8.To ensure proper blade assembly, make sure the label on the blades are facing the bottom of the ceiling fan. Slide blade through center slot in fan housing. Mount blade to fan housing using three
MOTOR HUB
BLADE SLOT
IN HOUSING
FAN BLADE
LABEL
Figure 5(LOCATED ON BOTTOM OF BLADE)
NOTE: Take care not to scratch fan housing when installing blades.
9.Remove two of the four screws in the motor assembly and loosen the remaining two screws (Figure 6).
10.Connect the terminals of the lower housing assembly to the terminals of the fan motor assembly (Figure 6).
Electrical Requirements
Your new ceiling fan will require a grounded electrical supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and capable of withstanding a load of at least 50 pounds.
! WARNING
To reduce the risk of fire, electric shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
If your fan is to replace an existing ceiling light fixture, turn electricity off at the main fuse box at this time and remove the existing light fixture.
! WARNING
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
FUSE AND
FUSE HOLDER
Figure 6
LOWER
HOUSING
ASSEMBLY
TERMINALS
FAN MOTOR
ASSEMBLY
REMOVE
2 SCREWS
LOOSEN
2 SCREWS
! WARNING
To avoid fire or shock, follow all wiring instructions carefully.
Any electrical work not described in these instructions should be done or approved by a licensed electrician.
How to Hang Your
Ceiling Fan
! WARNING
11.Attach the lower housing assembly to the fan motor using the two key slot holes. (Figure 7). Secure the lower housing assembly by tightening the two screws. Reinstall the two screws that were removed.
NOTE: Make sure wires and terminals are positioned in raised center area of lower housing assembly, and not pinched between fan and light kit.
The fan must be hung with at least 7' of clearance from floor to blades (Figure 8).
CEILING
AT LEAST
7'
SCREWS (2)
RAISED CENTER AREA OF LIGHT KIT HOUSING
LOWER
HOUSING
ASSEMBLY
KEY
SLOT
HOLE (2)
Figure 8 | FLOOR |
! WARNING
The outlet box and joist must be securely mounted and capable of supporting at least 50 lbs. Use only a U.L. outlet box listed as “Acceptable for Fan Support”.
Figure 7 | 5 | U.L. Model No.: CF955 |
|