Carrier 50ZHA024-060 instruction manual Introduction

Page 2

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death and/or property damage.

Before performing service or maintenance operations on system, turn off main power to unit and install lockout tag. Turn off accessory heater power switch if applicable.

Recognize safety information. This is the safety-alert symbol . When you see this symbol in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen- tial construction practices. We require these instructions as a minimum for a safe installation.

INTRODUCTION

50ZHA heat pump units are fully self-contained and designed for outdoor installation (See Fig. 1). As shown in Fig. 2, units are shipped in a horizontal-discharge configuration for installation on a ground-level slab. All units can be field-converted to downflow discharge configurations for rooftop applications with a field- supplied plenum.

RECEIVING AND INSTALLATION Step 1—Check Equipment

IDENTIFY UNIT

The unit model number and serial number are stamped on the unit identification plate. Check this information against shipping pa- pers. Verify that unit voltage and amperage listed on unit rating plate agree with power supplied for equipment.

INSPECT SHIPMENT

Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its securing points, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.

Check all items against shipping list. Immediately notify the nearest Carrier Distributor if any item is missing.

To prevent loss or damage, leave all parts in original packages until installation.

Step 2—Provide Unit Support

SLAB MOUNT

Place the unit on a rigid, level surface, suitable to support the unit weight. A concrete pad or a suitable fiberglass mounting pad is recommended. The flat surface should extend approximately 2-in. beyond the unit casing on the 2 sides. The duct connection side and condensate drain connection sides should be flush with the edge of the flat surface.

A 6-in. wide gravel apron should be used around the flat surface to prevent airflow blockage by grass or shrubs. Do not secure the unit to the flat surface except where required by local codes.

The unit should be level to within 1/4 inch. This is necessary for the unit drain to function properly.

GROUND MOUNT

The unit may also be installed directly on the ground if local codes permit. Place unit on level ground prepared with gravel for condensate discharge.

HURRICANE HOLD DOWN

Contact you local distributor for specific hurricane hold down details and PE (Professional Engineer) certification when required.

Step 3—Provide Clearances

The required minimum service clearances and clearances to combustibles are shown in Fig. 2. Adequate ventilation and outdoor coil air must be provided.

The outdoor fan pulls air through the outdoor coil and discharges it through the fan on the top cover. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 inches.

Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials.

OPERATIONAL HAZARD

Failure to follow this caution may result in unit component damage.

Do not restrict outdoor coil airflow. An air restriction at either the outdoor-air inlet or the fan discharge can be harmful to compressor life.

Step 4—Place Unit

Unit can be moved with the rigging holds provided in the unit base. Refer to Table 2 for operating weights. Use extreme caution to prevent damage when moving the unit. Unit must remain in an upright position during all moving operations. The unit must be level with in 1/4” for proper condensate drainage; the ground-level pad must be level before setting the unit in place. When a field-fabricated support is used, be sure that the support is level and that it properly supports the unit.

Step 5—Select and Install Ductwork

The design and installation of the duct system must be in accordance with:

the standards of the NFPA (National Fire Protection Associa- tion) for installation of nonresidence-type air conditioning and ventilating systems

NFPA90A or residence-type, NFPA90B; and/or local codes and residence-type, NFPA 90B

and/or local codes and ordinances

Select and size ductwork, supply-air registers and return-air grilles according to ASHRAE (American Society of Heating, Refrigera- tion, and Air Conditioning Engineers) recommendations.

Use the duct flanges provided on the supply- and return-air openings on the side of the unit. See Fig. 2 for connection sizes and locations. The 14-in. round duct collars are shipped inside the unit attached to the base pan in the indoor blower compartment. They

2

Image 2
Contents Table of Contents Safety ConsiderationsIntroduction Unit Base Dimensions, 50ZHA024-060 Provide for Condensate Disposal Unit SpecificationsUnit Damage Hazard HIGH-VOLTAGE Connections Install Electrical ConnectionsPhysical Data PRE-START-UP SizeRequired Subcooling F C Required Liquid Line TemperatureRequired Subcooling Check for Refrigerant Leaks Start-Up Cooling Section and Make AdjustmentsSTART-UP Refrigerant ChargeSize Rated Airflow High Airflow Indoor Airflow and Airflow AdjustmentsFor 208/230-V Blower Motors Typical Unit Electrical Diagram Sizes A05200 Accessory Electric Heater Wiring Electrical Data-50ZHA Sequence of Operation Unit ControlsHIGH-PRESSURE Relief Valve FAN OperationCooling Charging Chart MaintenanceUnit Top Removal Outdoor-Coil Side FIRE, EXPLOSION, Electrical SHOCK, CUT HAZ- ARDAir Filter Indoor Blower and MotorFilter Pressure Drop in. wg Accessory Electric Heat Pressure Drop In. wgWet Coil Pressure Drop Troubleshooting START-UP ChecklistTypical Heat Pump Operation, Heating Mode Troubleshooting-Cooling and Heating Symptom Cause RemedyIII. START-UP Preliminary InformationII. PRE-START-UP

50ZHA024-060 specifications

The Carrier 50ZHA024-060 is a remarkable rooftop unit designed for commercial applications, providing both cooling and heating solutions in a compact and efficient manner. Known for its reliability and advanced engineering, this model is ideal for businesses seeking to optimize indoor comfort while maintaining energy efficiency.

One of the key features of the 50ZHA unit is its advanced scroll compressor technology. This innovation not only ensures quiet operation but also offers superior efficiency, reducing operational costs. The unit is designed to deliver a wide range of capacity options, from 24,000 to 60,000 BTU/h, making it versatile for various building sizes and requirements.

The 50ZHA series employs a microprocessor-based control system that enhances user convenience and operational efficiency. This smart technology enables precise temperature control, scheduling, and diagnostics. Furthermore, it offers compatibility with advanced building management systems, allowing for seamless integration into modern HVAC setups.

Energy efficiency is a hallmark of the Carrier 50ZHA024-060, which is equipped with environmentally friendly refrigerants that meet current regulatory standards. This commitment to sustainability is further emphasized by its exceptional SEER and EER ratings, indicating lower energy consumption without compromising performance.

In terms of construction, the 50ZHA series features a robust design with corrosion-resistant materials, ensuring durability even in harsh environmental conditions. The unit’s compact rooftop design simplifies installation and reduces the footprint, making it an excellent choice for urban areas where space is limited.

Moreover, the Carrier 50ZHA models are equipped with advanced filtration systems that improve indoor air quality by minimizing airborne contaminants. This is particularly beneficial for commercial spaces, where maintaining a healthy environment is crucial for employee productivity and wellbeing.

The 50ZHA024-060 also offers various customizable options, including economizers for increased fresh air intake and enhanced humidity control features. These options allow businesses to tailor their HVAC solutions to specific operational needs, ensuring optimal comfort year-round.

In summary, the Carrier 50ZHA024-060 is an exceptional rooftop unit that combines advanced technology, energy efficiency, and user-friendly controls. Its sturdy construction, along with a range of customizable features, makes it a leading choice for commercial HVAC applications, ensuring sustained performance and comfort in diverse settings.