PHYSICAL DATA
UNIT SIZE | |||||||
Operating Weight lb (kg) | 195 (88.4) | 184 (83.5) | 177 (80.3) | 225 (102.1) | 228 (103.4) | 270 (122.5) | 337 (152.9) |
Shipping Weight lb (kg) | 223 (101.2) | 223 (101.2) | 218 (98.9) | 259 (117.5) | 267 (121.1) | 303 (137.4) | 372 (168.7) |
Compressor Type |
|
|
| Scroll |
|
|
|
REFRIGERANT |
|
|
| Puron→ |
|
| |
Control |
|
| TXV (Puron→ Hard Shutoff) |
|
| ||
Charge lb (kg) | 5.4 (2.45) | 5.48 (2.49) | 5.8 (2.63) | 6.97 (3.16) | 9.5 (4.31) | 11 (4.99) | 13.3 (6.03) |
COND FAN |
|
| Propeller Type, Direct Drive |
|
| ||
Air Discharge |
|
|
| Vertical |
|
|
|
Air Qty (CFM) | 2235 | 3223 | 3223 | 3810 | 3810 | 3810 | 4050 |
Motor HP | 1/12 | 1/12 | 1/12 | 1/5 | 1/5 | 1/5 | 1/4 |
Motor RPM | 800 | 800 | 800 | 800 | 800 | 800 | 800 |
COND COIL |
|
|
|
|
|
|
|
Face Area (Sq ft.) | 19.40 | 17.60 | 17.60 | 22.63 | 17.60 | 20.12 | 30.18 |
Fins per In. | 25 | 25 | 25 | 25 | 20 | 20 | 20 |
Rows | 1 | 1 | 1 | 1 | 2 | 2 | 2 |
Circuits | 3 | 4 | 4 | 5 | 7 | 7 | 7 |
VALVE CONNECT. (In. ID) |
|
|
|
|
|
|
|
Vapor | 5/8 | 5/8 | 3/4 | 3/4 | 7/8 | 7/8 | 7/8 |
Liquid |
|
|
| 3/8 |
|
|
|
REFRIGERANT TUBES (In. OD) |
|
|
|
|
|
|
|
Rated Vapor* |
| 5/8 |
| 3/4 |
| 7/8 | |
Liquid |
|
|
| 3/8 |
|
|
|
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
| LONG LINE APPLICATION: An application is considered | vertical separation is 200 ft. (60.96 m) when outdoor unit is | |||||||||||
| ”Long line” when the total equivalent tubing length exceeds 80 | above indoor unit, and up to 80 ft. (24.38 m) when the outdoor | |||||||||||
| ft. (24.38 m) or when there is more than 20 ft. (6.09 m) vertical | unit is below the indoor unit. Refer to Accessory Usage Guideline | |||||||||||
| separation between indoor and outdoor units. These applications | below for required accessories. See Longline Application | |||||||||||
| require additional accessories and system modifications for | Guideline for required piping and system modifications. Also, | |||||||||||
| reliable system operation. The maximum allowable total | refer to the table below for the vapor tube diameters based on the | |||||||||||
| equivalent | length is up | to 250 ft. | (76.2 m). | The maximum | total length to minimize the cooling capacity loss. |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Cooling Capacity Loss (%) |
|
|
| ||
| Unit | Maximum | Vapor Line |
|
|
|
| Total Equivalent Line Length ft. (m) |
|
|
| ||
| Nominal | Liquid Line |
| Standard |
|
|
|
|
|
|
| ||
| Diameters |
|
| Long Line Application Requires Accessories |
| ||||||||
| Size | Diameters |
| Application |
|
| |||||||
| (Btuh) | (In. OD) | (In. OD) |
|
|
|
|
|
|
|
| ||
|
|
|
| ||||||||||
|
|
|
|
| |||||||||
|
|
|
|
| |||||||||
| 18000 |
| 1/2 |
| 1 | 2 | 3 | 4 | 6 | 7 | 8 | 9 | 10 |
| 1 Stage | 3/8 |
| ||||||||||
| 5/8 |
| 0 | 0 | 1 | 1 | 1 | 2 | 2 | 3 | 3 | ||
| Puron AC |
|
| ||||||||||
| 24000 |
| 5/8 |
| 0 | 1 | 1 | 2 | 3 | 3 | 4 | 4 | 5 |
| 1 Stage | 3/8 | 3/4 |
| 0 | 0 | 0 | 0 | 1 | 1 | 1 | 1 | 1 |
| Puron AC |
| 7/8 |
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 30000 |
| 5/8 |
| 1 | 2 | 3 | 3 | 4 | 5 | 6 | 7 | 8 |
| 1 Stage | 3/8 | 3/4 |
| 0 | 0 | 1 | 1 | 1 | 2 | 2 | 2 | 3 |
| Puron AC |
| 7/8 |
| 0 | 0 | 0 | 0 | 1 | 1 | 1 | 1 | 1 |
| 36000 |
| 5/8 |
| 1 | 2 | 4 | 5 | 6 | 7 | 9 | 10 | 11 |
| 1 Stage | 3/8 | 3/4 |
| 0 | 0 | 1 | 1 | 2 | 2 | 3 | 3 | 4 |
| Puron AC |
| 7/8 |
| 0 | 0 | 0 | 0 | 1 | 1 | 1 | 1 | 2 |
| 42000 |
| 3/4 |
| 0 | 1 | 2 | 2 | 3 | 4 | 4 | 5 | 6 |
| 1 Stage | 3/8 | 7/8 |
| 0 | 0 | 1 | 1 | 1 | 2 | 2 | 2 | 3 |
| Puron AC |
| 1 1/8 |
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 48000 |
| 3/4 |
| 0 | 1 | 2 | 3 | 4 | 5 | 5 | 6 | 7 |
| 1 Stage | 3/8 | 7/8 |
| 0 | 0 | 1 | 1 | 2 | 2 | 2 | 3 | 3 |
| Puron AC |
| 1 1/8 |
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 |
| 60000 |
| 3/4 |
| 1 | 2 | 4 | 5 | 6 | 7 | 9 | 10 | 11 |
| 1 Stage | 3/8 | 7/8 |
| 0 | 1 | 2 | 2 | 3 | 4 | 4 | 5 | 5 |
| Puron AC |
| 1 1/8 |
| 0 | 0 | 0 | 1 | 1 | 1 | 1 | 1 | 1 |
| Applications | in this area are | long line. Accessories are required as shown recommended on Long Line Application Guidelines |
|
| ||||||||
| Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit | See Long Line Applica- | |||||||||||
| tion Guidelines |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
124A
3