Carrier 50RHE006-060 specifications Contents, Safety Considerations

Page 1

Aquazone™ 50RHE006-060 Water Source Heat Pumps Horizontal Unit 50 Hz, CE Mark R-407C

Installation, Start-Up, and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16

Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2

Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

STORAGE

PROTECTION

INSPECT UNIT

Step 3 — Unit Location. . . . . . . . . . . . . . . . . . . . . . . . . . . 6

• FIELD CONVERSION OF DISCHARGE AIR

Step 4 — Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . 7 Step 5 — Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

SOUND ATTENUATION

EXISTING DUCT SYSTEM

Step 6

— Condensate Drain

7

• VENTING

 

Step 7

— Piping Connections

8

WATER LOOP APPLICATIONS

GROUND-WATER APPLICATIONS

GROUND-LOOP APPLICATIONS

Step 8 — Electrical Wiring. . . . . . . . . . . . . . . . . . . . . . . . 9

POWER CONNECTION

SUPPLY VOLTAGE

220-VOLT OPERATION

PSC BLOWER SPEED SELECTION

Step 9 — Low Voltage Wiring. . . . . . . . . . . . . . . . . . . . 16

THERMOSTAT CONNECTIONS

WATER FREEZE PROTECTION

AIR COIL FREEZE PROTECTION

ACCESSORY CONNECTIONS

WATER SOLENOID VALVES

PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16,17 System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .17,18

C Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 17

C Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 17

D Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 17

D Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 17

D Control Accessory Relay Configurations . . . . . 18

Water Valve (Slow Opening) . . . . . . . . . . . . . . . . . . . 18

Outdoor Air Damper (OAD) . . . . . . . . . . . . . . . . . . . . 18

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-21

Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 19

Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 19

Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 19

Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 21

Page

Ground Coupled, Closed Loop and Plateframe Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 21

OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21,22 Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Units with Aquazone Complete C Control . . . . . . . 21 Units with Aquazone Deluxe D Control . . . . . . . . . . 21

SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22,23 Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Aquazone Deluxe D Control LED Indicators . . . . . 23

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-25 Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 24 Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 24 Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 24 Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 25

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 25-27 Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

START-UP CHECKLIST . . . . . . . . . . . . . . . . . . CL-1, CL-2

IMPORTANT: Read the entire instruction manual before starting installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo- nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func- tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau- tions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Improper installation, adjustment, alteration, service, main- tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individ- ual instructions packaged with the kits or accessories when installing.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

Catalog No. 005-00042

Printed in U.S.A.

Form 50RHE-C1SI

Pg 1

2-04

Replaces: New

Tab

5a

5a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 1
Contents Safety Considerations ContentsGeneral InstallationUnit 50RHE Physical Data Aquazone 50RHE006-060 UnitsRight Return Left ReturnTypical Installation 50RHE Units Conversion Left Return, Side Discharge to Back Discharge 50RHE Units Dimensions mm030,036 042,048Typical Ground-Water Piping Installation Water Quality Guidelines Electrical WiringCondition Acceptable Level CAP PSCRVS FP1Comp BMC Loss of Charge Pressure Switch Motorized ValveBlower Motor Capacitor Performance Monitor Blower Relay Sensor, Air Coil Freeze ProtectionTypical Aquazone Deluxe D Control Wiring 3-Phase Unit Electrical Data 50RHE VOLTS-PHASE Voltage Compressor FAN Total MIN MAXUnit Circuit RLA LRA FUSE/HACR FLA50RHE 50RHE Blower PerformanceAirflow Unit SpeedPRE-START-UP Low Voltage Wiring See FigField Selectable Inputs Control Jumper Settings SeeSTART-UP Control Accessory Relay ConfigurationsOperating Limits Unit Start-Up Heating Mode Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Cooling Heating50RHE Coaxial Water Pressure Drop Typical Unit Operating Pressures and TemperaturesAntifreeze Percentages by Volume Approximate Fluid Volume L Per 30 m of PipeOperation Units with Aquazone Complete C ControlControl LED Code Fault Descriptions Control Current LED Status Alarm Relay OperationsSystem Test Alarm Relay ServiceDescription Status LED Test LED ESDGravity Flow Method Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Fault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Page Page Copyright 2004 Carrier Corporation II. START-UP 50RHE R-407C Unit START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis

50RHE006-060 specifications

The Carrier 50RHE006-060 is a robust commercial rooftop unit designed for efficient heating and cooling in various applications. This model is part of Carrier’s renowned line of HVAC systems, known for their reliability and performance. With a nominal cooling capacity of 5 tons and heating capacity of 6 tons, this unit is suitable for medium-sized commercial spaces such as retail stores, offices, and schools.

One of the standout features of the Carrier 50RHE006-060 is its advanced scroll compressor technology. This type of compressor is recognized for its efficiency and durability, offering quiet operation while minimizing energy consumption. The inclusion of a variable-speed blower motor enhances comfort by providing consistent airflow while also reducing energy costs by adjusting the speed according to the demand.

Another key characteristic is its integrated microprocessor control system, which allows for precise temperature management. This feature not only provides optimal comfort but also ensures energy savings. The system’s controls can be easily integrated with existing building management systems, allowing for seamless operation and monitoring.

The Carrier 50RHE006-060 boasts enhanced insulation properties, which help reduce noise during operation and improve energy efficiency. Its robust design can withstand various weather conditions, making it a reliable choice for rooftop installation. Moreover, it is designed with accessibility in mind, featuring service doors that allow for easy maintenance, reducing downtime and operational costs.

In terms of efficiency, the unit is designed to meet or exceed EPA energy efficiency standards. It utilizes environmentally friendly refrigerants, adhering to regulations aimed at reducing greenhouse gas emissions. Additionally, the design includes a high-efficiency heat exchanger, which maximizes heat transfer and improves overall performance.

The Carrier 50RHE006-060 is also equipped with a dual-stage heat function, allowing it to provide optimal heating for varying weather conditions, ensuring comfort during the colder months. Furthermore, the unit’s design incorporates features such as hot gas bypass for improved dehumidification, making it adaptable to different climates and enhancing indoor air quality.

In summary, the Carrier 50RHE006-060 stands out with its efficient compressor technology, smart control systems, robust construction, and environmentally conscious design. These features make it a top choice for commercial spaces seeking an effective, reliable, and energy-efficient heating and cooling solution.