Step 4 - Rig and Place Unit -

Step 4 - Rig and Place Unit -

NOTE: Install accessories before placing unit.

a. Provide space around unit for service, filter access, and overhead clearance as indicated in Figure 2.

b. Move and store unit in upright position.

c. Use slings with spacer under base skid to prevent panel damage when using hoist.

d. Units as shipped are adequately dampened against vibration. If additional dampening is desired, place sponge rubber or rubber mat, between deck and base of unit or install vibration isolators.

e. Unit should be level. Unit leveling tolerance is 1/8 in. per linear ft in any direction.

Step 5 - Install Accessory Plenum (If Supplied) - Use plenum as template to mark hole locations in top panel. Drill 0.154-in. holes in top panel at marked locations and attach plenum with screws supplied.

FIGURE 1 - BASE UNIT INTERIOR DETAILS

(TYPICAL UNIT SHOWN)

UNIT

*04

*06

*08,*12

A

36.13(918)

48.26(1226)

B

21.63(549)

29.88(759)

C

59.25(1505)

72.00(1828)

D

 

SEE NOTE 2

 

E

 

24(51)

 

F

11.25(286)

13.50(343)

15.63(397)

G

13.00 (330)

15.50(394)

18.38(466)

H

0.75(19)

0.75(19)

1.00 (25)

J

11.59(294)

10.34(263)

11.37(289)

K

17.13(435)

24.20(615)

L

20.38(519)

25.50(646)

M

17.11(435)

17.11(435)

 

 

 

 

NOTES:

1. Certified dimension drawings available upon request

2. Minimum required clearance at back of unit is zero. Clearance above and at right (90MA*08,*12 only) and at left of unit depends on space required for accessory plenum, ductwork, condenser piping, accessory heater piping, condensate drain line and power wiring

3. Water connections are located on left side of unit (Refer to “Make Condenser Connections”, Condensate drain connections are located on left side of unit for *04 & *06, and on both sides of unit for *08 & *12.

FIGURE 2 - UNIT DIMENSIONS

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

Printed in U.S.A.

Pg 8

90MA-3SI SUPERCEDES FORM 62-02971-00 09-2009

 

 

Image 8
Contents Single-PackageMarine Cooling Units COMPONENT ARRANGEMENT - *04/*06COMPONENT ARRANGEMENT - *08/*12 Installation, Operation and Service InstructionsFPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter FemaleFPT = Female Pipe Thread MPT = Male Pipe Thread Page FPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter FemaleFPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter FemaleFPT = Female Pipe Thread MPT = Male Pipe Thread FIGURE 2 - UNIT DIMENSIONS Step 4 - Rig and Place UnitFIGURE 1 - BASE UNIT INTERIOR DETAILS TYPICAL UNIT SHOWNFIGURE 3 - HORIZONTAL WHEEL CENTERING FIGURE 4 - CONCENTRIC WHEEL ALIGNMENTStep 10 - Make Condenser Connections FIGURE 5 - TYPICAL CONDENSER WATER PIPINGFIGURE 6 - CONNECTION LOCATIONS FIGURE 7 - CONDENSATE DRAIN TRAP OPERATION Step 12 - Make Electrical ConnectionsTo start unit To Shut Down UnitReturn-AirGrille Removal SERVICEFIGURE 8 - FAN PULLEY ADJUSTMENT FIGURE 10 - FORCED CIRCULATION METHOD Water Regulating ValveFIGURE 9 - GRAVITY FLOW METHOD Charging the System 90MU R-407C, R-404A,and R-134aunits 90MA-3SISUPERCEDES FORM FIGURE 12 WIRING SCHEMATIC - 90MA/MU*04/*06FOR NOTES AND LEGEND, SEE FIGURE FIGURE 13 COMPONENT ARRANGEMENT - 90MA/MU*04/*06 90MA-3SISUPERCEDES FORM90MA-3SISUPERCEDES FORM FIGURE 14 - ELECTRICAL SCHEMATIC - 90MA/MU*08/*12FOR NOTES AND LEGEND, SEE FIGURE 90MA-3SISUPERCEDES FORM 90MA-3SISUPERCEDES FORM 90MA-3SISUPERCEDES FORM