Dimplex SI 75ZSR manual Connection on Heating Side, Electrical Connection

Page 6

7.4

7.2Connection on Heating Side

ATTENTION!

The heating system must be flushed prior to connecting the heat pump.

Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to re- move any impurities that may be present, as well as residues of sealing material, and the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.

ATTENTION!

The supplied strainer must be fitted in the heating water inlet of the heat pump in order to protect the condenser against the ingress of impurities.

Once the installation on the heating side has been completed, the heating system must be filled, de-aerated and pressure- tested.

Heating water minimum flow rate

The heating water minimum flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing a differential pressure-free manifold or an overflow valve. The procedure for setting an overflow valve is described in the Chapter Commis- sioning.

Frost protection for installations prone to frost

Provided the controller and heating circulating pumps are ready for operation, the frost protection feature of the controller is ac- tive. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. In heat pump instal- lations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.

7.4Electrical Connection

The following electrical connections must be established on the heat pump:

„Connection of the control wire to terminals X1: L/N/PE in the control box of the heat pump.

„Connection of the load wire to terminals X5: L1/L2/L3/PE in the control box of the heat pump.

„Connection of the brine pump (to be supplied by the cus- tomer) to terminal PE and pump contactor K5: 2/4/6 on the control panel of the HP.

All electrical components required for the operation of the heat pump are located in the control box.

For more detailed instructions concerning the connection and functioning of the heat pump controller (e.g. the supplied external wall sensor) please refer to the enclosed operating manual of the controller.

An automatic circuit-breaker with simultaneous tripping of all ex- ternal conductors is to be provided in the load power supply. The circuit-breaker must be an all-pole disconnect device with a con- tact gap of at least 3 mm. The same applies to any additional dis- able contactors that may be required, e.g. during shut-off periods imposed by the utility company. The required cross-sectional area of the conductors is to be selected according to the power consumption of the heat pump, the technical connection require- ments of the relevant utility company and all applicable regula- tions. Power consumption data of the heat pump is provided in the product literature and on the nameplate. The terminals are designed for a max. conductor cross-section of 35 mm².

ATTENTION!

The clockwise phase sequence must be observed when connecting the load lines (the heat pump will deliver no output and will be very noisy when the phase sequence is incorrect).

English

7.3Connection on Heat Source

Side

The following procedure must be observed when making the connection:

Connect the brine line to the flow and return pipe of the heat pump.

The hydraulic plumbing diagram must be observed here.

ATTENTION!

The supplied strainer must be fitted in the heat source inlet of the heat pump in order to protect the evaporator against the ingress of impurities.

In addition, a microbubble deaerator must be installed in the heat source system.

The brine liquid must be produced prior to charging the system. The brine concentration must be at least 25 %. Freeze protection down to -14°C can thus be ensured.

Only antifreeze products on the basis of mono-ethylene glycol or propylene glycol may be used.

The heat source system must be vented (de-aerated) and checked for leaks.

ATTENTION!

The brine solution must contain at least 25 % of an antifreeze agent on a mono-ethylene glycol or propylene glycol basis and must be mixed prior to filling.

The power cable must be run through the guide tubes, inserted into the side of the control box and secured by means of the strain relief.

www.dimplex.de

E-5

Image 6
Contents SI 75ZSR Table of contents Legal Provisions Guidelines Read immediatelyImportant Information Energy-Efficient Use Heat PumpApplication Purpose of the heat pumpBaseline Unit Principle of OperationTransport AccessoriesInstallation MountingConnection on Heating Side Electrical ConnectionConnection on Heat Source Side Commissioning Procedure CommissioningPreparatory Steps Care/Cleaning Malfunctions / TroubleshootingDecommissioning / Disposal Device Information Performance dataAnhang / Appendix / Annexes IIIMaßbild / Dimension drawing / Schéma coté  Diagramme / Schematics / Diagrammes Heizbetrieb / Heating operation / Mode chauffageKühlbetrieb / Cooling operation / Mode refroidissement RQFWLRQQHPHQWjFRPSUHVVHXUStromlaufpläne / Wiring diagrams / Schémas électriques Anhang · Appendix · Annexes Last / Load / Charge Anschlussplan Standardregler Anhang · Appendix · Annexes EJP Abkürzungen Abbreviations Darstellung / Schematic view / Représentation schématique XIIXiii XIV

SI 75ZSR specifications

The Dimplex SI 75ZSR is an innovative and highly efficient heater designed to meet the modern heating needs of residential spaces. Renowned for its sleek design and advanced technologies, the SI 75ZSR is a popular choice for homeowners seeking both functionality and aesthetic appeal.

One of the standout features of the Dimplex SI 75ZSR is its impressive energy efficiency. The unit operates using a highly efficient heating element that ensures rapid warmth without excessive energy consumption. This efficiency translates to lower energy bills and a reduced carbon footprint, making it an environmentally friendly option for heating.

The SI 75ZSR employs advanced heating technologies, including a built-in thermostat that allows users to maintain their desired temperature with precision. This thermostat can intelligently adjust the heater's output based on the room's conditions, ensuring that energy is not wasted in an attempt to maintain warmth in adequately heated spaces.

Another key characteristic of the Dimplex SI 75ZSR is its user-friendly interface, which includes intuitive controls for temperature settings and timer functions. This feature allows users to program the heater to operate only when needed, further enhancing energy savings.

Furthermore, the unit is equipped with innovative safety features, such as overheat protection and a tip-over switch, which automatically shuts off the heater if it is knocked over. These safety measures provide peace of mind for users, particularly in households with children or pets.

The design of the SI 75ZSR is also noteworthy. It boasts a modern and stylish appearance that can seamlessly blend into various interior decors. Available in multiple colors and finishes, the heater can serve as a functional piece while complementing the overall aesthetics of a room.

Installation is made easy with the Dimplex SI 75ZSR, as it is lightweight and can be mounted on walls or placed on the floor, allowing for flexibility in placement. Its compact size makes it suitable for both large and small spaces, whether it's a cozy living room or a spacious bedroom.

In summary, the Dimplex SI 75ZSR stands out for its efficiency, advanced heating technologies, user-friendly controls, safety features, and modern design. It is an ideal solution for those looking to heat their homes comfortably and sustainably.