Carrier 50VT-A Outdoor Coil, Indoor Coil, and Condensate Drain Pan, Outdoor Fan, Indoor Airflow

Page 26

50VT-- A

Step 2 — Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.

The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.

Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.

Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a plumbers snake or similar probe device.

Step 3 — Outdoor Fan

Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit. Damage to unit may result.

1.Remove 6 screws holding outdoor grille and motor to top cover.

2.Turn motor/grille assembly upside down on top cover to expose fan blade.

3.Inspect the fan blades for cracks or bends.

4.If fan needs to be removed, loosen setscrew and slide fan off motor shaft.

5.When replacing fan blade, position blade back to same posi- tion as before.

6.Ensure that setscrew engages the flat area on the motor shaft when tightening.

7.Replace grille.

Step 4 — Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.

Remove access panels (see Fig 22) to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any discolored or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.

After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.

Step 5 — Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak.

If oil is detected or if low performance is suspected, leak-test all refrigerant tubing using an electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.

If no refrigerant leaks are found and low performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.

Step 6 — Indoor Airflow

The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply-air and return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to Indoor Airflow and Airflow Adjustments section to check the system airflow.

Step 7 — Metering Devices-TXV & Piston

This unit uses 2 types of metering devices. The outdoor metering device is a fixed orifice and is contained in the brass hex-body in each liquid line feeding the outdoor coils. The indoor metering device is a TXV type device.

C99097

Fig. 20 - Refrigerant Circuit

Control

Blower Access

Access Panel

Compressor Panel

Access Panel

A09214

Fig. 21 - Unit Access Panels

26

Image 26
Contents Table of Contents Safety ConsiderationsCheck Equipment Receiving and InstallationIntroduction Provide Unit Support50VT-A24-30 Unit Dimensions 50VT-A36-60 Unit Dimensions Large Curb Rigging/Lifting of Unit See Fig Rig and Place UnitInspection Unit Falling HazardSelect and Install Ductwork Personal Injury HazardHigh-Voltage Connections Install Electrical ConnectionsProvide for Condensate Disposal Unit Component Damage HazardStandard Connections Special Procedures for 208-V OperationAccessory Electric Heaters Installation Control Voltage ConnectionsPhysical Data Unit 50VT-A Minimum Airflow for Reliable Electric Heater Operation CFMConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 50VT a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Check for Refrigerant Leaks Start-Up AdjustmentsSTART-UP Checking Cooling and Heating Control OperationTwo Cooling Fan Speeds Set-up Dehumidification feature used Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Unit Operation HazardColor Coding for Indoor Fan Motor Leads Single Speed Cooling With Higher Electric Heat SpeedContinuous Fan Operation Defrost Defrost ControlQuiet Shift Dry Coil Air Delivery Downflow Discharge Horizontal and Downflow Filter Pressure Drop Table IN. W.CElectric Heat Pressure Drop Table in. W.C Small Cabinet Electric Heat Pressure Drop Table in. W.C Large CabinetIndoor Blower and Motor MaintenanceAir Filter Personal Injury and Unit Damage HazardCooling Charging Table-Subcooling OF2 Outdoor Fan Electrical Controls and WiringOutdoor Coil, Indoor Coil, and Condensate Drain Pan Refrigerant CircuitHigh-Pressure Switch Pressure SwitchesLoss of Charge Switch Copeland Scroll Compressor Puron RefrigerantSystem Information TroubleshootingSTART-UP Checklist Puronr R-410A Quick Reference Guide Troubleshooting Chart Symptom Cause RemedyPreliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 50VT---09SI
Related manuals
Manual 6 pages 26.5 Kb

50VT-A specifications

Carrier’s 50VT-A and 50EZ-A series exemplify cutting-edge advancements in heating, ventilation, and air conditioning (HVAC) technology. These products are engineered to meet diverse climate control needs in residential and commercial applications while ensuring operational efficiency and superior indoor air quality.

The Carrier 50VT-A series stands out with its variable-speed technology, which allows for precise temperature control by adjusting the cooling or heating output based on current demand. This capability not only optimizes energy consumption but also enhances comfort by eliminating temperature swings. The 50VT-A units are equipped with hybrid heat technology, which enables seamless integration with alternative heating sources, providing flexibility in energy use.

On the other hand, the Carrier 50EZ-A offers a unique solution for those seeking efficient and reliable climate control in a more compact design. This series incorporates advanced inverter technology, which continuously adjusts the compressor speed, ensuring that the system operates at the utmost efficiency regardless of environmental conditions. The result is significant energy savings and quieter operation compared to traditional units.

Both series feature intelligent refrigerant management, utilizing R-410A refrigerant, which is environmentally friendly and designed to reduce greenhouse gas emissions. The systems are engineered with robust insulation and sound-dampening materials, minimizing noise levels for a peaceful indoor environment.

In addition to their impressive technical specifications, the Carrier 50VT-A and 50EZ-A units come equipped with smart controls, allowing users to monitor and adjust settings remotely through mobile applications. This connectivity feature empowers homeowners and businesses to manage energy consumption, set schedules, and receive maintenance alerts, ensuring optimal performance at all times.

Durability is an important characteristic of both series, as they are designed to withstand various environmental conditions. With corrosion-resistant coatings and high-grade materials, these units promise longevity and reliable performance over their operational lifespan.

In summary, Carrier’s 50VT-A and 50EZ-A series offer an innovative blend of efficiency, advanced technology, and user-friendly features. Whether for residential or commercial applications, these systems provide exceptional comfort, lower energy costs, and an environmentally conscious choice for modern HVAC solutions.