Allied Air Enterprises 4AC16LT Start-Up, Refrigerant Charge Adjustment, Refrigerant Charging

Page 12

START-UP

CAUTION

If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.

1. Rotate fan to check for frozen bearings or binding.

Refrigerant Charge Adjustment

Liquid Line Set

Oz. per 5 ft. adjust

Diameter

from 15 ft. line set*

 

 

3/8 in.

3 oz. per 5 ft.

 

 

*If line length is greater than 15 ft., add this amount. If line length is less than 15 ft., remove this amount.

2.Inspect all factory and field-installed wiring for loose connections.

3.After evacuation is complete, open liquid line and suction line service valves to release refrigerant charge (contained in outdoor unit) into system.

4.Replace the stem caps and secure finger tight, then tighten an additional 1/6 of a turn.

5.Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit nameplate. If not, do not start equipment until the power company has been consulted and the voltage condition corrected.

6.Set thermostat for cooling demand, turn on power to indoor blower and close the outdoor unit disconnect switch to start the unit.

7.Recheck unit voltage with unit running. Power must be within range shown on unit nameplate.

Refrigerant Charging

This system is charged with R410A refrigerant which operates at much higher pressures than R22. The liquid line drier provided with the unit is approved for use with R410A. Do not replace it with one designed for use with R22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device.

R410A refrigerant cylinders are rose colored. Refriger- ant should be added through the vapor valve in the liquid state.

Certain R410A cylinders are identified as being equipped with a dip tube. These allow liquid refriger- ant to be drawn from the bottom of the cylinder without inverting the cylinder. Do not turn this type of cylinder upside down to draw refrigerant.

Units are factory charged with the amount of R410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15' line set. For varying lengths of line set, refer to Table 4 for refrigerant charge adjustment.

Table 4

IMPORTANT

Mineral oils are not compatible with R410A. If oil must be added, it must be a polyol ester oil.

If the system is void of refrigerant, clean the system using the procedure described below.

1.Use dry nitrogen to pressurize the system and check for leaks. Repair leaks, if possible.

2.Evacuate the system to remove as much of the moisture as possible.

3.Use dry nitrogen to break the vacuum.

4.Evacuate the system again.

5.Weigh the appropriate amount of R410A refrigerant (listed on unit nameplate) into the system.

6.Monitor the system to determine the amount of moisture remaining in the oil. Use a test kit to verify that the moisture content is within the kit’s dry color range. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future.

The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter- mined by the outdoor ambient temperature.

Measure the liquid line temperature and the outdoor ambient temperature as outlined below:

1.Connect the manifold gauge set to the service valve ports as follows:

Low pressure gauge to suction line service valve

High pressure gauge to liquid line service valve

506467-01

Issue 1008

Page 12

Image 12
Contents 4AC16LT Series Lennox International Inc. CompanyInstallation Installation ClearancesTorque Table Slab MountingElectrical Wiring Slab MountingThermostat Designations Refrigerant PipingInstalling Refrigerant Line PlacementLine Set Isolation Outside Unit Placement Installation Refrigerant Line Sets Installing Horizontal RunsRefrigerant Metering Device on Refrigerant Line Sets Transition from Vertical to Horizontal Flushing Connections Flushing Existing Line Set and Indoor CoilRefrigerant Metering Device TXV DataLiquid and Suction Line Service Valves To Access the Schrader PortTo Close Liquid or Suction Line Service Valve Suction Line Ball Type Service ValveBall Type Service Valve Valve Open Leak TestingUsing an Electronic Leak Detector EvacuationPage Refrigerant Charge Adjustment START-UPRefrigerant Charging Charge Using Weigh-In Method Blocking Outdoor CoilR410A Temperature/Pressure Chart Subcooling ValuesApproach Values for TXV Systems Issue Interpreting the Diagnostic LEDs 24VAC Power WiringThermostat Demand Wiring OperationFlash Codes LEDFault Description Troubleshooting Information Status Miswired Module Troubleshooting Sensing holesMaintenance Indoor CoilIndoor Unit Start-Up and Performance Checklist Wiring Diagram P/N

4AC16LT specifications

The Allied Air Enterprises 4AC16LT is a highly efficient air conditioning unit designed to provide optimal cooling solutions for residential and light commercial applications. This model exemplifies the balance of innovative technology and user-friendly features, making it a popular choice for homeowners and contractors alike.

One of the standout characteristics of the 4AC16LT is its ENERGY STAR certification, which signifies its energy efficiency and eco-friendly operation. The unit is engineered to reduce energy consumption while delivering reliable performance, ultimately helping to lower electricity bills for consumers.

The 4AC16LT features a scroll compressor, a technology known for its durability and efficiency. This compressor design not only improves the overall cooling efficiency but also minimizes operational noise, providing a quiet and comfortable indoor environment. The unit's sound levels are notably reduced, making it ideal for residential settings where noise can be a significant concern.

In addition to its efficient compressor, the unit boasts a range of advanced technologies. The integrated smart diagnostic features allow technicians to quickly identify and troubleshoot issues, streamlining maintenance and reducing downtime. This is particularly beneficial for contractors, as it enhances service response times and customer satisfaction.

The 4AC16LT is also equipped with a durable cabinet design, which is resistant to rust and corrosion, ensuring longevity and reliability in various environmental conditions. The pre-painted steel casing not only enhances the unit’s durability but also adds an aesthetic appeal that blends well with most home exteriors.

Further enhancing its appeal, the unit utilizes environmentally friendly refrigerants that comply with current regulations. This commitment to sustainability demonstrates Allied Air Enterprises’ focus on innovation while caring for the environment.

Moreover, the model is designed with ease of installation in mind. The compact size and lightweight construction of the 4AC16LT facilitate straightforward installation, saving time and labor costs for technicians.

In summary, the Allied Air Enterprises 4AC16LT air conditioning unit is a top-tier choice that incorporates energy efficiency, advanced technology, and a user-friendly design. Its combination of quiet operation, robust features, and commitment to sustainability makes it an excellent investment for anyone seeking reliable indoor comfort.