Carrier 90MA/MF/MU manual Condensers may require cleaning of water-deposited scale

Page 16

BELT TENSION ADJUSTMENT - Shut off unit power

supply. Loosen fan motor from mounting bracket. Do not loosen motor mounting bracket from unit. Move fan motor up or down until proper belt tension is achieved (approximately 3/4-in. deflection with 8-pound tension at midpoint of belt span).

Lubrication - Fan motor and fan shaft bearings are lubricated for the life of the bearings. No re-lubrication is required

5.4Return--Air Filter

Inspect filters twice monthly and clean as required by operating conditions. Filter size and type are listed in Table 1, Table 3 or Table 2. To clean filters flush with hot water or steam or soak in a mild water solution of soap or detergent. Refer to filter manufacturer’s instructions as applicable. Do not operate unit without return-air filters in place.

5.5Condensate Drain

Clean the drain line and unit drain pan at the start of each cooling season. Check flow by pouring water into drain. Be sure trap is filled as shown in Figure 7 to maintain an air seal.

5.6Evaporator Coil

WARNING

Never reach into unit while fan is running. Lock open and tag unit disconnect before working on fan. Remove fuses and take them with you after noting this on tag.

Remove dirt and debris from evaporator coil as required by condition. Clean coil with a stiff brush, vacuum cleaner or compressed air. Use a fin comb of the correct tooth spacing (Refer toTable 1, Table 3 or Table 2 for coil fins/inch) when straightening mashed or bent coil fins.

5.7Water Regulating Valve

PREPARATION FOR OPERATION.

a.Open the water regulating valve inlet and outlet isola- tion valves.

b.Close the water regulating valve bypass valve.

ADJUSTMENT

a. The compressor discharge pressure is controlled by the water regulating valve and may be monitored by observing liquid line pressure.

NOTE

Adjustments to the water regulating valve must be made slowly, allowing ample time for re- sponse and stabilization.

b. Install a calibrated gauge at the liquid line service port. Operating liquid line range for R-22 units is 250 to 270 psig (1724 to 1862 kPa), for R-134a units is 155 to 180 psig (1069 to 1241 kPa) and for R-407C is 267 to 288 psig (1841 to 1986 kPa). If pressure read- ing is below operating range, rotate the square head adjusting screw counterclockwise; this will increase

spring tension, decrease water flow and increase pres- sure.

If pressure reading is above operating range, rotate the square head adjusting screw clockwise; this will decrease spring tension, increase water flow and de- crease pressure.

c. Only the water regulating valve opening point is ad- justable. The closing point is 3 to 7 psig below the opening point and is non-adjustable.

5.8Condenser

Condensers may require cleaning of water-deposited scale.

WARNING

Follow all Safety codes. Wear safety glasses and rubber gloves when using inhibited hy- drochloric acid solution.

Clean condensers with an inhibited hydrochloric acid solution. The acid can stain hands and clothing, attack concrete and, without inhibitor, can attack steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.

Warm solution acts faster, but cold solution is just as effective if applied for a longer period.

Figure 9 Gravity Flow Method

GRAVITY FLOW METHOD

a.Disconnect condenser piping at unit, including isola- tion valves and water regulating valve.

b.Fill condenser as shown in Figure 9. Follow acid manufacturer’s instructions. When condenser is full, allow solution to remain overnight

c.Drain condenser and flush with clean water.

FORCED CIRCULATION METHOD

a.Disconnect condenser piping at unit, including isola- tion valves and water regulating valve.

b.Fill system as shown in Figure 10. Follow acid manufacturer’s instructions. Fully open vent pipe when filling system. The vent may be closed when system is full and pump is operating.

62--10458--00

10

 

Image 16
Contents Installation Operation & Service Models Safety Summary 62--10458--00 Safety-2 Table of Contents List of Illustrations Introduction Base Unit 90MA/MF/MU Units 404 406 408 Base Unit 90MA/MF Units Unit Dimensions Install water-regulating valve in water supply line Unit Length of RUN Operation Service Condensers may require cleaning of water-deposited scale Forced Circulation Method Refrigerant Charging 134a Units Mounting Wiring Schematic -- 90MA/MF/MU004/006 Component Arrangement -- 90MA/MF/MU004/006 62--10458--00 Wiring Schematic -- 90MA/MF/MU008/012 Component Arrangement -- 90MA/MF/MU008/012 62--10458--00 Index 62--10458--00

90MA/MF/MU specifications

The Carrier 90MA/MF/MU series represents a significant advancement in HVAC technology, designed for commercial applications needing reliability, efficiency, and precision in climate control. These units are renowned for their ability to cater to varying thermal loads while minimizing energy consumption, making them an ideal choice for various settings including offices, retail spaces, and industrial facilities.

One of the standout features of the Carrier 90MA/MF/MU series is its impressive energy efficiency. The equipment is designed with advanced thermodynamic principles to ensure maximum heat transfer and minimal energy loss. With high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), these units help building owners achieve higher energy savings compared to traditional HVAC systems.

Another significant characteristic of the 90MA/MF/MU series is the integration of advanced control technologies. The units come equipped with sophisticated microprocessor-based controls that allow for precise temperature management and enhance overall system performance. Features like modulating capabilities and variable speed fans provide superior comfort levels by continuously adjusting to the changing environmental conditions.

The 90MA series also emphasizes quiet operation, which is critical for commercial environments. The innovative design includes insulation and vibration dampening technologies that reduce noise levels, ensuring a comfortable working atmosphere.

Durability and reliability are also central to the design of the Carrier 90MA/MF/MU series. These units are engineered with high-quality materials and components, including robust compressors and corrosion-resistant finishes that withstand harsh weather conditions. This durability extends the lifespan of the units, thus reducing maintenance costs and downtime.

In terms of versatility, the 90MA/MF/MU series offers a broad range of configurations and options, including various sizes and capacities. This flexibility allows for tailored solutions that meet the specific needs of different applications, from large commercial buildings to smaller retail outlets.

The series also supports environmentally friendly refrigerants that comply with global standards, marking Carrier’s commitment to sustainable practices. This approach not only reduces environmental impact but also positions businesses favorably in the eyes of eco-conscious consumers.

Overall, the Carrier 90MA/MF/MU series stands out as a pinnacle of efficiency, performance, and reliability in the commercial HVAC market. Its advanced technologies and thoughtful design cater to the diverse needs of modern businesses while promoting a sustainable and comfortable indoor environment.