Dimplex LIK 8MER manual Start-UP, Preparation, Start-Up Procedure

Page 8

7

English

7 Start-UP

7.1General Information

To ensure that start-up is performed correctly, it should only be carried out by an after-sales service technician authorised by the manufacturer. This may be a condition for extending the guaran- tee (see Warranty Service). Start-up should be carried out in heating operation.

7.2Preparation

The following items need to be checked prior to start-up:

„All of the heat pump connections must be established as de- scribed in Chapter 6.

„All valves that could impair the proper flow of the heating water in the heating circuit must be open.

„The air intake and air outlet paths must be clear.

„The ventilator must turn in the direction indicated by the ar- row.

„The heat pump controller must be adapted to the heating system in accordance with the controller's operating instruc- tions.

„Ensure the condensate outflow functions.

„The outflow from the heating water pressure relief valve must also function correctly.

„De-aeration of the heating system:

Ensure that all heating circuits are open and the heat circu- lating pump is operating (level III).

Connect the voltage to the heat pump controller. Select the heat generator 2 operating mode and de-aerate the system at its highest point. Top up with water if required (maintain static minimum pressure).

Heat source

Max. temperature spread

temperature

between heating flow and return

From

To

flow

-20 °C

-15 °C

4 K

 

 

 

-14 °C

-10 °C

5 K

-9 °C

-5 °C

6 K

 

 

 

-4 °C

0 °C

7 K

1 °C

5 °C

8 K

 

 

 

6 °C

10 °C

9 K

11 °C

15 °C

10 K

 

 

 

16 °C

20 °C

11 K

21 °C

25 °C

12 K

 

 

 

26 °C

30 °C

13 K

31 °C

35 °C

14 K

 

 

 

Any faults occurring during operation are also displayed on the heat pump controller and can be corrected as described in the operating instructions of the heat pump controller.

For external temperatures below 10 °C and heating water tem- peratures below 16 °C, the buffer tank should be heated up with the 2nd heat generator to at least 25 °C.

Observe the following procedure to implement a smooth start-up:

1)Close all of the heating circuits.

2)Fully open the overflow valve.

3)Use the controller to select the automatic operating mode.

4)Wait until the buffer tank has reached a temperature of at least 25 °C.

5)Now slowly reopen the heating circuit valves in succession so that the heating water throughput is constantly raised by slightly opening the respective heating circuit. The heating water temperature in the buffer tank must not be allowed to drop below 20 °C during this process. This ensures that the heat pump can be defrosted at any time.

7.3Start-Up Procedure

The heat pump is started up via the heat pump controller. Adjust- ments should be made in compliance with the instructions.

The performance level of the circulating pump must be adapted to the respective heating system.

The overflow valve must be adjusted to the requirements of the respective heating system. Incorrect adjustment can lead to faulty operation and increased energy consumption. We recom- mend carrying out the following procedure to correctly adjust the overflow valve:

Close all of the heating circuits that may also be closed during operation (depending on the type of heat pump usage) so that the most unfavourable operating state - with respect to the water flow rate - is achieved. This normally means the heating circuits of the rooms on the south and west sides of the building. At least one heating circuit must remain open (e.g. bathroom).

The overflow valve should be opened far enough to produce the maximum temperature spread between the heating flow and re- turn flow listed in the following table for the current heat source temperature. The temperature spread should be measured as close as possible to the heat pump. The heating element of mono energy systems should be disconnected.

6)Set the minimum volume flow quantity on the overflow valve and heat circulating pump when all heating circuits are fully open and a heating water temperature in the buffer tank of approx. 20 °C is maintained.

7)New buildings have an increased heat consumption on ac- count of the energy required to dry them out. This increased heat consumption means that marginally dimensioned heat- ing systems can not always achieve the desired room tem- perature. In such cases, we recommend keeping a 2nd heat generator on standby during the first heating period. The limit temperature on the heat pump controller should also be turned up to 15 °C.

E-7

Image 8
Contents LIK 8MER Table of contents Please Read Immediately Important InformationLegal Regulations Directives Energy-Efficient Use Heat PumpPurpose of the Heat Pump Scope of DeliveryApplication Operating PrincipleTransport Switch BoxAccessories Pack Installation Set-UPHeating System Connection Electrical ConnectionPreparation Start-Up ProcedureStart-UP Decommissioning/ Disposal Maintenance / CleaningFaults / Trouble- Shooting Device Information Type and order code DesignMaßbilder / Dimension Drawings / Schémas cotés Anhang / Appendix / AnnexesSchémas cotés Maßbilder / DimensionDrawings Einbaumaße / Installation Dimensions / Cotes de montage AnhangDiagramme / Diagrams / Diagrammes Heizbetrieb / Heating Operation / Mode chauffageKühlbetrieb / Cooling Operation / Mode refroidissement HGLQJXQJHQÂ&RQGLWLRQVÂ&RQGLWLRQVStromlaufpläne / Circuit Diagrams / Schémas électriques VII Last / Load / Charge Anhang · Appendix · Annexes HXFKWH +XPLGLW\ +XPLGLWp Gruppe K12 Elektron. Relais f. Schwimmbadwasserumwälz XII Darstellung / Schematic view / Représentation XiiiXIV Anhang · Appendix · Annexes

LIK 8MER specifications

The Dimplex LIK 8MER is a cutting-edge electric radiator that combines modern technology with stylish design. Designed to provide efficient warmth and comfort in residential settings, this heating solution stands out for its user-friendly features and high performance.

One of the main characteristics of the LIK 8MER is its advanced electronic control system, which promotes efficient energy usage. This system allows for precise temperature management, ensuring that your living space remains comfortable without excessive energy consumption. The radiator can be programmed to suit your lifestyle, with options to set different temperature levels for various times of the day or week.

The LIK 8MER is equipped with Dimplex’s unique Duo Heat technology, which enhances heat distribution throughout the room. This technology combines convection heating and thermal storage, allowing the radiator to store heat and release it gradually, ensuring consistent warmth. As a result, users experience a more stable and comfortable environment, devoid of the cold drafts often associated with traditional heating systems.

Another key feature of the Dimplex LIK 8MER is its sleek design. The radiator's minimalist aesthetic allows it to seamlessly integrate into any home décor, making it an attractive addition to both modern and traditional interiors. Available in various sizes, the LIK 8MER can easily fit in different spaces, whether it’s a living room, bedroom, or hallway.

In terms of safety, the LIK 8MER is designed with multiple features to ensure peace of mind for users. It includes overheat protection, which automatically turns off the radiator if it gets too hot, preventing any risk of fire. Furthermore, its surface temperature is kept at safe levels, making it suitable for homes with children or pets.

Additional technologies include a built-in timer and an intelligent learning function. The timer allows users to set the radiator to turn on or off according to their schedule, while the learning function adapts to the user’s habits, optimizing energy use based on past behavior.

Overall, the Dimplex LIK 8MER electric radiator is a perfect blend of technology, efficiency, and style. Its innovative features and thoughtful design make it a practical choice for anyone seeking to enhance their home heating experience. Whether you are aiming to save on energy bills or simply seeking reliable warmth, the LIK 8MER delivers on all fronts.