0.708in.

C02017

Fig. 13—Outdoor-Fan Adjustment (060 Size)

After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumenta- tion. Refer to the unit wiring label when making these checkouts.

NOTE: Refer to the Sequence of Operation section, as an aid in determining proper control operation.

Step 7—Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrig- erant leak.

If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing using an electronic leak-detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section. (See Table of Contents for page number.)

If no refrigerant leaks are found and low cooling performance is suspected, refer to Refrigerant Charge. (See Table of Contents for page number.)

Step 8—Indoor Airflow

The cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and return-air grilles are open and free from obstructions,

and that the air filter is clean. When necessary, refer to Indoor Airflow and Airflow Adjustments section to check the system airflow.

Step 9—Metering Devices

Refrigerant cooling metering device is an Accurator (024-042) or TXV (048 and 060) located upstream of the indoor coil distributor assembly. Refrigerant heating mode metering device is an Accu- rater located upstrem of the outdoor coil distributor assembly.

Step 10—Lubrication

COMPRESSOR—The compressor is charged with the correct amount of oil at the factory.

FAN MOTOR BEARINGS—Fan motor bearings are perma- nently lubricated. No further lubrication of outdoor or indoor fan motors is required.

Step 11—Liquid Line Strainer

The liquid line strainer (to protect metering device) is made of wire mesh and is located in the liquid line on the inlet side of the metering device.

Check valves are also located in the liquid lines near the strainers. The Strainers are the larger of the two components.

Step 12—High Flow Valves

Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves cannot be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.

TROUBLESHOOTING

Use the Troubleshooting Cooling and Heating guide if problems occur with these units.

START-UP CHECKLIST

Use the Start-Up checklist to ensure proper start-up procedures are followed.

17

Image 17
Contents Safety Considerations Table of ContentsIntroduction Unit Base Dimensions, 50ZHA024-060 Provide for Condensate Disposal Unit SpecificationsUnit Damage Hazard HIGH-VOLTAGE Connections Install Electrical ConnectionsPhysical Data Size PRE-START-UPRequired Subcooling F C Required Liquid Line TemperatureRequired Subcooling START-UP Start-Up Cooling Section and Make AdjustmentsCheck for Refrigerant Leaks Refrigerant ChargeSize Rated Airflow High Airflow Indoor Airflow and Airflow AdjustmentsFor 208/230-V Blower Motors Typical Unit Electrical Diagram Sizes A05200 Accessory Electric Heater Wiring Electrical Data-50ZHA HIGH-PRESSURE Relief Valve Unit ControlsSequence of Operation FAN OperationMaintenance Cooling Charging ChartAir Filter FIRE, EXPLOSION, Electrical SHOCK, CUT HAZ- ARDUnit Top Removal Outdoor-Coil Side Indoor Blower and MotorFilter Pressure Drop in. wg Accessory Electric Heat Pressure Drop In. wgWet Coil Pressure Drop START-UP Checklist TroubleshootingTypical Heat Pump Operation, Heating Mode Symptom Cause Remedy Troubleshooting-Cooling and HeatingIII. START-UP Preliminary InformationII. PRE-START-UP

50ZHA024-060 specifications

The Carrier 50ZHA024-060 is a remarkable rooftop unit designed for commercial applications, providing both cooling and heating solutions in a compact and efficient manner. Known for its reliability and advanced engineering, this model is ideal for businesses seeking to optimize indoor comfort while maintaining energy efficiency.

One of the key features of the 50ZHA unit is its advanced scroll compressor technology. This innovation not only ensures quiet operation but also offers superior efficiency, reducing operational costs. The unit is designed to deliver a wide range of capacity options, from 24,000 to 60,000 BTU/h, making it versatile for various building sizes and requirements.

The 50ZHA series employs a microprocessor-based control system that enhances user convenience and operational efficiency. This smart technology enables precise temperature control, scheduling, and diagnostics. Furthermore, it offers compatibility with advanced building management systems, allowing for seamless integration into modern HVAC setups.

Energy efficiency is a hallmark of the Carrier 50ZHA024-060, which is equipped with environmentally friendly refrigerants that meet current regulatory standards. This commitment to sustainability is further emphasized by its exceptional SEER and EER ratings, indicating lower energy consumption without compromising performance.

In terms of construction, the 50ZHA series features a robust design with corrosion-resistant materials, ensuring durability even in harsh environmental conditions. The unit’s compact rooftop design simplifies installation and reduces the footprint, making it an excellent choice for urban areas where space is limited.

Moreover, the Carrier 50ZHA models are equipped with advanced filtration systems that improve indoor air quality by minimizing airborne contaminants. This is particularly beneficial for commercial spaces, where maintaining a healthy environment is crucial for employee productivity and wellbeing.

The 50ZHA024-060 also offers various customizable options, including economizers for increased fresh air intake and enhanced humidity control features. These options allow businesses to tailor their HVAC solutions to specific operational needs, ensuring optimal comfort year-round.

In summary, the Carrier 50ZHA024-060 is an exceptional rooftop unit that combines advanced technology, energy efficiency, and user-friendly controls. Its sturdy construction, along with a range of customizable features, makes it a leading choice for commercial HVAC applications, ensuring sustained performance and comfort in diverse settings.