical DataMake Electrical Connections Field Power SupplyIFC NECFLA MCA Mocp LRA Hacr Electrical DataVoltage Comp no Electric Heater †Used to determine minimum disconnect per NEC Electric Heater UsageHeat Anticipator Settings Field Control WiringVI. Adjust FACTORY-INSTALLED Options A. Disconnect Switch Perfect Humidity Dehumidification SystemAccessory Field-Installed Humidistat Optional EconoMi$er Convenience OutletManual Outdoor-Air Damper Hood Box Removal EconoMi$er IV Standard SensorsOutdoor-Air Hood Construction EconoMi$er IV Sensor Usage EconoMi$er IV Control ModesEconoMi$er IV Controller Potentiometer LED Locations Enthalpy Changeover Set Points Page Ppm CO2 Sensor Standard SettingsUnit Heater Required Config VII. Adjust EVAPORATOR-FAN SpeedMinimum Required Airflow Exceptions UrationEvaporator-Fan Motor Data Standard Motor Fan Rpm at Motor Pulley Setting* Standard Motor/DriveFan Rpm at Motor Pulley Setting* High-Static Motor/Drive Accessory/FIOP Electric Heaters Static Pressure in. wg Accessory/FIOP EconoMi$er IV Static Pressure* in. wgEvaporator-Fan Motor Data High-Static Motors General FAN Performance NotesAirflow 866 697 1088 756 1324 832 690 1051 750 1285901 703 1125 762 1365 974 716 1204 774 1449506 629 625 688 745 489 386866 502 4241656 15671748 1844805 695 953 749 1100 799 1249 748 684 891 738 1034 789 1177865 707 760 1170 809 1323929 718 1086 771 1244 820 1401 865 707 1018 760 1170 809 13231665 1873668 1116 726 654 1040 713683 1197 739 697 1281 753596 629 802 694 1021 465 4021252 471 421882 684 1125 746 1378 823 674 1059 737 1306944 695 1194 756 1453 1009 705 1266 766 1533467 614 594 681 728 462 348868 474 3812821 27162293 996 2501 1038 2713 29301677 808 1876 855 2081 710 1482723 1577 1775 820 19781582 796 1777 1492 784 16831677 808 1876 1877781 1445 614 929 673628 997 685 791 1525VI. Refrigerant Service Ports Internal WiringPRE-START-UP START-UP Unit PreparationXI. Safety Relief Heating if Accessory Heater is InstalledIX. Cooling XII. Ventilation Continuous FANPerfect Humidity System Normal Design Cooling Operation Service Cleaning Units With Power ExhaustEvaporator Coil Condenser CoilsIV. BELT/PULLEY Adjustment III. CONDENSER-FAN Adjustment FIGECONOMI$ER IV Adjustment II. LubricationCooling Charging Charts, Standard 551B090 Unit Cooling Charging Charts, Standard 551B120 Unit VII. Replacement Parts Problem Cause Remedy Troubleshooting Unit TroubleshootingCooling Troubleshooting Reheat Mode Will Not Energize Subcooling Mode Liquid ReheatWill Not Energize Low System CapacityII. ECONOMI$ER IV Troubleshooting EconoMi$er IV Input/Output Logic EconoMi$er IV Troubleshooting CompletionInputs Outputs Demand Control EnthalpyIndex Operating sequence Cooling EconoMi$er HeatingPage Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 170 pages 34.1 Kb Manual 61 pages 53.59 Kb

551B specifications

The Bryant 551B and 551C are two highly efficient air conditioning units designed to provide optimal comfort in residential settings. Known for their reliability and performance, these models are part of Bryant's esteemed line of heating and cooling solutions.

One of the standout features of the Bryant 551B is its two-stage cooling system, which allows for better humidity control and increased comfort. This ensures that homeowners can enjoy consistent temperatures while reducing energy consumption. The unit operates quietly, thanks to its noise-reducing technology, making it an ideal choice for bedrooms and living spaces.

On the other hand, the Bryant 551C builds upon this foundation with its variable-speed compressor. This technology allows the unit to adjust its cooling output according to the specific needs of the home. This results in seamless operation and even greater energy efficiency. Both models also incorporate Bryant's advanced control capabilities, which allow users to monitor and adjust settings remotely via smart devices, adding a layer of convenience and modernity to home climate control.

With an emphasis on durability, both the 551B and 551C feature a galvanized steel cabinet that protects against weather-related damage. The powder coat finish further enhances their resistance to rust and corrosion, ensuring a long lifespan and minimal maintenance.

Another significant characteristic of these units is their excellent Seasonal Energy Efficiency Ratio (SEER) ratings. The 551B boasts a SEER rating of up to 16, while the 551C takes it even further with ratings exceeding 20. This efficiency not only translates to lower energy bills for homeowners but also contributes to a reduced carbon footprint, making these units environmentally friendly options.

Both models are also designed to operate with eco-friendly refrigerants, aligning with modern energy standards and regulations aimed at reducing greenhouse gas emissions.

In summary, the Bryant 551B and 551C are exemplary choices for homeowners looking for reliable, efficient, and high-performing air conditioning solutions. With features such as two-stage and variable-speed compressors, advanced smart technology, and robust construction, these models stand out in the competitive HVAC market. They promise a comfortable indoor environment along with significant energy savings, making them a wise investment for the future.