1 | 2 | 3 | 4 | 5 | 6 | RED(+) |
|
|
|
|
|
| WHT(GND) | CCN COM | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| SEN |
|
|
|
|
| SW1 |
|
|
|
|
|
|
|
|
|
|
| BRN (GND) | SENSOR WIRING | |
|
|
|
|
| BLU (SPT) |
|
|
|
|
|
|
|
|
| |
50TC |
|
|
|
|
|
| C08201 | |
|
|
|
|
|
| |||
Fig. 30 - | ||||||||
| ||||||||
| Connect | |||||||
| connections. Connect the | |||||||
| terminals 1 and 3 (see Fig. 31). |
| ||||||
|
|
| TB1 | PL | ||||
| SEN | 1 |
|
|
| |||
|
|
|
| |||||
| SEN | 3 |
|
|
| |||
|
|
|
|
C08212
Fig. 31 - PremierLink T-55 Sensor
Connect
1 | 2 | 3 | 4 | 5 | 6 | RED(+) |
|
|
|
|
|
| WHT(GND) | CCN COM | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| SEN |
| SET |
|
|
| SW1 |
|
|
|
| BLK |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| (T56) |
|
|
|
|
|
| BRN (GND) | SENSOR WIRING | |
|
|
|
|
| BLU (SPT) |
| |
|
|
|
|
|
|
| JUMPER |
|
|
|
|
|
|
| TERMINALS |
|
|
|
|
|
|
| AS SHOWN |
Cool Warm
C08202
Fig. 32 - T-56 Internal Connections
| TB1 | PL |
SEN | 1 | |
| TB1 | PL |
SEN | 3 |
Jumper
SET
SET 5
C08213
Fig. 33 - PremierLink T-56 Sensor
Connect Thermostat — A
If the 50TC unit is equipped with
SPACECTB
THERMOSTAT THERMOSTAT
R R
TB1PL
G 2
Y1 4
Y2 6
W1 8
W2 10
C | C | CTB |
THERMOSTAT
C08119
Fig. 34 - Space Thermostat Connections
If the 50TC unit has an economizer system and
Configure the unit for Thermostat Mode — Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.
22