Carrier 40QNC, 40QNQ Troubleshooting, Fault Code, Green LED Indoor Unit Fault

Page 23

TROUBLESHOOTING

See Table 12 and Table 13 for troubleshooting information.

Fault Code

Once a failure occurs with the indoor unit in operation, the green LED on the indoor unit flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 3 seconds elapses.

 

Table 12 – Green LED (Indoor Unit Fault)

 

 

CODE

DESCRIPTION

3

Room Air Sensor Fault

4

Indoor Unit Coil Sensor Fault

14

Outdoor Unit Air Sensor Fault

Table 13 – Troubleshooting

PROBLEM

POSSIBLE CAUSE

SOLUTION

 

Unit not energized

Check the main power connection.

Compressor and Fan of the Outdoor

Main switch is set to OFF

Check and put it to ON position.

Main switch fuses are blown

Replace fuses.

Unit Will Not Start

Compressor cycling protection is on

Wait for 3 minutes.

 

Main power voltage is too low

Check and set to the correct voltage.

 

Electrical connections are too loose or are wrong

Check and tighten or correct connections.

Compressor Will Not Start, But Out-

Electrical connections of compressor are loose or

Check and tighten or repair compressor.

door Fan is Operating

wrong

 

 

Compressor burnt out; seized or protection device

Check for the cause and replace compressor if neces-

 

on

sary.

 

Wrong refrigerant charge in unit (excessive or low)

Drain refrigerant, evacuate and recharge. CAUTION: Do

 

or air or other non ---condensable gasses in the

not vent refrigerant to the atmosphere; use refrigerant

 

circuit

recovery equipment.

Compressor Stops Due to Over---tem-

Main voltage is too high or too low

Check voltage setting and adjust if necessary.

Condenser coil obstructed

Remove obstruction.

perature

Outdoor fan off

Check cause and resume operation or repair.

 

Wrong indoor unit thermistors

Replace thermistors.

 

Refrigerant circuit clogged

Check and remove obstructions.

 

Reversing valve faulty on heat pump models

Replace reversing valve.

 

 

Drain refrigerant, evacuate and recharge. CAUTION: Do

 

Expansion device clogged or covered with ice

not vent refrigerant to the atmosphere; use refrigerant

 

 

recovery equipment.

 

Unit selected is too small for application require-

Contact a qualified service technician for a system evalu-

 

ments

ation.

 

Indoor temperature setting too low or too high

Check temperature setting.

Compressor Runs Continuously

Outdoor unit fan faulty

Replace outdoor fan.

Air or other non ---condensable gasses in the cir-

Drain refrigerant, evacuate and recharge. CAUTION: Do

 

 

not vent refrigerant to the atmosphere; use refrigerant

 

cuit

 

recovery equipment.

 

 

 

Obstructions at air intake or dirty indoor unit filters

Remove obstruction and/or clean filter.

Frequent Ice ---Build---Up on Outdoor

Outdoor fan is stopped

Check cause and repair.

Coil

 

 

 

Outdoor coil dirty or obstructed

Clean or remove obstructions.

 

Condenser fan faulty

Replace condenser fan.

Discharge Pressure Too High

Indoor temperature setting too low or too high

Check temperature setting.

Air or other non ---condensable gasses in the cir-

Drain refrigerant, evacuate and recharge. CAUTION: Do

 

 

not vent refrigerant to the atmosphere; use refrigerant

 

cuit

 

recovery equipment.

 

 

Discharge Pressure Too Low

Indoor temperature setting too high or too low

Check temperature setting.

Outdoor coil dirty or obstructed

Clean or remove obstructions.

 

Indoor unit air filter dirty

Clean filter.

Suction Pressure Too High

Indoor temperature setting too high or too low

Check temperature setting.

Reversing valve faulty or internal leak

Replace reversing valve.

 

 

Indoor temperature setting too high or too low

Check temperature setting.

 

Evaporator coil covered with ice

Air circulation on the evaporator not sufficient; check and

Suction Pressure Too Low

repair.

 

 

Expansion device or suction line clogged

Check and repair.

 

Outdoor fan does not stop during defrost periods

Check electrical parts.

 

Electrical connection loose

Check connections.

Outdoor Fan Cycling Due to Over---

Fan motor burn out

Replace.

Fan bearing seized

Check and repair.

Temperature Protection

 

Drain refrigerant, evacuate and replace.

 

Expansion device clogged or covered with ice

CAUTION: Do not vent refrigerant to the atmosphere; use

 

 

refrigerant recovery equipment.

23

Image 23
Contents 40QNC, QNQ Unit Safety ConsiderationsDimensions Outdoor Dimensions IndoorCoil Facing Wall --- in. mm Fan Facing Wall --- in. mm Clearances IndoorClearances Outdoor System Requirements Parts ListOperating Range Power and Connecting Cables Field SuppliedAccessories User InterfaceRefrigerant Line Routing InstallationComplete Pre-installation Checks Consider System RequirementsMounting on Roof Side Or Bottom PipingMounting on Ground 38HDF Units Complete Outdoor Refrigerant Piping Connec- tionsMounting Unit on Wall Connection at Outdoor Unit38QRF Units Complete Outdoor Power and Control WiringPower Wiring 38QRF Control Terminal Strip 40QNC, QNQ Fan Coil Electrical Data 38HDF / 38QRF Electrical Data40QNC01824 Matched with 38HDF Typical Wiring Schematic 40QNQ018,024 Matched with 38QRF Typical Wiring Schematic 40QNC030, 036 Matched with 38HDF Typical Wiring Schematic 40QNQ030, 036 Matched with 38QRF Typical Wiring Schematic Location of Piping, Hose, and Wiring Run Power Wiring for Indoor UnitWired Control Unit ConfigurationRemote Control Configuration Control Wiring Between Indoor and Outdoor Units Zone Manager Wiring for Zone ManagerEvacuate and Dehydrate the System Using Vacuum PumpSTART-UP Preliminary ChecksTo Start the Unit Test Mode Sequence of OperationSet Unit in Test Mode Using Wireless Control Set Unit in Test Mode Using Wired ControlFilter Drier ServicePump-down Procedure Refrigerant ChargingTroubleshooting TroubleshootingFault Code Green LED Indoor Unit FaultCatalog No 40QNC---Q---9SI

40QNQ, 40QNC specifications

The Carrier 40QNC and 40QNQ are advanced rooftop packaged units designed for efficient heating and cooling in commercial applications. These units are particularly known for their reliability, versatility, and energy-efficient performance, making them a preferred choice for building owners and HVAC professionals alike.

One of the standout features of the Carrier 40QNC and 40QNQ units is their variable-speed technology. This innovative system allows for precise control of airflow and temperature, ensuring that indoor environments maintain consistent comfort levels while minimizing energy consumption. The variable-speed compressor operates at different speeds based on the cooling demand, leading to reduced energy costs and improved overall efficiency.

In terms of energy performance, both models boast high Seasonal Energy Efficiency Ratios (SEER) and Heating Seasonal Performance Factors (HSPF). This not only contributes to lower energy bills but also helps in meeting energy efficiency standards and regulations in various regions. This makes the 40QNC and 40QNQ ideal for environmentally conscious building projects aiming for sustainability.

Another notable feature is the advanced microchannel coil technology utilized in these units. Microchannel coils are lighter, more compact, and provide enhanced heat exchange capabilities compared to traditional coils. This technology contributes to a more efficient refrigerant flow and ultimately leads to improved performance and durability of the unit.

Moreover, both models come equipped with a robust control system that enhances user interface. With smart thermostat compatibility, users can easily manage their building's climate remotely, ensuring optimal comfort and energy management. These systems are designed to integrate seamlessly with building management systems (BMS), allowing for greater control and optimization.

The construction of the Carrier 40QNC and 40QNQ also deserves mention. The units are built with durable materials designed to withstand harsh weather conditions, providing longevity and reliability. Additionally, the low sound levels produced by these units make them suitable for noise-sensitive settings, ensuring comfort without disruptive operation.

In summary, the Carrier 40QNC and 40QNQ are exemplary rooftop packaged units that combine advanced technology, energy efficiency, and reliable performance. Their variable-speed operation, microchannel coil technology, and robust control systems make them ideal solutions for commercial heating and cooling needs, catering to both comfort and sustainability.