Greenheck Fan QEID manual Specifications, Model QEI-L, QEI-I/II and Qeid

Page 52

Specifications

Model QEI-L, QEI-I/II and QEID

Supply, exhaust, or return air fans shall be of the inline mixed flow type.

The housing shall be constructed of welded heavy-gauge steel to assure no air leakage. Housing shall have inlet and outlet collars for slip-fit duct connections. The housing and bearing and/or motor supports shall be constructed of heavy-gauge steel members to prevent vibration and rigidly support the shaft and bearings. Welded steel vanes shall straighten the flow of air from the fan discharge.

All QEI-L and QEI-I/II units up through size 27 shall incorporate a universal mounting system that allows the fan to be mounted in either vertical or horizontal configurations and field rotation of the motor position in

90 degree increments. Bearing life shall not be reduced below specified level in different configurations. QEI-I/II units size 30 and larger shall allow for field rotation of motor positions. Units shall accommodate base mount or ceiling hung mounting without structural modifications to the fan.

The wheel shall be of the mixed flow type. Wheels shall have a wheel cone, spherical back plate and single thickness cambered blades. Wheels shall be statically and dynamically balanced to balance grade

G6.3 per ANSI S2.19. The wheel cone and fan inlet cone shall be carefully matched and shall have precise running tolerances for maximum performance and operating efficiency.

Each assembled fan shall be test run at the factory at the specified fan RPM. The

maximum allowable fan vibration shall be

0.15in/sec. peak velocity, filter-in for QEI-I/II with signatures taken on each bearing in three planes; horizontal, vertical, and axial. Maximum vibration of 0.08 in/sec. peak velocity, filter-in for QEID in a single plane on the fan housing. This report shall be provided at no charge to the customer upon request.

Inlet and outlet sound power levels shall be provided for each of the eight octave bands at the point of operation.

Fans shall be licensed to bear the AMCA Seal for Sound and Air Performance.

Mixed flow fans shall be Model QEI-L, QEI-I/II or QEID as manufactured by Greenheck Fan Corporation, Schofield, Wisconsin, USA and shall be supplied as shown on the plans and in the fan schedule.

Additional Belt Drive Specification

Turned, precision ground and polished steel shafts shall be sized so the first critical speed is at least 25% over the maximum operating speed. Close tolerances shall be maintained where the shaft makes contact with the bearings.

Bearings shall be heavy-duty, grease lubricated, self-aligning ball or roller type with extended lubrication lines.

QEI-I/II and QEI-L (horizontal mount) bearings shall be selected for a minimum life L10 of 80,000 (L50 of 400,000) hours at maximum operating speed. QEI-L (vertical mount) bearings shall be selected for a minimum life, L10 of 50,000 (L50 of 250,000) hours at maximum operating speed.

Our Warranty

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.

Prepared to Support Green Building Efforts

P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com

00.CVI.1018 R7 5-2012 IP Copyright © 2012 Greenheck Fan Corp.

Image 52
Contents Mixed Flow Fans Quiet & Efficient, Inline Mixed Flow FansStandard Construction Model Number NomenclatureValue Added Features Maintenance / Serviceable Construction AdvantagesQuality Assurance Test Electrostatic Powder CoatingsInlet and Outlet Sound Power Levels Field Rotatable Housing / Compact SizeSlip-Fit Duct Connections AutoCAD and 3-D Revit ModelsDesign & Performance Mixed Flow Axial/Centrifugal HybridSound and Efficiency Airflow ProfilesWheel Characteristics Sound Power versus Sound PressureBelt Drive Fan Class Direct Drive Percent Wheel WidthSound Vault Housing Radiated Sound Enclosure Optional FeaturesWhy use a Sound Vault? Optional Two-coat Paint System Zinc AdvantageCertifications & Listings Belt Drive versus Direct Drive Belt Drive AdvantagesDirect Drive Advantages Tubular Centrifugal Fan QEI-I Mixed Flow FanQEI-I/II Sizes 9-27 and all QEI-L Belt Drive Mounting ConfigurationsQEI-I/II Sizes Roof Upblast Roof Upblast & Spark Resistant ConstructionSpark Resistant Construction Accessories AvailabilityExploded View Direct Drive Selection Charts Qeid Dimensional Data 870 RPM 60 HzQEI Dimensional Data QEIQEI-9 Class Performance Data25 kW 381 mm55 kg QEI-12 Class I & QEI-L73 kg QEI-12 Class 82 kg464 mm QEI-15 Class I & QEI-L64 kg QEI-15 Class 100 kgQEI-16 Class I & QEI-L 508 mmQEI-16 Class 109 kgQEI-18 Class I & QEI-L 565 mm87 kg 118 kgQEI-18 Class 141 kg622 mm QEI-20 Class I & QEI-L105 kg QEI-20 Class 163 kgQEI-22 Class I & QEI-L 686 mm123 kg 168 kgQEI-22 Class 191 kgQEI-24 Class I & QEI-L 762 mm182 kg 213 kg55 kW QEI-24 Class249 kg QEI-27 Class I & QEI-L 838 mm214 kg 245 kgQEI-27 Class 304 kgQEI-30 Class I & QEI-L 75 kW927 mm 286 kgQEI-30 Class 454 kgQEI-33 Class I & QEI-L 1022 mm332 kg 449 kgQEI-33 Class 544 kg1130 mm QEI-36 Class I & QEI-L409 kg QEI-36 Class 635 kg1245 mm QEI-40 Class680 kg 862 kg 1378 mm QEI-44 Class907 kg 1043 kg 1524 mm QEI-49 Class1089 kg 11 kW 1406 kg1676 mm QEI-54 Class1315 kg 1633 kg 1854 mm QEI-60 Class1588 kg 1905 kg Specifications Model QEI-L, QEI-I/II and Qeid