Carrier 50PG03-07 installation instructions Field Control Thermidistat Wiring

Page 10

50PG03-- 07

Temperature Control

The unit can be controlled with either a Carrier-approved space temperature sensor, a Carrier accessory Thermidistatt device, or a Carrier-approved accessory thermostat. Install the temperature control device according to the installation instructions included with the accessory. Locate the device on a solid interior wall in the conditioned space to sense average temperature. Carrier space temperature sensor wiring connections are shown in Fig. 10. General thermostat field control wiring connections are shown in Fig. 9. Carrier Thermidistat device wiring connections are shown in Fig. 11. Configuration of the unit control is required to specify the control input type before unit operation.

Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 9-11.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.

Set heat anticipator settings as follows:

VOLTAGE

Stage 1

STAGE 1 AND 2

(W1) ON

(W1 AND W2) ON

 

 

 

 

All

0.2

0.4

Settingsmay be changed slightly to provide a greater degree of comfort for a particular installation.

Humidity Control

Unit can be controlled with either a Carrier accessory Thermidistat device or a Carrier-approved accessory humidistat (switch output). The input for an accessory humidity sensor with 4 to 20 mA output is another option available when an economizer board is installed. Install the humidity control device according to the installation instructions included with the accessory. Locate the device on a solid interior wall in the conditioned space to sense average humidity. Carrier Thermidistat device wiring connections are shown in Fig. 11. General humidistat wiring connections are shown in Fig. 12. Configuration of the unit control is required to specify the control input type before unit operation. Refer to the

Controls, Start-up, Operation and Troubleshooting manual for configuration.

Units with the Humidi-MiZertoption receive a discrete input from a field-installed device (such as from the Carrier humidistat or Thermidistat device). The discrete input is connected to the TB1 terminal strip points labeled Humidistat 1 and 2. As this is a discrete input, one of the connection points is for power to the switch and the other is the return path. (See Fig. 12.)

A space relative humidity sensor input (SP.RH) is only available if an economizer board (ECB) is installed in the unit and then the sensor can be connected to the OAQ point TB1-4. (See Fig. 12.) This input is used instead of the discrete humidistat or thermidistat inputs. The input controls the Humidi-MiZer using the 4 to 20 mA as percent humidity. The relative humidity value (measured by the relative humidity sensor) can be displayed on the Scrolling Marquee, in the space through a System Pilott device, or can be read by other CCN devices where it can be used to perform more advanced functions. The humidity sensor must be configured correctly; refer to the Controls, Start-up, Operation, and Troubleshooting manual for details.

If the customer also wishes to install a smoke detector into a Humidi-MiZer equipped 50PG unit, the fire shutdown connection points are on Plug PL-19, located in the economizer section. See the unit wiring schematic for wiring. For third-party smoke detector, see Fig. 13.

Point 19-3 is the 24 vac power source for the detector and point 19-5 is the 24 vac signal input for fire shutdown.

More information is available in the third party control section of the Controls, Start-up, Operation, and Troubleshooting manual.

 

 

 

 

 

 

 

 

 

 

THERMIDISTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEHUM

 

 

OC

 

R

 

Y1

 

Y2

 

W1

 

W2

 

G

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB1

 

5

 

R

 

Y1

 

Y2

 

W1

 

W2

 

G

 

C

 

1

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HUMIDISTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOFTOP UNIT

 

 

 

 

 

 

 

C07055

Fig. 11 - Field Control Thermidistat Wiring

C07045

Fig. 12 - Humidi-MiZer Low-Voltage Terminal Strip - Humidity Sensor/Humidity Wiring

10

Image 10
Contents Installation Instructions 50PG03 Base Unit Dimensions Provide Unit Support Rig and Place UnitRefrigerant Type Base Unit 50PGCompressor Condenser CoilEvaporator FAN RETURN-AIR FiltersField Fabricate Ductwork Install External Trap for Condensate DrainMake Unit Duct Connections Field Power Supply Make Electrical ConnectionsField Power Wiring Connections Field Control Thermidistat Wiring Third Party Smoke Detector on Humidi-MiZert Exhaust IFM Electric Heat Power Supply Disconnect Unit Range SizeNominal Voltage Compressor OFM RLA LRA FLA TypeRLA LRA Electric Heat Power SupplyVoltage Compressor Type FLA50PG03 Range IFM IFM Electric Heat Power SupplyRLA LRA FLA IFM Electric Heat Power Supply Disconnect Range IFM SizeRange Size Electric Heat Power Supply DisconnectVoltage Compressor OFM RLA13.9 15.0 23.9 13.9 15.0 22.1 High575-3-60 518 633 13.9 15.0 22.1 36.3 37.1RLA LRA FLA Type 18.5 20.0 27.8 17.3 15.0 27.617.3 15.0 28.4 18.5 20.0 29.551.8/57.5 38.5/38.539.3/43.1 64.3/72.0Install Outdoor Air Hoods Units with Economizer Install All Accessories

50PG03-07 specifications

The Carrier 50PG03-07 is a cutting-edge rooftop unit designed to provide exceptional heating and cooling capabilities for commercial spaces. Known for its durability and efficiency, this model is part of Carrier's renowned line of packaged rooftop units, combining advanced technologies with a user-friendly design.

One of the standout features of the 50PG03-07 is its energy efficiency. This unit is equipped with a high-efficiency compressor that maximizes performance while minimizing energy consumption. The unit often boasts a high SEER (Seasonal Energy Efficiency Ratio) rating, making it an environmentally friendly choice for businesses looking to reduce their operating costs and carbon footprint.

The 50PG03-07 incorporates advanced controls, including a microprocessor-based control system that allows for precise temperature management and monitoring. This system not only enhances user comfort but also provides diagnostic capabilities, ensuring the unit operates at peak performance and identifying any potential issues early on.

In terms of design, the Carrier 50PG03-07 features a compact and robust structure that is built to withstand various weather conditions, ensuring longevity and reliability. The unit’s easy access panels simplify maintenance, allowing technicians to perform routine checks and repairs without cumbersome disassembly.

The air distribution system of the 50PG03-07 is engineered for optimal airflow, enhancing comfort across different areas of a building. It features multiple options for air handling, including variable air volume controls, which allows for customized air delivery to suit specific space requirements.

Noise reduction technology is also a priority in this model. The unit is designed to operate quietly, minimizing disruptions in office environments, retail settings, or other commercial spaces. This ensures that occupants can focus on their tasks without being disturbed by mechanical sounds.

Furthermore, the Carrier 50PG03-07 is adaptable with various accessories that can enhance its functionality, such as economizers for improved ventilation and humidity control. By integrating these components, businesses can create an efficient and effective HVAC system tailored to their specific needs.

Finally, the Carrier 50PG03-07 meets stringent industry standards for safety and performance, providing users with peace of mind. With its blend of innovative technology, energy efficiency, and construction resilience, the 50PG03-07 remains a popular choice for businesses seeking reliable climate control solutions.