Carrier 50VT-A Standard Connections, Special Procedures for 208-V Operation

Page 9

HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

3-PHASE SHOWN

1-PHASE USES

TWO POWER

EQUIP GR

LEADS

CONTROL BOX

POWER

SUPPLY

FIELD-SUPPLIED FUSED DISCONNECT

control voltage wires), use no. 16 AWG color-coded, insulated (35° C minimum) wires.

Standard Connections

Locate the eight (nine on 3-phase) low voltage thermostat leads in 24 volt splice box. See Fig. 10 for connection diagram. Run the low-voltage leads from the thermostat, through the control wiring inlet hole grommet (Fig. 2 and 3), and into the low-voltage splice box. Provide a drip loop before running wires through panel. Secure and strain relief all wires so that they do not interfere with

LOW-VOLTAGE POWER LEADS (SEE UNIT)

WIRING LABEL

SPLICE BOX

WHT(W1)

W1

 

VIO (W2)

W2

 

YEL(Y)

Y

 

GRN(G)

G

 

RED(R)

R

 

BRN(C)

C

 

ORN(O)

O

 

BLU(DH)

DH

 

GRA(Y2)

3-Phase

 

 

Only

THERMOSTAT (TYPICAL)

operation of unit. A gray wire is standard on 3-phase units for connection to an economizer.

If an accessory electric heater is installed, low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 connector.

NOTE: If the unit 24V wires do not have a matching receptacle, cut the 24V wires from the electric heater plug, strip the ends, and wire nut together to match the schematic connections. If the electric heater 24V wires do not have a matching plug, cut the 24V wires from the unit receptacle, strip the ends, and wire nut together to match the schematic connections.

50VT-- A

A09071

Fig. 10 - High- and Control-Voltage Connections

Single phase units:

1.Run the high-voltage (L1, L2) and ground lead into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the line side of the contactor.

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

5.Connect field wire L2 to yellow wire on connection 23 of the compressor contactor.

Three-phase units:

1.Run the high-voltage (L1, L2, L3) and ground lead into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the line side of the contactor.

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

5.Connect field wire L3 to yellow wire on connection 13 of the compressor contactor.

6.Connect field wire L2 to blue wire from compressor.

Special Procedures for 208-V Operation

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing or servicing system, always turn off main power to system. Tag the disconnect switch with a suitable warning label. With disconnect switch open, move black wire from transformer (3/16 in.) terminal marked 230 to terminal marked 208. This retaps transformer to primary voltage of 208 vac.

Control Voltage Connections

NOTE: Do not use any type of power-stealing thermostat. Unit control problems may result.

Use no. 18 American Wire Gage (AWG) color-coded, insulated (35°C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as measured along the

Factory wires are provided for electric heat staging W1 and W2 (W2 and W3 on IFB). If room thermostat has only one stage of supplemental heat, connect white and violet wires shown in Fig. 10 to second stage heat field wire.

Some electric heaters have four control wires (plus common wire). Consult unit wiring diagram and electric heater wiring diagram for additional details.

Transformer Protection

The transformer is of the energy-limiting type. It is set to withstand a 30-second overload or shorted secondary condition. If an overload or short is present, correct overload condition and check for blown fuse on Interface Fan Board. Replace fuse as required with correct size and rating.

Accessory Electric Heaters Installation

Electric heaters may be installed with the 50VT-A units per instructions supplied with electric heater package. See unit rating plate for factory-approved electric heater kits.

Sequence of Operation

a. CONTINUOUS FAN

(1.) Thermostat closes circuit R to G energizing the blower motor for continuous fan.

b. COOLING MODE

(1.) If indoor temperature is above temperature set point, thermostat closes circuits R to G, R to Y and

Rto O-The unit delivers cooling airflow.

c.ELECTRIC HEATING MODE

(1.) Thermostat closes circuit R to W/W1, or W2 and R to G. There are no on or off delays.

d.HEAT PUMP HEATING MODE

(1.) Thermostat closes circuits R to G and R to Y. The compressor, indoor and outdoor fans are energized.

e.HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT

(1.) Thermostat closes circuits R to G, R to Y and R to W/W1 or W2. The compressor, indoor and outdoor fans are energized, as well as the electric heat relays.

f.DEFROST MODE

The defrost mode is automatically energized by the defrost board during heating mode. The defrost board energizes “O” (reversing valve) and “W2” (electric heat). It also de-energizes the outdoor fan. When defrost is complete, unit will return to heating mode. If room thermostat is satisfied during defrost, unit will shut down and restart in defrost on next call for heat.

9

Image 9
Contents Safety Considerations Table of ContentsIntroduction Receiving and InstallationCheck Equipment Provide Unit Support50VT-A24-30 Unit Dimensions 50VT-A36-60 Unit Dimensions Large Curb Inspection Rig and Place UnitRigging/Lifting of Unit See Fig Unit Falling HazardPersonal Injury Hazard Select and Install DuctworkProvide for Condensate Disposal Install Electrical ConnectionsHigh-Voltage Connections Unit Component Damage HazardAccessory Electric Heaters Installation Special Procedures for 208-V OperationStandard Connections Control Voltage ConnectionsMinimum Airflow for Reliable Electric Heater Operation CFM Physical Data Unit 50VT-AConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 50VT a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram START-UP Start-Up AdjustmentsCheck for Refrigerant Leaks Checking Cooling and Heating Control OperationIndoor Airflow and Airflow Adjustments Checking and Adjusting Refrigerant ChargeTwo Cooling Fan Speeds Set-up Dehumidification feature used Unit Operation HazardSingle Speed Cooling With Higher Electric Heat Speed Continuous Fan OperationColor Coding for Indoor Fan Motor Leads Defrost Control Quiet ShiftDefrost Horizontal and Downflow Filter Pressure Drop Table IN. W.C Dry Coil Air Delivery Downflow DischargeElectric Heat Pressure Drop Table in. W.C Large Cabinet Electric Heat Pressure Drop Table in. W.C Small CabinetAir Filter MaintenanceIndoor Blower and Motor Personal Injury and Unit Damage HazardCooling Charging Table-Subcooling OF2 Outdoor Coil, Indoor Coil, and Condensate Drain Pan Electrical Controls and WiringOutdoor Fan Refrigerant CircuitLoss of Charge Switch Pressure SwitchesHigh-Pressure Switch Copeland Scroll Compressor Puron RefrigerantTroubleshooting START-UP ChecklistSystem Information Puronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting ChartRemove and Store in Job Files TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 50VT---09SI
Related manuals
Manual 6 pages 26.5 Kb

50VT-A specifications

Carrier’s 50VT-A and 50EZ-A series exemplify cutting-edge advancements in heating, ventilation, and air conditioning (HVAC) technology. These products are engineered to meet diverse climate control needs in residential and commercial applications while ensuring operational efficiency and superior indoor air quality.

The Carrier 50VT-A series stands out with its variable-speed technology, which allows for precise temperature control by adjusting the cooling or heating output based on current demand. This capability not only optimizes energy consumption but also enhances comfort by eliminating temperature swings. The 50VT-A units are equipped with hybrid heat technology, which enables seamless integration with alternative heating sources, providing flexibility in energy use.

On the other hand, the Carrier 50EZ-A offers a unique solution for those seeking efficient and reliable climate control in a more compact design. This series incorporates advanced inverter technology, which continuously adjusts the compressor speed, ensuring that the system operates at the utmost efficiency regardless of environmental conditions. The result is significant energy savings and quieter operation compared to traditional units.

Both series feature intelligent refrigerant management, utilizing R-410A refrigerant, which is environmentally friendly and designed to reduce greenhouse gas emissions. The systems are engineered with robust insulation and sound-dampening materials, minimizing noise levels for a peaceful indoor environment.

In addition to their impressive technical specifications, the Carrier 50VT-A and 50EZ-A units come equipped with smart controls, allowing users to monitor and adjust settings remotely through mobile applications. This connectivity feature empowers homeowners and businesses to manage energy consumption, set schedules, and receive maintenance alerts, ensuring optimal performance at all times.

Durability is an important characteristic of both series, as they are designed to withstand various environmental conditions. With corrosion-resistant coatings and high-grade materials, these units promise longevity and reliable performance over their operational lifespan.

In summary, Carrier’s 50VT-A and 50EZ-A series offer an innovative blend of efficiency, advanced technology, and user-friendly features. Whether for residential or commercial applications, these systems provide exceptional comfort, lower energy costs, and an environmentally conscious choice for modern HVAC solutions.