Small Packaged Products Standard Altitude Only
Cancels: IIK | IIK |
|
Installation Instructions
Part Number: CPLPCONV006A00 2 to 5 Tons
NOTE: Read the entire instruction manual before starting the installation.
This symbol → indicates a change since the last issue.
Firing Tube
SAFETY CONSIDERATIONS
Installing and servicing air conditioning equipment can be hazard- ous due to system fuels. Only trained and qualified personnel should install, service, or repair air conditioning equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils, or cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, on tags, and on labels attached to the unit.
Recognize safety information. This is the
Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the
Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available.
Before converting a unit to LP, remove the burner assembly and inspect the heat exchanger tubes. If there are
MUST BE REMOVED PRIOR TO CONVERTING
THIS UNIT TO LP. Discard the baffles after removal.
This conversion kit is to be installed by qualified service personnel in accordance with these instructions and all codes and requirements of the authority having jurisdiction, and in Canada, in accordance with the requirements of the CAN/CGA (Canadian Gas Association) B149.2 Installation Code. Failure to follow these instructions could result in serious injury, property damage or death. The qualified agency performing this work assumes responsibility for this conversion.
|
| NOx Baffle | |
|
| C00151 | |
→ |
| Fig. | |
|
| This unit is designed to operate at 3.5 in. wg (±0.3 in. wg) of |
|
|
|
| |
|
| manifold pressure with liquid propane (LP) gas. Exceeding |
|
|
| this pressure may result in explosion, injury or death. |
|
→ |
|
|
|
| INTRODUCTION | ||
| These instructions cover the installation of a liquid propane | ||
| conversion kit on models 48GS, 582A, | ||
| |||
| combination automatic gas valve regulator. | ||
|
| DESCRIPTION AND USAGE | |
| This kit is applicable to units with heating inputs from 60,000 to | ||
| 130,000 Btu/hrinstalled at standard altitudes from 0 ft to 2000 ft. | ||
| It cannot be used for high altitude installations or on units with | ||
| heating inputs of 40,000 Btu/hr. High altitude conversions | ||
| |||
| sions of 40,000 Btu/hr units should use Kit | ||
| #CPCLPCONV008A00 (applicable for any altitude from 0 ft to | ||
| 6000 ft). | ||
|
| INSTALLATION |
Before performing service or maintenance operations on unit, turn off gas supply first, then the main power switch to unit. Electrical shock could cause serious injury or death. TAG DISCONNECT SWITCH WITH SUITABLE WARNING LABEL.
→1. Turn off gas supply first, then power to unit.
2.Remove the front access panel from unit.
3.Disconnect the gas pipe from the gas valve.
4.Disconnect orange sparker cable at the ignition control.