When a bypass diode is wired in parallel with the series string, the forced current will flow through the diode and bypass the shaded module, thereby minimizing module heating and array current losses.
For
Diodes that are used as bypass diodes must:
・Have a Rated Average Forward Current [IF(AV)] Above maximum system current at highest module operating temperature.
・Have a Rated Repetitive Peak Reverse Voltage [VRRM] Above maximum system voltage at lowest module operating temperature.
12. MAINTENANCE
Kyocera modules are designed for long life and require very little maintenance. Under most weather conditions, normal rainfall is sufficient to keep the module glass surface clean. If dirt
13. SPECIFICATIONS
The electrical and physical specifications can be found at the end of this document (Table 2).
NOTES
・The electrical characteristics are within ±10 percent of indicated values of Isc, Voc, and Pmax under standard test conditions (irradiance of 1KW/m2, AM 1.5 spectrum, and cell temperature of 25℃).
・Under certain conditions, a photovoltaic module is likely to produce more current and / or voltage than reported at standard test conditions. Accordingly, the values of Isc and Voc marked on this module should be multiplied by a factor of 1.25 when determining component voltage ratings, conductor ampacities, fuse sizes, and sizes of regulators which are connected to the PV output. Refer to Section
MANUFACTURED IN JAPAN BY KYOCERA CORPORATION
KSI GROUP
Kyocera Solar Inc. (Headquarters)
7812 East Acoma Drive, Scottsdale, AZ 85260, USA Tel: (480)
Fax: (480)
Kyocera Solar Pty, Ltd.
36 Windorah St., Unit 6 Stafford 4053 Queensland, Australia Tel: (61)
Fax: (61)
Kyocera Solar Argentina S.A.
Mejico 2145, 16400 Martinez Prov. de Buenos Aires Argentina Tel: (54)
Fax: (54)
Kyocera Solar Do Brazil
Rua Mauricio da Costa Faria, 85
Fax: (55)
KFG GROUP
Kyocera Fineceramics GmBH
Fritz Müller Strasse 107,
Fax: (49)
KAP GROUP
Kyocera Asia Pacific Singapore
Fritz Müller Strasse 107,
298 Tiong Bahru Road,
Tel: (65)
Fax: (65)