Carrier 90MA, 90MU specifications

Page 4
Manual background

TABLE 1C - 90MA/MU PHYSICAL DATA – R-404A , ENGLISH UNITS (See Table 2C for SI units)

 

BASE UNIT (90MA/MU)

UNITS

504

 

506

 

508

 

512

 

NOMINAL CAPACITY

Tons

3

 

5

 

7.5

 

10

 

REFRIGERANT

 

 

 

 

R-

 

 

 

 

 

 

OPERATING WEIGHT

 

 

 

 

 

 

 

 

 

 

 

 

Base unit 90MA

Pounds

390

 

427

 

895

 

950

 

 

Base Unit 90MU

Pounds

330

 

360

 

 

835

 

890

 

 

Discharge Plenum

Pounds

25

 

25

 

 

50

 

50

 

COMPRESSOR TYPE

 

Scroll

 

 

 

Semi-Hermetic, Recip

 

 

Qty Cylinders

 

N/

 

 

4

 

6

 

 

Qty Unloading Cylinders

 

N/

 

 

 

0

 

 

2

 

 

Qty Capacity Steps

 

1

 

 

 

1

 

 

2

 

DISCHARGE

PRESSURE SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

Opens (90MA)

PSIG

 

 

395+/

-10

 

 

 

 

 

Closes (90MA)

PSIG

 

 

295+/-10

 

 

 

 

 

Opens (90MU)

PSIG

 

 

 

426+/-7

 

 

 

 

 

Closes (90MU)

PSIG

 

 

320+/-20

 

 

 

 

SUCTION

PRESSURE SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

Opens

PSIG

 

 

 

27+/

-4

 

 

 

 

 

Closes

PSIG

 

 

 

67+/-4

 

 

 

 

REFRIGERANT

 

 

 

 

 

 

 

 

 

 

 

 

Typ

 

 

 

 

R-

 

 

 

 

 

 

Qty (90MA ONLY))

Pounds

3.1

 

5.3

 

 

11.2

 

 

10.0

 

CONDENSER

(90MA ONLY)

 

 

 

 

 

 

 

 

 

 

 

 

Number...Type

 

 

 

1…Tube

in Tube

 

 

 

 

 

Water Volume

Gallons

0.39

 

0.86

 

 

 

2.42

 

EVAPORATOR AIR FAN

 

Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60hz

 

 

Nominal Flow

CFM

1200

 

2000

 

 

3000

 

 

4000

 

 

Standard Speed Range

RPM

647-915

 

647-915

 

 

487-690

 

 

591-838

 

 

Maximum Allowable Speed

RPM

 

 

 

1250

 

 

 

 

 

Belt Qty/Pulley Pitch Diameter

Inches

1 / 6.4

 

1 / 6.4

 

 

1 / 8.5

 

 

1 / 7.0

 

 

Motor Pulley Pitch Diameter Range

Inches

 

 

2.4 to 3.4

inches

 

 

 

 

 

Motor Nominal Rating (@ 60Hz)…Frame Size

 

 

 

 

 

 

 

 

 

 

 

 

Standard

HP

1/3…56

 

3/4…56

 

 

1…56

 

 

2…56

 

 

Alternate (SeeNote 1)

HP

3/4…56

 

1…56

 

 

2…56

 

 

3…56

 

 

Alternate (See Note 1)

HP

N/

 

N/

 

 

3…56

 

 

N/

 

EVAPORATOR COIL

 

3/8 OD, Copper Tubes, Aluminum Fin

 

 

Tube

 

 

 

 

Prime

 

 

 

 

 

Qty Rows…Fin Spacing

Fins/Inch

2…14.4

 

3…14.4

 

 

 

3…12.5

 

 

Face Area

Sq Ft

5

 

5

 

 

7.3

 

 

8.5

 

RETURN AIR FILTERS

 

 

Factory Supplied, Cleanable

 

 

Qty…Size

Inches

2…16 x 25 x 1

 

 

4…16 x 20 x 1

 

CONDENSER

CONNECTIONS (90MA ONLY)

 

 

 

 

 

 

 

 

 

 

 

 

Water Inlet (bottom)

Inches FPT

1/2

 

3/4

 

 

1

 

 

1

 

 

Water Outler (top)

Inches FPT

1/2

 

3/4

 

 

1

 

 

1

 

 

Maximum Working Pressure (Refrigerant Side)

PSIG

 

 

 

400

 

 

 

 

CONDENSATE DRAIN CONNECTIONS

Inches FPT

 

 

 

3/4

 

 

 

 

ACCESSORY ELECTRIC HEAT

 

 

 

 

 

 

 

 

 

 

 

 

Capacity @ 460 volts

Watts

5.25

 

 

 

 

17.5

 

 

Capacity @ 400 volts

Watts

4.03

 

 

 

 

13.4

 

 

Number of Electric Heat Stages

 

1

 

 

 

 

2

LEGEND

 

 

 

 

 

 

 

 

 

 

FPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter Female

NOTES:

1. Motors other than those furnished with unit must be purchased separately. Contact your Carrier Marine representative

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

Printed in U.S.A.

Pg 4

90MA-3SI SUPERCEDES FORM 62-02971-00 09-2009

 

 

Image 4
Contents Single-PackageMarine Cooling Units COMPONENT ARRANGEMENT - *04/*06COMPONENT ARRANGEMENT - *08/*12 Installation, Operation and Service InstructionsFPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter FemaleFPT = Female Pipe Thread MPT = Male Pipe Thread Page FPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter FemaleFPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter FemaleFPT = Female Pipe Thread MPT = Male Pipe Thread FIGURE 2 - UNIT DIMENSIONS Step 4 - Rig and Place UnitFIGURE 1 - BASE UNIT INTERIOR DETAILS TYPICAL UNIT SHOWNFIGURE 3 - HORIZONTAL WHEEL CENTERING FIGURE 4 - CONCENTRIC WHEEL ALIGNMENTStep 10 - Make Condenser Connections FIGURE 5 - TYPICAL CONDENSER WATER PIPINGFIGURE 6 - CONNECTION LOCATIONS FIGURE 7 - CONDENSATE DRAIN TRAP OPERATION Step 12 - Make Electrical ConnectionsTo start unit To Shut Down UnitFIGURE 8 - FAN PULLEY ADJUSTMENT SERVICEReturn-AirGrille Removal FIGURE 9 - GRAVITY FLOW METHOD Water Regulating ValveFIGURE 10 - FORCED CIRCULATION METHOD Charging the System 90MU R-407C, R-404A,and R-134aunits FOR NOTES AND LEGEND, SEE FIGURE FIGURE 12 WIRING SCHEMATIC - 90MA/MU*04/*0690MA-3SISUPERCEDES FORM FIGURE 13 COMPONENT ARRANGEMENT - 90MA/MU*04/*06 90MA-3SISUPERCEDES FORMFOR NOTES AND LEGEND, SEE FIGURE FIGURE 14 - ELECTRICAL SCHEMATIC - 90MA/MU*08/*1290MA-3SISUPERCEDES FORM 90MA-3SISUPERCEDES FORM 90MA-3SISUPERCEDES FORM 90MA-3SISUPERCEDES FORM