Emerson 250, 350 operation manual Power Supply Troubleshooting, General Troubleshooting

Page 32

2.Water damage to the electronics module or sensor probe. This is potentially the most severe case the symptoms are unpredictable. If there is any suspicion that the transmitter may have incurred water damage please contact the factory to make arrangements to have the unit sent back for factory inspection.

Physical and water damage are not covered under warranty.

3.Magnetic Indentation. It is possible for any magnetostrictive instrument to have residual magnetic energy stored along the length of the waveguide. These magnetic anomalies can interfere with the output response signal. If this appears to be the case a level gage float (or a bar magnet preferably) may be run along the length of the sensor tube, past the head of the transmitter, in an even motion without stopping. This will usually clear all such magnetic anomalies.

Never move a magnet in perpendicular motion away from the sensor tube. This will always leave a residual magnetic field in the waveguide which causes the transmitter output to be erroneous or unstable.

The LTM-350 is HART compatible, however HART communication will not work if the unit is not powering up.

8.2 Power Supply Troubleshooting

The LTM-250/350 is designed to operate with a supply voltage of 13 – 36 Vdc (minimum 13V @ 20mA) across its terminal without affecting the analog current output. The most common supply voltage used is 24Vdc.

At times additional resistance in the loop is necessary, either in the form of a second load resistor or higher resistance safety barrier. This will appear to limit the maximum output of the transmitter to below 20mA. The transmitter will perform correctly up to a certain point. To resolve this problem, the voltage of the loop supply must be increased. Even a slight adjustment of 1Vdc may be sufficient.

All connections must be checked for improper wiring or polarity before power is applied. LTM- Series transmitters are polarity protected.

8.3 General Troubleshooting

Below are some troubleshooting procedures for the LTM transmitters that have been established overtime.

Symptom: Transmitter is not powering up. The LCD is not turning on.

Resolutions:

1.Make sure power is applied correctly (meaning plus and minus are not reversed). The transmitter is polarity protected.

2.Make sure the electronics module is seated properly. Open the front cover (where the LCD is) and firmly push on the “Magtech” text. A good way to tell if the electronics are not seated properly is by making sure the protection screws are not physically higher than the outside of the housing. Sometimes pulling the electronics module out and putting it back in can reseat the electronics correctly. Use cutters or needle nose pliers to grip the protection screw and lightly pull on each screw (alternate).

29

Image 32
Contents Instructions Table of Contents Icon Key LTM-350 has Hart ProtocolWarranty WarrantyTransmitter Configurations Transmitter OverviewGeneral Description Product IdentificationGage Mounted Transmitter Standalone TransmitterTransmitter with a Stilling-well Technology Theory of Operation Transmitter DescriptionDetailed Description Configuration options must be chosen at quoting stage Basic Transmitter Block DiagramInstallation Gage Mount InstallationStandalone Installation General Installation GuidelinesPossible transmitter configurations Clamps do not have to meetPage When insulating gages Insulation against extreme heat/coldField Wiring Recommended Loop WiringFollowing is the Hart Topology Area Classification Installation Safety Transmitter Specifications Electronic SpecificationsSensor Probe Specifications Hazardous Locations / General RatingsMenu Structure and Features Pushbutton OperationMenu Structure Main Screen scrollingFollowing is the LTM-250/350 LCD Menu Flowchart Menu Structure … Select Alarm Description Select PVChange Range LCD Menu examples G R n g e Select Lower Range Value LRVDescription Trim SensorOffset M S n s r F sDescription Trim Digital-Analog-Converter DAC Test LoopExit LCD Menu examples I m D a C T L o o p I t ?MA Out Or % Range FeaturesScroll or Level or Intrface Features Exclusive to the LTM-250/350 models Following is a flow chart of the advanced menusFeatures Exclusive to the LTM-250/350 models Features Exclusive to the LTM-250/350 models Features Exclusive to the LTM-250/350 models Features Exclusive to the LTM-250/350 models LTM Troubleshooting TroubleshootingTransmitter Calibration CalibrationPhysical and water damage are not covered under warranty Power Supply TroubleshootingGeneral Troubleshooting LTM-350 has Hart Protocol Hart Protocol General InformationHart Protocol Menus and Flowchart … USLWhen Interf is PV, Interf is displayed
Related manuals
Manual 32 pages 36.12 Kb

350, 250 specifications

Emerson 250 and 350 are cutting-edge products that represent a significant leap in automation technology and process control systems. Designed with a focus on versatility, reliability, and efficiency, these systems are tailored to meet the demands of various industries, including manufacturing, oil and gas, and chemical processing.

One of the standout features of the Emerson 250 and 350 is their advanced control algorithms. These algorithms enable precise control of processes, allowing for enhanced stability and improved operational efficiency. By optimizing real-time decision-making, the systems can adapt to variable operating conditions, thereby reducing downtime and enhancing productivity.

The Emerson 250 and 350 are equipped with intuitive user interfaces that streamline operation and monitoring. These interfaces provide operators with easy access to critical data and insights, facilitating informed decision-making. The systems’ graphical displays and touch-screen capabilities enhance user experience, making it easier to configure settings and respond to alerts promptly.

Moreover, both models are built with robust communication protocols, ensuring seamless integration with existing infrastructure. This adaptability enables businesses to leverage their current investments in technology while expanding their automation capabilities. The systems support various communication standards, including OPC, Ethernet/IP, and Modbus, ensuring they can connect effortlessly to other devices and databases.

Another key characteristic of the Emerson 250 and 350 is their scalability. Designed to grow alongside a business, these systems can be expanded or modified to accommodate increasing operational demands. This flexibility is critical in today's fast-paced industrial environment, where agility and responsiveness are paramount.

In terms of reliability, the Emerson 250 and 350 boast rugged designs that withstand the harsh conditions often present in industrial settings. With features like enhanced environmental resistance and fail-safe mechanisms, these systems ensure continuous operation and minimize the risk of failures, providing peace of mind for operators.

In summary, the Emerson 250 and 350 stand out with their advanced control algorithms, user-friendly interfaces, robust communication capabilities, scalability, and reliability. These characteristics make them ideal solutions for businesses aiming to improve automation and process control while adapting to the ever-evolving demands of the industrial sector.