Omega Vehicle Security CCT-05 Series CCT-05 Electrical Features, Sensor Type Selection, Input

Page 8

SENSOR TYPE SELECTION

This signal conditioner can connect to standard sensors such as PNP, NPN, Namur or ac signals. See the Connections Section.

The signal conditioner provides two excitation voltages for the sensors, 24 Vdc for PNP or NPN sensors and 8.2 Vdc for NAMUR sensors. Table 4 indicates which jumpers must be selected for each type of sensor. The jumpers are located on the "MP" input board. See Fig. 8.

TABLE 4

Sensor type selection

close

(Selector A)

jumper

 

 

NAMUR

10 & 9

NPN/PNP (3 wires)

10

NPN (Open collector)

10 & 7

PNP (Open collector)

10 & 8

Vac ≤ 100

10

Vac ≥ 100

-----

 

 

CCT-05 ELECTRICAL FEATURES

INPUT

SIGNAL TYPE

PNP, NPN, Namur, Vac

FREQUENCY

Min. 10 Hz. Max. 40 KHz.

AUXILIARY POWER SUPPLY

+24 Vdc @ 25 mA. for PNP, NPN.

 

8.2 Vdc for Namur

OUTPUT

 

 

0 to 20 mA or 4 to 20 mA

RL< 600 Ω max. 22 mA ±3%

0 to 10 Vdc

RL> 1000 Ω max. 11 V ±3%

ACCURACY

0.2 % FS

RESPONSE TIME

250 mS

GALVANIC ISOLATION

Input, Output and Power Supply are all isolated

 

to 2 kVeff. 50 Hz/1 m.

GENERAL SPECIFICATIONS

 

 

RIPPLE

0.5 %

BAND PASS

1.5 Hz (-3 dB)

STORAGE TEMPERATURE

-30° to +80°C

OPERATING TEMPERATURE

-10° to +60°C

TEMPERATURE COEFFICIENT

0.015 %/°C

STANDARD POWER SUPPLY

115 Vac (±10%) 50/60 Hz

POWER CONSUMPTION

1.5 VA

TEST VOLTAGE

4 kVeff. 50 Hz/1m.

7

Image 8
Contents User’sGuide Omega.comTM Table of Contents Open the Housing ProcedureProcedure for Disassembly Internal OverviewRecomended Wiring PrecautionsChanging the Power Supply ProtectionsChanging the Signal Output NON Standard Output Voltages CurrentsAmplifier Gain Offset AdjustOverview CCT-05 Electrical Features General SpecificationsSensor Type Selection InputSignal Input Range Selection Adjustment and Calibration ProcedureSignal Output ConnectionsMechanical DimensionsTechnical Data Page USAWARRANTY/DISCLAIMER Temperature