Allied Air Enterprises 4AC16LT manual Installing Refrigerant Line, Placement, Line Set Isolation

Page 4

Select line set diameters from Table 2 to ensure that oil return to the compressor. Size vertical suction riser to maintain minimum velocity at minimum capacity. Recommended line length is 50’ or less. If more than 50’ line set is required, contact Technical Service.

Table 2 shows the diameters for line sets up to 100’ although vertical lift applications and trapping requirements need to be reviewed with Technical Service for line sets over 50’.

Refrigerant Line Set Diameters (in.)

Liquid Line

Line S et Length and S ize

BTUH

 

12 ft. 25 ft. 50 ft. 75 ft. 100 ft.

24,000

3/8

3/8

3/8

3/8

3/8

36,000

3/8

3/8

3/8

3/8

1/2

48,000

3/8

3/8

3/8

1/2

1/2

60,000 3/8 3/8 3/8 1/2 1/2

S uction L ine

L ine S et L ength and S ize

B T U H

 

12 ft. 25 ft. 50 ft. 75 ft. 100 ft.

24,000

3/4

3/4

3/4

3/4

7/8

36,000

7/8

7/8

7/8

7/8

1-1/8

48,000

7/8

1-1/8

1-1/8

1-1/8

1-1/8

60,000 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8

For installations exceeding 50’, contact

Technical Services.

Table 2

WARNING

Polyolester (POE) oils used with R-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until ready to make connections.

Installing Refrigerant Line

During the installation of an air conditioning system, it is important to properly isolate the refrigerant line to prevent unnecssary vibration. Line set contact with the structure (wall, ceiling, or floor) may cause objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Close attention to line set isolation must be observed. If refrigeration lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building.

Following are some points to consider when placing and installing a high-efficiency outdoor unit:

Placement

Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neighbor’s home, not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a bedroom window. Glass has a verry high level of sound transmission. Figure 4 shows how to place the outdoor unit and line set to reduce line set vibration.

Line Set Isolation

Illustrations on the pages 6 and 7 demonstrate procedures which ensure proper refrigerant line set isolation. Figure 6 shows how to install line sets on horizontal runs. Figure 7 shows how to make a transition from horizontal to vertical. Figure 9 shows how to install line sets on vertical runs.

Brazing Connection Procedure

1.Cut ends of refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round; do not pinch end of line.

2.Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the system.

3.Use silver alloy brazing rods (5% or 6% silver alloy for copper-to-copper brazing or 45% silver alloy for

506467-01

Issue 1008

Page 4

Image 4
Contents 4AC16LT Series Lennox International Inc. CompanyInstallation Installation ClearancesTorque Table Slab MountingElectrical Wiring Slab MountingThermostat Designations Refrigerant PipingPlacement Installing Refrigerant LineLine Set Isolation Refrigerant Line Sets Installing Horizontal Runs Outside Unit Placement InstallationRefrigerant Metering Device on Refrigerant Line Sets Transition from Vertical to Horizontal Flushing Connections Flushing Existing Line Set and Indoor CoilRefrigerant Metering Device TXV DataLiquid and Suction Line Service Valves To Access the Schrader PortTo Close Liquid or Suction Line Service Valve Suction Line Ball Type Service ValveBall Type Service Valve Valve Open Leak TestingUsing an Electronic Leak Detector EvacuationPage START-UP Refrigerant Charge AdjustmentRefrigerant Charging Charge Using Weigh-In Method Blocking Outdoor CoilSubcooling Values R410A Temperature/Pressure ChartApproach Values for TXV Systems Issue Interpreting the Diagnostic LEDs 24VAC Power WiringThermostat Demand Wiring OperationFlash Codes LEDFault Description Troubleshooting Information Status Miswired Module Troubleshooting Sensing holesIndoor Coil MaintenanceIndoor Unit Start-Up and Performance Checklist Wiring Diagram P/N

4AC16LT specifications

The Allied Air Enterprises 4AC16LT is a highly efficient air conditioning unit designed to provide optimal cooling solutions for residential and light commercial applications. This model exemplifies the balance of innovative technology and user-friendly features, making it a popular choice for homeowners and contractors alike.

One of the standout characteristics of the 4AC16LT is its ENERGY STAR certification, which signifies its energy efficiency and eco-friendly operation. The unit is engineered to reduce energy consumption while delivering reliable performance, ultimately helping to lower electricity bills for consumers.

The 4AC16LT features a scroll compressor, a technology known for its durability and efficiency. This compressor design not only improves the overall cooling efficiency but also minimizes operational noise, providing a quiet and comfortable indoor environment. The unit's sound levels are notably reduced, making it ideal for residential settings where noise can be a significant concern.

In addition to its efficient compressor, the unit boasts a range of advanced technologies. The integrated smart diagnostic features allow technicians to quickly identify and troubleshoot issues, streamlining maintenance and reducing downtime. This is particularly beneficial for contractors, as it enhances service response times and customer satisfaction.

The 4AC16LT is also equipped with a durable cabinet design, which is resistant to rust and corrosion, ensuring longevity and reliability in various environmental conditions. The pre-painted steel casing not only enhances the unit’s durability but also adds an aesthetic appeal that blends well with most home exteriors.

Further enhancing its appeal, the unit utilizes environmentally friendly refrigerants that comply with current regulations. This commitment to sustainability demonstrates Allied Air Enterprises’ focus on innovation while caring for the environment.

Moreover, the model is designed with ease of installation in mind. The compact size and lightweight construction of the 4AC16LT facilitate straightforward installation, saving time and labor costs for technicians.

In summary, the Allied Air Enterprises 4AC16LT air conditioning unit is a top-tier choice that incorporates energy efficiency, advanced technology, and a user-friendly design. Its combination of quiet operation, robust features, and commitment to sustainability makes it an excellent investment for anyone seeking reliable indoor comfort.