START-UP

Unit Preparation — Make sure that unit has been in- stalled in accordance with these installation instructions and applicable codes.

Return-Air Filters — Make sure correct filters are in- stalled in filter tracks. See Table 1. Do not operate unit without return-air filters.

Compressor Mounting — Compressors are internally spring mounted. Do not loosen or remove compressor hold- down bolts.

Internal Wiring — Check all electrical connections in unit control boxes. Tighten as required.

Refrigerant Service Ports — To service refrigerant service ports, remove compressor access panel. Each unit sys- tem has 4 Schrader-type service gage ports: one on the suction line, one on the liquid line, and two on the compressor dis- charge line. Be sure that caps on the ports are tight. One Schrader-type valve is located under both the high-pressure switch and the low-pressure switch.

High Flow Valves — Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with o-rings located inside the caps. These valves cannot be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.

Compressor Rotation — On 3-phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compres- sor is rotating in the proper direction:

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pres- sure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pres- sure does not rise to normal levels:

1.Note that the evaporator fan is probably also rotating in the wrong direction.

2.Turn off power to the unit.

3.Reverse any two of the unit power leads.

4.Reapply power to the compressor.

The suction and discharge pressure levels should now move to their normal start-up levels.

NOTE: When the compressor is rotating in the wrong direc- tion, the unit makes an elevated level of noise and does not provide cooling.

Cooling — Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust ther- mostat to a setting below room temperature. Compressor starts on closure of contactor.

Check unit charge. Refer to Service, Refrigerant Charge section, page 39.

Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after 30-second delay.

TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting thermostat at a position above room tem- perature shuts unit off temporarily until space temperature ex- ceeds thermostat setting.

Main Burners — Main burners are factory set and should require no adjustment.

TO CHECK ignition of main burners and heating controls, move thermostat set point above room temperature and verify that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the thermostat setting below room temperature and verify that the burners and evaporator fan turn off. (Fan will turn off only if fan selector switch is in the AUTO. position.)

Refer to Table 30 for the correct orifice to use at high altitudes.

Table 30 — Altitude Compensation*

 

74,000 AND 115,000

150,000 BTUH

 

BTUH NOMINAL

 

NOMINAL INPUT

 

INPUT

ELEVATION

 

 

(ft)

Natural

Liquid

Natural

Liquid

Gas

Propane

Gas

Propane

 

 

Orifice

Orifice

Orifice

Orifice

 

Size†

Size†

Size†

Size†

0-2,000

33

43

30

38

2,000

34

43

30

39

3,000

35

44

31

40

4,000

36

44

32

41

5,000

36

44

33

42

6,000

37

45

34

43

7,000

37

45

35

43

8,000

38

46

36

44

9,000

39

47

37

44

10,000

41

48

38

45

11,000

43

48

39

45

12,000

44

49

40

46

13,000

44

49

41

47

14,000

45

50

42

47

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.

†Orifices available through your Carrier distributor.

Heating

1.Purge gas supply line of air by opening union ahead of gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.

2.Turn on electrical supply and manual gas valve.

3.Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature.

4.The induced-draft motor will start.

5.After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lock- out. To reset the control, break the 24-v power to W1.

6.The evaporator-fan motor will turn on 45 seconds after the burners are ignited.

7.The evaporator-fan motor will turn off 45 seconds after thermostat temperature is satisfied.

8.Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.

NOTE: The default value for the evaporator-fan motor ON/ OFF delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be extended to 180 seconds. When one flash of the LED is observed, the evaporator-fan ON/OFF delay has been modified.

36

Image 36
Contents Installation, Start-Up, Service Instructions Field Fabricate Ductwork Secure all Rig and Place Unit Inspect unit forRoof Curb Dimensions Install Flue Hood Flue hood is shipped Install Gas Piping Unit is equipped forPhysical Data 48TF004-007 Unit Size 48TFFurnace Section Base Unit Dimensions Make Electrical Connections Steel Pipe Nominal DiameterFeet Or largerTerminal Block AHAElectrical Data Supply SizeType FLA RLA LRAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Position SettingTypical Access Panel Locations Horizontal Discharge Block-Off Plate Wiring Connections for Outdoor-Air Thermostat Completed Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Default Potentiometer Settin gs SettingsPotentiometer Default Setting CO2 SP PPM Chan geover Set PointsAdjust Evaporator-Fan Speed Ad Direct Drive Motor MountingFan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure* in. wg 48TF004-007Motor Data 48TF004 3 Tons Standard Motor Direct Drive 48TF004 3 Tons Alternate Motor Belt Drive48TF004 3 Tons HIGH-STATIC Motor Belt Drive 48TF005 4 Tons Standard Motor Direct Drive48TF005 4 Tons Alternate Motor Belt Drive 48TF006 5 Tons Standard Motor Direct Drive 48TF006 5 Tons Alternate Motor Belt Drive48TF006 5 Tons HIGH-STATIC Motor Belt Drive 48TF007 6 Tons Standard Motor Belt Drive 48TF007 6 Tons HIGH-STATIC Motor Belt Drive 109 149189 2291028 10641005 93848TF005 4 Tons Alternate Motor Belt Drive 48TF005 4 Tons HIGH-STATIC Motor Belt Drive 1600 770 420 826 483 1700 811 494 865 5671800 852 578 1900 894 5671221 1600 826 483 931 641 1020 788 1101 956 11781252 1700 865 567 966 725 1051 883 1133 1061 1205885 623 942 700 928 700 982 779971 787 1022 867 1015 891 1063 9981900 982 779 1084 932 1160 1006 1223 1114 2000 1022 867 1121 1014 1188 1097 1254 12162100 1063 998 1140 1064 1196 1272 1292 2200 1104 1081 1159 1106 1229 1258Heating Altitude CompensationBtuh Nominal Nominal InputPage Service Economizer Adjustment Refer to Optional Econo LubricationTON Unit Charging Chart Cooling Charging Chart, 48TF006 TON Unit 60 Hz Charging ChartLED Error Code Description LED Indication Error Code DescriptionOFF FlashesBurner Tray Details LED Error Code Service Analysis Heating Service AnalysisProblem Cause Remedy LED OFFCooling Service Analysis Durablade Economizer Troubleshooting IFCEconoMi$er Troubleshooting Typical Wiring Diagram and Component Arrangement SAT CAPSEN SW1Copyright 2000 Carrier Corporation Page Remove and Use in Job File Preliminary Information

48TF004-007 specifications

The Carrier 48TF004-007 is part of the brand's renowned rooftop unit series, designed to deliver efficient, reliable performance for commercial applications. Ideal for spaces such as offices, retail stores, and small manufacturing facilities, these units encapsulate advanced technology to enhance indoor air quality and optimize climate control.

One of the standout features of the Carrier 48TF004-007 units is their variable speed compressor technology. This innovation not only allows for precise temperature control but also reduces energy consumption by modulating the compressor's speed according to the cooling or heating demand. By operating at lower speeds during less demanding conditions, these units significantly decrease energy usage compared to traditional single-speed compressors, contributing to lower utility bills and a reduced carbon footprint.

Energy efficiency is further enhanced with the inclusion of high-performance scroll compressors, which are known for their reliable operation and quiet performance. Coupled with an Energy Efficiency Ratio (EER) that meets or exceeds industry standards, these systems are designed to offer economical operation without sacrificing comfort.

Incorporating smart controls and connectivity features, the Carrier 48TF004-007 units allow for easy integration into building management systems (BMS). This enhances the ability to monitor and manage energy usage in real time, further promoting efficiency. The units are also compatible with various thermostat options, allowing for user-friendly operation and customization of settings.

Another significant characteristic of the Carrier 48TF004-007 is its durable construction. Built with galvanized steel and powder-coated finishes, these units are designed to withstand the rigors of outdoor installation, ensuring long-lasting performance even in harsh weather conditions. Additionally, the units come equipped with advanced filtration systems that help improve indoor air quality by effectively removing dust, allergens, and other particulate matter from the air.

Maintenance is simplified with the Carrier 48TF004-007, providing easy access to vital components, which supports reduced downtime and service costs. The units also feature low operating sound levels, making them suitable for noise-sensitive applications.

In conclusion, the Carrier 48TF004-007 rooftop units stand out for their energy efficiency, advanced technology, durability, and ease of maintenance, making them an excellent choice for any commercial space looking to enhance comfort while effectively managing operational costs.