Carrier 50VT-A installation instructions Troubleshooting Chart, Symptom Cause Remedy

Page 30

50VT-- A

Table 10 – Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

 

 

 

 

Power failure

Call power company

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

 

Defective contactor, transformer, or high--pressure,

Replace component

Compressor and condenser fan will not start.

loss--of--charge or low--pressure switch

 

 

 

 

 

Insufficient line voltage

Determine cause and correct

 

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

 

Thermostat setting too high

Lower thermostat setting below room tempera-

 

ture

 

 

 

 

 

 

Faulty wiring or loose connections in compressor cir-

Check wiring and repair or replace

 

cuit

 

 

 

 

 

Compressor will not start but condenser fan

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

runs

 

 

Defective run/start capacitor, overload, start relay

Determine cause and replace

 

 

One leg of 3--phase power dead

Replace fuse or reset circuit breaker

 

Determine cause

 

 

 

 

 

Three-phase scroll compressor

 

Correct the direction of rotation by reversing the

makes excessive noise, and there may be a

Scroll compressor is rotating in the wrong direction

3--phase power leads to the unit.

low pressure differential.

 

 

 

 

 

 

 

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

 

charge to capacities shown on rating plate

 

 

 

 

 

 

Defective compressor

Replace and determine cause

Compressor cycles (other than normally sat-

Insufficient line voltage

Determine cause and correct

Blocked condenser

Determine cause and correct

isfying thermostat).

Defective run/start capacitor, overload or start relay

Determine cause and replace

 

 

Defective thermostat

Replace thermostat

 

Faulty condenser--fan motor or capacitor

Replace

 

Restriction in refrigerant system

Locate restriction and remove

 

Dirty air filter

Replace filter

 

Unit undersized for load

Decrease load or increase unit size

 

Thermostat set too low

Reset thermostat

Compressor operates continuously

Low refrigerant charge

Locate leak, repair, and recharge

Mechanical damage in compressor

Replace compressor

 

 

Air in system

Recover refrigerant, evacuate system, and re-

 

charge

 

 

 

 

 

 

Condenser coil dirty or restricted

Clean coil or remove restriction

 

Dirty air filter

Replace filter

 

Dirty condenser coil

Clean coil

Excessive head pressure

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

 

 

charge

 

 

 

 

 

 

Condenser air restricted or air short--cycling

Determine cause and correct

 

Low refrigerant charge

Check for leaks, repair, and recharge.

Head pressure too low

Compressor IPR leaking

Replace compressor

 

Restriction in liquid tube

Remove restriction

 

High heat load

Check for source and eliminate

Excessive suction pressure

Compressor IPR leaking

Replace compressor

 

Refrigerant overcharged

Recover excess refrigerant

 

Dirty air filter

Replace filter

 

Low refrigerant charge

Check for leaks, repair and recharge

 

Metering device or low side restricted

Remove source of restriction

Suction pressure too low

Insufficient evaporator airflow

Increase air quantity

Check filter–replace if necessary

 

 

 

 

 

 

Temperature too low in conditioned area

Reset thermostat

 

Outdoor ambient below 55°F (12.7°C)

Install low--ambient kit

 

Filter drier restricted

Replace filter

30

Image 30
Contents Table of Contents Safety ConsiderationsCheck Equipment Receiving and InstallationIntroduction Provide Unit Support50VT-A24-30 Unit Dimensions 50VT-A36-60 Unit Dimensions Large Curb Rigging/Lifting of Unit See Fig Rig and Place UnitInspection Unit Falling HazardSelect and Install Ductwork Personal Injury HazardHigh-Voltage Connections Install Electrical ConnectionsProvide for Condensate Disposal Unit Component Damage HazardStandard Connections Special Procedures for 208-V OperationAccessory Electric Heaters Installation Control Voltage ConnectionsPhysical Data Unit 50VT-A Minimum Airflow for Reliable Electric Heater Operation CFMConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 50VT a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Check for Refrigerant Leaks Start-Up AdjustmentsSTART-UP Checking Cooling and Heating Control OperationTwo Cooling Fan Speeds Set-up Dehumidification feature used Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Unit Operation HazardSingle Speed Cooling With Higher Electric Heat Speed Continuous Fan OperationColor Coding for Indoor Fan Motor Leads Defrost Control Quiet ShiftDefrost Dry Coil Air Delivery Downflow Discharge Horizontal and Downflow Filter Pressure Drop Table IN. W.CElectric Heat Pressure Drop Table in. W.C Small Cabinet Electric Heat Pressure Drop Table in. W.C Large CabinetIndoor Blower and Motor MaintenanceAir Filter Personal Injury and Unit Damage HazardCooling Charging Table-Subcooling OF2 Outdoor Fan Electrical Controls and WiringOutdoor Coil, Indoor Coil, and Condensate Drain Pan Refrigerant CircuitHigh-Pressure Switch Pressure SwitchesLoss of Charge Switch Copeland Scroll Compressor Puron RefrigerantTroubleshooting START-UP ChecklistSystem Information Puronr R-410A Quick Reference Guide Troubleshooting Chart Symptom Cause RemedyPreliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 50VT---09SI
Related manuals
Manual 6 pages 26.5 Kb

50VT-A specifications

Carrier’s 50VT-A and 50EZ-A series exemplify cutting-edge advancements in heating, ventilation, and air conditioning (HVAC) technology. These products are engineered to meet diverse climate control needs in residential and commercial applications while ensuring operational efficiency and superior indoor air quality.

The Carrier 50VT-A series stands out with its variable-speed technology, which allows for precise temperature control by adjusting the cooling or heating output based on current demand. This capability not only optimizes energy consumption but also enhances comfort by eliminating temperature swings. The 50VT-A units are equipped with hybrid heat technology, which enables seamless integration with alternative heating sources, providing flexibility in energy use.

On the other hand, the Carrier 50EZ-A offers a unique solution for those seeking efficient and reliable climate control in a more compact design. This series incorporates advanced inverter technology, which continuously adjusts the compressor speed, ensuring that the system operates at the utmost efficiency regardless of environmental conditions. The result is significant energy savings and quieter operation compared to traditional units.

Both series feature intelligent refrigerant management, utilizing R-410A refrigerant, which is environmentally friendly and designed to reduce greenhouse gas emissions. The systems are engineered with robust insulation and sound-dampening materials, minimizing noise levels for a peaceful indoor environment.

In addition to their impressive technical specifications, the Carrier 50VT-A and 50EZ-A units come equipped with smart controls, allowing users to monitor and adjust settings remotely through mobile applications. This connectivity feature empowers homeowners and businesses to manage energy consumption, set schedules, and receive maintenance alerts, ensuring optimal performance at all times.

Durability is an important characteristic of both series, as they are designed to withstand various environmental conditions. With corrosion-resistant coatings and high-grade materials, these units promise longevity and reliable performance over their operational lifespan.

In summary, Carrier’s 50VT-A and 50EZ-A series offer an innovative blend of efficiency, advanced technology, and user-friendly features. Whether for residential or commercial applications, these systems provide exceptional comfort, lower energy costs, and an environmentally conscious choice for modern HVAC solutions.