Bryant 598B Installing TXV in Place of Piston, Replacing R-22 TXV or NON-BALANCE Port Puron TXV

Page 3

B

INLET

D A

COIL

E

BULB

INSULATION

TAPE

C

A01418

Fig. 5—TXV Kit Contents

INSTALLING TXV IN PLACE OF PISTON

1.Remove any existing refrigerant and ensure coil has not been exposed to atmospheric pressure for more than 15 minutes.

2.Remove indoor coil inlet tube at piston body inlet. Use back-up wrench to prevent damage.

3.Remove piston retainer, begin careful not to damage scaling surface of O-ring.

4.Remove and discard factory-installed piston. (Replace re- tainer if O-ring is damaged.)

5.Reinstall piston retainer in piston body.

6.Replace indoor coil inlet tube. Use back-up wrench to prevent damage.

CAUTION: To prevent damage to the unit, use a brazing shield and wrap TXV with wet cloth.

7.Sweat swivel adapter (see Fig. 5D) to inlet of indoor coil and attach to TXV (see Fig. 5A) outlet. Use backup wrench to avoid damage to tubing or valve. Sweat Inlet of TXV, marked “IN” to liquid line. Avoid excessive heat which could damage valve

8.Install vapor elbow (see Fig. 5B) with equalizer adapter to suction tube of line set and suction connection to indoor coil. Adapter has a 1/4-in. male connector or attaching equalizer tube.

9.Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter.

10.Attach TXV bulb to horizontal section of suction line using bulb straps provided. (See Fig. 5C.) Insulate bulb with factory-supplied insulation tape. (See Fig. 5E.) See Fig. 6 for correct positioning of sensing bulb.

11.Proceed with remainder of unit installation.

REPLACING R-22 TXV OR NON-BALANCE PORT PURON TXV

1.Remove any existing refrigerant and ensure coil has not been exposed to atmospheric pressure for more than 15 minutes.

—3—

2.Remove coil access panel and fitting panel from front of cabinet.

3.Remove TXV support clamp using the 5/16-in. nut driver. Save the clamp.

4.Remove TXV using a backup wrench on flare connections to prevent damage to tubing.

5.Using wire cutters, cut equalizer tube off flush with vapor tube inside cabinet.

6.Remove bulb from vapor tube inside cabinet.

7.Braze equalizer stub-tube closed. Use protective barrier as necessary to prevent damage to drain pan.

IMPORTANT: Route the equalizer tube of approved Puron® TXV through suction line connection opening in fitting panel prior to replacing fitting panel around tubing.

8.Install TXV with 3/8-in. copper tubing through small hole in service panel. (See Fig. 5A.) To avoid damage to tubing or valve, use wrench and backup wrench to attach TXV to distributor.

9.Reinstall TXV support clamp (removed in item 3).

10.Attach TXV bulb to vapor tube inside cabinet, in same location as original was when removed, using supplied bulb strap. (See Fig. 5C.) See Fig. 6 for correct positioning of sensing bulb.

11.Route equalizer tube through suction connection opening (large hole) in fitting panel and install fitting panel in place.

12.Sweat inlet of TXV, marked “IN” to liquid line. Avoid excessive heat which could damage valve.

13.Install vapor elbow with equalizer adapter to vapor line of line set and vapor connection to indoor coil. (See Fig. 5B.) Adapter has a 1/4-in. male connector for attaching equalizer tube. (See Fig. 5B.)

14.Connect equalizer tube of TXV by 1/4-in. equalizer fitting, on vapor line adapter. Use backup wrench to prevent damage to equalizer fitting.

15.Proceed with the remainder of unit installation.

B. LONG-LINE APPLICATIONS

For refrigerant piping arrangements with equivalent lengths greater than 50 ft or when elevation difference between indoor and/or outdoor unit is more than 20 ft, follow all requirements of the Long-Line Guideline section in the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using Puron Refrigerant.

VI. MAKE PIPING CONNECTIONS

WARNING: Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.

CAUTION: Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.

Image 3
Contents Installation Recommendations Safety ConsiderationsInstall TXV Installation Check Equipment and JOB Site Unpack UnitII. Install on a SOLID, Level Mounting PAD DimensionsInstalling TXV in Place of Piston Replacing R-22 TXV or NON-BALANCE Port Puron TXVLONG-LINE Applications VI. Make Piping Connections Sweat Connection Install LIQUID-LINE Filter DrierOutdoor Unit Connected to FACTORY- Approved Indoor Unit Refrigerant TubingFinal Tubing Check Route Ground and Power WiresConnect Ground and Power Wires Connect Control WiringAirflow Selection for FK4C or FV4A FAN Coils Accessory UsageVIII. Install Electrical Accessories General Latent Capacity Control LCCTypical 24V Wiring Diagram See notes 1, 2, 3, Programmable FK4C, FV4A Thermidistat Wiring Diagram Notes Unit Charge XI. Check Charge Cooling only ProcedureRequired LIQUID-LINE Temperature F START-UPXII. System Functions and Sequence of OPERA- Tion Subcooling TemperaturesFactory Defaults ONE Minute Speed Change Time DelayPressure Switch Protection Temperature ThermistorsMajor Components XIII. Final Checks Care and MaintenanceWiring Diagram-024, 036 Wiring Diagram-060
Related manuals
Manual 40 pages 2.5 Kb

598B specifications

The Bryant 598B, a model in the world of heating, ventilation, and air conditioning (HVAC) systems, stands out due to its efficient and reliable performance. This compact air conditioning unit is engineered to provide optimal cooling, making it an excellent choice for various residential and light commercial applications.

One of the main features of the Bryant 598B is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which indicates its energy efficiency in cooling mode. With a SEER rating that often exceeds industry standards, the 598B helps homeowners save on energy bills while minimizing their carbon footprint. This high efficiency is a key advantage, especially in regions experiencing extreme temperatures.

The Bryant 598B utilizes advanced technologies that enhance its overall performance and longevity. One of the standout technologies is the two-stage compressor, which allows the unit to operate at different cooling capacities depending on the current heat load. This capability not only improves comfort levels by maintaining consistent temperatures but also reduces wear and tear on the system, leading to extended lifespan and reliability.

Another noteworthy characteristic of the 598B is its quiet operation. Equipped with a sound-dampening design, the unit minimizes operational noise, ensuring peaceful indoor and outdoor environments. This feature is especially appreciated in areas where noise reduction is a priority, such as residential neighborhoods.

The Bryant 598B also comes with a durable cabinet built from high-quality materials that resist corrosion and withstand harsh weather conditions. This durability is crucial for maintaining performance over time, providing peace of mind for homeowners who invest in this HVAC solution.

Installation and maintenance of the Bryant 598B are facilitated by its user-friendly design. The unit includes features that allow for straightforward access to components, making service and upkeep more manageable for HVAC professionals.

In conclusion, the Bryant 598B air conditioning unit offers an appealing combination of energy efficiency, advanced technology, quiet operation, and durability. Whether for a new home or a system replacement, the Bryant 598B is an excellent choice for those seeking reliable and effective cooling solutions that align with modern efficiency standards.