Carrier 90MU, 90MA specifications Condensate Drain Trap

Page 11
FIGURE 7 - CONDENSATE DRAIN TRAP

TABLE 3 - RECOMMENDED LINE SIZES (INCHES) REMOTE CONDENSERS

UNIT

REFRIGERANT

 

 

 

LENGTH OF RUN

 

 

 

 

 

 

 

 

 

 

 

90MU

TYPE

0-25

26-50

51-75

76-100

 

 

DISCH

LIQUID

DISCH

LIQUID

DISCH

LIQUID

DISCH

LIQUID

404

R-407C

1/2

3/8

5/8

3/8

5/8

3/8

5/8

3/8

406

R-407C

5/8

3/8

3/4

3/8

3/4

3/8

3/4

3/8

408

R-407C

3/4

1/2

3/4

1/2

7/8

1/2

7/8

1/2

412

R-407C

7/8

1/2

7/8

1/2

7/8

1/2

1-1/8

5/8

504

R-404A

5/8

3/8

5/8

3/8

3/4

3/8

3/4

3/8

506

R-404A

3/4

1/2

3/4

1/2

7/8

1/2

7/8

1/2

508

R-404A

7/8

1/2

7/8

1/2

1-1/8

1/2

1-1/8

5/8

512

R-404A

7/8

5/8

1-1/8

5/8

1-1/8

5/8

1-1/8

5/8

* Recommended line sizes correspond to 2 degree F drop.

NOTES:

1.Pipe sizes should never be smaller than cooling unit connection size.

2.Table is based on 2 degree F drop over entire length. Excessive (more than a few) elbows and fittings will significantly affect pressure drop. If this situation exists, line sizing must be re- calculated.

Step 11 - Install Unit Drain Line - Install a trapped

 

condensate drain line at unit drain connection The drain

 

requires standard pipe connected to condensate pan

 

nipple(s). Figure 7 shows proper trap design.

 

Determine design negative static pressure. This

 

pressure is not the same as fan total static pressure, which

 

includes pressure losses downstream as well as upstream

 

from the evaporator air fan. Always assume the worst

 

conditions, such as having return air filters clogged with

 

debris.

 

Referring to Figure 7, differential 1 must be equal to or

 

larger than negative static pressure at design operating

 

condition. Store enough water in trap to prevent losing

 

seal. Differential 2 must be equal to or larger than one-half

 

the maximum negative static pressure. To avoid loss of

 

seal when the fan starts, differential 3 must be greater

 

than the maximum negative static pressure.

 

Do not use drain line smaller than 3/4 inch. Use hole(s)

 

provided in panel for drain line. Pitch drain line downward

 

toward scupper. Installation of a plugged tee is

FIGURE 7 - CONDENSATE DRAIN TRAP

recommended for cleaning. Fill trap with water to make an

air seal. Observe all sanitary requirements.

 

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

Printed in U.S.A.

Pg 11

90MA-3SI SUPERCEDES FORM 62-02971-00 09-2009

 

 

Image 11
Contents Installation, Operation and Service Instructions Single-PackageMarine Cooling UnitsCOMPONENT ARRANGEMENT - *04/*06 COMPONENT ARRANGEMENT - *08/*12ODF = Outside Diameter Female FPT = Female Pipe Thread MPT = Male Pipe ThreadFPT = Female Pipe Thread MPT = Male Pipe Thread Page ODF = Outside Diameter Female FPT = Female Pipe Thread MPT = Male Pipe ThreadODF = Outside Diameter Female FPT = Female Pipe Thread MPT = Male Pipe ThreadFPT = Female Pipe Thread MPT = Male Pipe Thread TYPICAL UNIT SHOWN FIGURE 2 - UNIT DIMENSIONSStep 4 - Rig and Place Unit FIGURE 1 - BASE UNIT INTERIOR DETAILSFIGURE 5 - TYPICAL CONDENSER WATER PIPING FIGURE 3 - HORIZONTAL WHEEL CENTERINGFIGURE 4 - CONCENTRIC WHEEL ALIGNMENT Step 10 - Make Condenser ConnectionsFIGURE 6 - CONNECTION LOCATIONS FIGURE 7 - CONDENSATE DRAIN TRAP To Shut Down Unit OPERATIONStep 12 - Make Electrical Connections To start unitReturn-AirGrille Removal SERVICEFIGURE 8 - FAN PULLEY ADJUSTMENT FIGURE 10 - FORCED CIRCULATION METHOD Water Regulating ValveFIGURE 9 - GRAVITY FLOW METHOD Charging the System 90MU R-407C, R-404A,and R-134aunits 90MA-3SISUPERCEDES FORM FIGURE 12 WIRING SCHEMATIC - 90MA/MU*04/*06FOR NOTES AND LEGEND, SEE FIGURE 90MA-3SISUPERCEDES FORM FIGURE 13 COMPONENT ARRANGEMENT - 90MA/MU*04/*0690MA-3SISUPERCEDES FORM FIGURE 14 - ELECTRICAL SCHEMATIC - 90MA/MU*08/*12FOR NOTES AND LEGEND, SEE FIGURE 90MA-3SISUPERCEDES FORM 90MA-3SISUPERCEDES FORM 90MA-3SISUPERCEDES FORM