Carrier 50RHE006-060 specifications Troubleshooting, Fault Heating Cooling Possible Cause Solution

Page 26

Table 16 — Troubleshooting

FAULT

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Main Power Problems

X

X

Green Status LED Off

Check line voltage circuit breaker and disconnect.

 

 

 

 

Check for line voltage between L1 and L2 on the contactor.

 

 

 

 

Check for 24 vac between R and C on controller.

 

 

 

 

Check primary/secondary voltage on transformer.

HP Fault — Code 2

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

High Pressure

 

 

cooling

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

 

 

 

X

Water temperature out of

Bring water temperature within design parameters.

 

 

 

range in cooling

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

heating

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

Dirty air coil — construction dust etc.

 

 

 

 

External static too high. Check Table 4.

 

X

 

Air temperature out of range

Bring return air temperature within design parameters.

 

 

 

in heating

 

 

X

X

Overcharged with refrigerant

Check superheat/subcooling vs typical operating condition Table 9.

 

X

X

Bad HP switch

Check switch continuity and operation. Replace.

LP/LOC Fault — Code 3

X

X

Insufficient charge

Check for refrigerant leaks.

Low Pressure/Loss of

 

 

 

 

X

 

Compressor pump down at

Check charge and start-up water flow.

Charge

 

 

 

start-up

 

 

 

 

 

FP1 Fault — Code 4

X

 

Reduced or no water flow in

Check pump operation or water valve operation/setting.

Water Freeze Protection

 

 

heating

 

 

 

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

X

 

Inadequate antifreeze level

Check antifreeze density with hydrometer.

 

X

 

Improper freeze protect set-

Clip JW2 jumper for antifreeze (–12.2 C) use.

 

 

 

ting (–1.1 C vs –12.2 C)

 

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

range

 

 

X

X

Bad thermistor

Check temperature and impedance correlation.

FP2 Fault — Code 5

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Air Coil Freeze

 

 

cooling

 

 

 

Check fan motor operation and airflow restrictions.

Protection

 

 

 

 

 

 

External static too high. Check Table 4.

 

 

 

 

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering air temperature within design

 

 

 

 

parameters.

 

 

X

Improper freeze protect set-

Normal airside applications will require –1.1 C only.

 

 

 

ting (–1.1 C vs –12.2 C)

 

 

X

X

Bad thermistor

Check temperature and impedance correlation.

Condensate Fault —

X

X

Blocked drain

Check for blockage and clean drain.

Code 6

 

 

 

 

X

X

Improper trap

Check trap dimensions and location ahead of vent.

 

 

 

X

Poor drainage

Check for piping slope away from unit.

 

 

 

 

Check slope of unit toward outlet.

 

 

 

 

Poor venting. Check vent location.

 

 

X

Moisture on sensor

Check for moisture shorting to air coil.

Over/Under Voltage —

X

X

Under voltage

Check power supply and 24 vac voltage before and during operation.

Code 7

 

 

 

 

 

 

 

Check power supply wire size.

(Auto Resetting)

 

 

 

 

 

 

Check compressor starting.

 

 

 

 

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply voltage.

 

X

X

Over voltage

Check power supply voltage and 24 vac before and during operation.

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply voltage.

Performance Monitor —

X

 

Heating mode FP2> 51.7 C

Check for poor airflow or overcharged unit.

Code 8

 

 

 

 

 

X

Cooling mode FP1> 51.7 C

Check for poor water flow or airflow.

 

 

 

 

 

OR FP2< 4.4 C

 

FP1 and FP2

X

 

FP1 temperature is higher

Swap FP1 and FP2 thermistors.

Thermistors —

 

 

than FP2 temperature.

 

Code 9

 

 

 

 

 

X

FP2 temperature is higher

Swap FP1 and FP2 thermistors.

 

 

 

 

 

than FP1 temperature.

 

No Fault Code Shown

X

X

No compressor operation

See scroll compressor rotation section.

 

X

X

Compressor overload

Check and replace if necessary.

 

X

X

Control board

Reset power and check operation.

Unit Short Cycles

X

X

Dirty air filter

Check and clean air filter.

 

X

X

Unit in 'Test Mode'

Reset power or wait 20 minutes for auto exit.

 

X

X

Unit selection

Unit may be oversized for space. Check sizing for actual load of space.

 

X

X

Compressor overload

Check and replace if necessary.

Only Fan Runs

X

X

Thermostat position

Ensure thermostat set for heating or cooling operation.

 

X

X

Unit locked out

Check for lockout codes. Reset power.

 

X

X

Compressor overload

Check compressor overload. Replace if necessary.

 

X

X

Thermostat wiring

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

operation in Test mode.

LEGEND

 

 

 

 

RV — Reversing Valve

 

 

 

 

26

Image 26
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data Aquazone 50RHE006-060 Units Unit 50RHELeft Return Right ReturnTypical Installation 50RHE Units Conversion Left Return, Side Discharge to Back Discharge 030,036 Dimensions mm50RHE Units 042,048Typical Ground-Water Piping Installation Condition Acceptable Level Electrical WiringWater Quality Guidelines RVS PSCCAP FP1Comp Blower Motor Capacitor Performance Monitor Blower Relay Loss of Charge Pressure Switch Motorized ValveBMC Sensor, Air Coil Freeze ProtectionTypical Aquazone Deluxe D Control Wiring 3-Phase Unit Unit Circuit 50RHE VOLTS-PHASE Voltage Compressor FAN Total MIN MAXElectrical Data RLA LRA FUSE/HACR FLAAirflow 50RHE Blower Performance50RHE Unit SpeedLow Voltage Wiring See Fig PRE-START-UPControl Jumper Settings See Field Selectable InputsOperating Limits Control Accessory Relay ConfigurationsSTART-UP Water Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Cooling HeatingTypical Unit Operating Pressures and Temperatures 50RHE Coaxial Water Pressure DropOperation Approximate Fluid Volume L Per 30 m of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlSystem Test Control Current LED Status Alarm Relay OperationsControl LED Code Fault Descriptions Description Status LED Test LED ServiceAlarm Relay ESDGravity Flow Method Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Troubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate Page Page Copyright 2004 Carrier Corporation 50RHE R-407C Unit START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis

50RHE006-060 specifications

The Carrier 50RHE006-060 is a robust commercial rooftop unit designed for efficient heating and cooling in various applications. This model is part of Carrier’s renowned line of HVAC systems, known for their reliability and performance. With a nominal cooling capacity of 5 tons and heating capacity of 6 tons, this unit is suitable for medium-sized commercial spaces such as retail stores, offices, and schools.

One of the standout features of the Carrier 50RHE006-060 is its advanced scroll compressor technology. This type of compressor is recognized for its efficiency and durability, offering quiet operation while minimizing energy consumption. The inclusion of a variable-speed blower motor enhances comfort by providing consistent airflow while also reducing energy costs by adjusting the speed according to the demand.

Another key characteristic is its integrated microprocessor control system, which allows for precise temperature management. This feature not only provides optimal comfort but also ensures energy savings. The system’s controls can be easily integrated with existing building management systems, allowing for seamless operation and monitoring.

The Carrier 50RHE006-060 boasts enhanced insulation properties, which help reduce noise during operation and improve energy efficiency. Its robust design can withstand various weather conditions, making it a reliable choice for rooftop installation. Moreover, it is designed with accessibility in mind, featuring service doors that allow for easy maintenance, reducing downtime and operational costs.

In terms of efficiency, the unit is designed to meet or exceed EPA energy efficiency standards. It utilizes environmentally friendly refrigerants, adhering to regulations aimed at reducing greenhouse gas emissions. Additionally, the design includes a high-efficiency heat exchanger, which maximizes heat transfer and improves overall performance.

The Carrier 50RHE006-060 is also equipped with a dual-stage heat function, allowing it to provide optimal heating for varying weather conditions, ensuring comfort during the colder months. Furthermore, the unit’s design incorporates features such as hot gas bypass for improved dehumidification, making it adaptable to different climates and enhancing indoor air quality.

In summary, the Carrier 50RHE006-060 stands out with its efficient compressor technology, smart control systems, robust construction, and environmentally conscious design. These features make it a top choice for commercial spaces seeking an effective, reliable, and energy-efficient heating and cooling solution.