Carrier 50TC installation instructions Field Fabricate Ductwork, Unit Leveling Tolerances

Page 10

MAXIMUM ALLOWABLE

DIFFERENCE IN. (MM)

A-B

B-C

A-C

0.5” (13)

1.0” (25)

1.0” (25)

C06110

Fig. 6 - Unit Leveling Tolerances

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 87 Pa (0.35 in. wg) with economizer or 112 Pa (0.45 in. wg) without economizer.

For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.

Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

For units with accessory electric heaters: Horizontal applications require a minimum clearance to combustible surfaces of 25 mm (1-in) from duct for first 305 mm (12-in) away from unit. Vertical applications do not require a minimum clearance.

Minimum clearance is not required around ductwork.

50TC

 

 

PLACE ALL SEAL STRIP

DETAIL A

“B”

914-1371

IN PLACE BEFORE PLACING

UNIT ON ROOF CURB

 

 

(36"-54")

 

 

 

 

 

 

DUCT END

 

 

“C”

SEE DETAIL “A”

 

 

 

 

FAN

 

 

 

SIDE

“A”

 

 

 

 

 

 

 

 

C09458

 

MAX WEIGHT

 

 

 

DIMENSIONS

 

 

 

UNIT

 

A

 

B

 

C

 

 

 

 

 

 

KG

LB

MM

 

IN

MM

 

IN

MM

 

IN

50TC-A07

336

740

1890

 

74.5

965

 

38.0

850

 

33.5

 

 

 

 

 

 

 

 

 

 

 

 

50TC-D08

641

1410

2235

 

88.0

1040

 

41.0

1055

 

41.5

 

 

 

 

 

 

 

 

 

 

 

 

50TC-D09

693

1525

2235

 

88.0

1030

 

40.5

1255

 

49.5

 

 

 

 

 

 

 

 

 

 

 

 

50TC-D12

711

1565

2235

 

88.0

1015

 

40.0

1255

 

49.5

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Dimensions in ( ) are in inches.

2.Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 7 - Rigging Details

10

Image 10
Contents Installation Instructions 50TC Unit Dimensional Drawing 07 Size Units Unit Dimensional Drawing 07 Size Unit Unit Dimensional Drawing 08, 09 and 12 Size Units Plan for Unit Location Roof mountInspect unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details 07 Size Units Roof Curb Details 08 12 Size Units Field Fabricate Ductwork Unit Leveling TolerancesEconomizer Hood Removal and Setup Factory Option Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Rig and Place UnitFactory Option Two Position Damper Hood Removal and SetupEconomizer Hood and Two-Position Hood Install External Condensate Trap and Line Make Electrical ConnectionsAll units Units with Factory-Installed DisconnectThru-Base Connections Units without Thru-Base Connections Field Control WiringHeat Anticipator Settings ThermostatElectric Heaters Heater Model NumberAccessory Electric Heater Control Connections PremierLinkt Factory-Option PremierLink ControllerPremierLink Wiring Schematic PremierLink Sensor Usage 33ZCT55SPT CRTEMPSN001A00Space Sensor Mode Thermostat Mode55 Space Temperature Sensor Wiring Enthalpy Switch HH57AC077 Connections Economizer controlsIndoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection PremierLink Wiring Fan Pressure Switch ConnectionColor Code Recommendations PremierLink CCN Bus ConnectionsRTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsConnecting Discrete Inputs Filter Status RTU-MP / Indoor CO2 Sensor 33ZCSENCO2 ConnectionsFan Status Communication Wiring Protocols GeneralRemote Occupancy Local Access RTU-MP Troubleshooting Communication LEDsLEDs LEDs on the RTU-MP show the status of certain functionsEconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsInstall Accessories Pre-Start and Start-UpUnit Wire/MOCP Sizing Data STD17.5 108 Disc 50TC Catalog No 50TC---C02SI

50TC specifications

The Carrier 50TC is a cutting-edge commercial rooftop unit designed for optimal performance and reliability in a variety of HVAC applications. This unit is particularly well-suited for small to medium-sized facilities that require efficient heating, ventilation, and air conditioning solutions. A hallmark of the Carrier 50TC is its impressive energy efficiency, enabling users to significantly lower their operational costs while maintaining a comfortable indoor environment.

One of the standout features of the Carrier 50TC is its advanced performance technologies. The unit employs a high-efficiency scroll compressor that enhances refrigerant management, allowing for exceptional cooling capacities while minimizing energy consumption. Additionally, the unit is equipped with variable speed fans, which further contribute to its operational efficiency. These fans adjust their speed according to the cooling demands, allowing the system to consume energy only when necessary.

The Carrier 50TC also incorporates an innovative control system that provides intelligent diagnostics and an array of customizable settings. This system helps in monitoring the unit's performance, ensuring maximum efficiency and early detection of potential maintenance issues. Users can easily integrate the unit within their existing building management systems, enhancing overall operational control and streamlining HVAC management procedures.

Durability and ease of maintenance are key characteristics of the Carrier 50TC, designed specifically to withstand harsh weather conditions while providing long-lasting performance. The unit's robust construction includes a powder-coated cabinet, which not only improves its aesthetic appeal but also protects against corrosion, ensuring longevity.

Moreover, the Carrier 50TC is designed with eco-friendliness in mind. It utilizes environmentally friendly refrigerants, aligning with modern regulations aimed at reducing the impact of HVAC systems on the environment. By choosing the Carrier 50TC, businesses can contribute to sustainability efforts while enjoying effective temperature control.

In summary, the Carrier 50TC combines energy efficiency, advanced technologies, and robust design to deliver a reliable HVAC solution for commercial applications. With its smart control system, high-efficiency components, and eco-friendly operation, the Carrier 50TC sets a standard for performance and sustainability in the commercial heating and cooling market.