Carrier 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM specifications Occupancy Schedule Information Screen

Page 36

Table 7 — Occupancy Schedule Information Screen

DESCRIPTION

DEFAULT

POINT NAME

Manual Override Hours

0

OVRD

Period 1: Day of Week

11111111

DOW1

Period 1: Occupied From

00:00

OCC1

Period 1: Occupied To

24:00

UNOCC1

Period 2: Day of Week

00000000

DOW2

Period 2: Occupied From

00:00

OCC2

Period 2: Occupied To

24:00

UNOCC2

Period 3: Day of Week

00000000

DOW3

Period 3: Occupied From

00:00

OCC3

Period 3: Occupied To

24:00

UNOCC3

Period 4: Day of Week

00000000

DOW4

Period 4: Occupied From

00:00

OCC4

Period 4: Occupied To

24:00

UNOCC4

Period 5: Day of Week

00000000

DOW5

Period 5: Occupied From

00:00

OCC5

Period 5: Occupied To

24:00

UNOCC5

Period 6: Day of Week

00000000

DOW6

Period 6: Occupied From

00:00

OCC6

Period 6: Occupied To

24:00

UNOCC6

Period 7: Day of Week

00000000

DOW7

Period 7: Occupied From

00:00

OCC7

Period 7: Occupied To

24:00

UNOCC7

Period 8: Day of Week

00000000

DOW8

Period 8: Occupied From

00:00

OCC8

Period 8: Occupied To

24:00

UNOCC8

If a 1 is configured in the corresponding place for a certain day of the week, the related “Occupied from” and “Occupied to” times for that period will take effect on that day of the week. If a 1 is placed in the holiday field the related times will take effect on a day configured as a holiday. A zero means the schedule period will not apply to that day.

Period (1-8):

 

 

Day of Week:

Range

0 or 1

 

Default Values

11111111 for period 1,

 

00000000 for periods 2-8.

Occupied From — This field is used to configure the hour and minute, in military time, when the mode for the zone controller becomes occupied.

Period (1-8):

 

Occupied from: Units

Hours: Minutes

Range

00:00 to 24:00

Default Value

00:00

Occupied To — This field is used to configure the hour and minute, in military time, when the occupied mode for the zone controller becomes unoccupied.

Period (1-8):

 

Occupied from: Units

Hours: Minutes

Range

00:00 to 24:00

Default Value

24:00

SET POINT SCREEN — The Set Point screen is used to modify the zone controller set points. See Table 8.

Occupied Heat — The Occupied Heat set point is used to con- figure the heating set point for the zone controller during Occu- pied mode.

Occupied Heat: Units

F (C)

Range

40.0 to 90.0

Default Value

70.0

Occupied Cool — The Occupied Cool set point is used to con- figure the cooling set point for the zone controller during Occu- pied mode.

Occupied Cool: Units

F (C)

Range

45.0 to 99.9

Default Value

74.0

Unoccupied Heat — The Unoccupied Heat set point is used to configure the heating set point for the zone controller during Unoccupied mode.

Unoccupied Heat: Units

F (C)

Range

40.0 to 90.0

Default Value

55.0

Unoccupied Cool — The Unoccupied Cool set point is used to configure the cooling set point for the zone controller during Unoccupied mode.

Unoccupied Cool: Units

F (C)

Range

45.0 to 99.9

Default Value

90.0

Occupied High Humidity — The Occupied High Humidity set point is used to configure the humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.

Occupied High Humidity: Units

% Humidity

Range

0.0 to 100.0

Default Value

60.0

Unoccupied High Humidity — The unoccupied high humidi- ty set point is used to configure the unoccupied humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.

Unoccupied

 

High Humidity: Units

% humidity

Range

0 to 100

Default Value

100

1001

36

Image 36
Contents Installation, Start-Up Configuration Instructions General Typical Carrier Linkage System → Zone Controller Physical Details 33ZCFANTRM Shown HF23BJ042→ VAV Fan Terminal Zone Controller → Single Duct Air Terminal Zone ControllerZone Controller Damper Configuration Low Low Yel Blu Ora Red Wht Com SPT HF23BJ042 PAT Yel → J Zone Controller Wiring Dual Duct Applications Zone Controller Wiring Dual Duct Applications → Install Sensors Airflow Pickup Installation Space Temperature Sensor Wiring Communication Bus Wiring to Zone Controller Primary Air Temperature Sensor Part Number 33ZCSENPAT → Supply Air Temperature Probe Part No Zcsensat Locations Indoor Air Quality CO2 Sensor→ Indoor Air Quality Sensor Wiring Ventilation Rated Based on CO2 Set PointRecommended Cables Color Code RecommendationsHumidity Sensor Wiring → Remote Occupancy Wiring → Typical Water Valve and Sensor Installation Communication Bus WiringInitial Operation and Test Perform the following Configuration → Points Display ScreenDefault Value Display range Network Access Read/Write → Alarm Limit Configuration ScreenPPM → Linkage Coordinator Configuration Screen = low, 3 = high Occupancy Schedule Information Screen Airflow Service Configuration Screen → Set Point ScreenRange Default Value Terminal Service Configuration Screen RndszClockwise Rotation Range Default Value Normal Options Service Configuration ScreenPpm parts per million Secondary Damper Service Configuration Screen SrndszCOOLING, Heating → Linkage Maintenance Screen Occupancy Maintenance Screen Commissioning Mode Display Range → Zone Air Balance/Commissioning Table → Zone Maintenance Table Read/Write Page Copyright 1999 Carrier Corporation

33ZCSECTRM, 33ZCVAVTRM, 33ZCFANTRM specifications

The Carrier 33ZCFANTRM, 33ZCSECTRM, and 33ZCVAVTRM are advanced air conditioning units designed for commercial and light industrial applications. These models represent Carrier's commitment to innovation and energy efficiency, offering unbeatable performance while ensuring minimal environmental impact.

One of the main features of the Carrier 33ZCFANTRM series is its outstanding energy efficiency. These units are designed to meet or exceed Energy Efficiency Ratio (EER) standards, which translates to reduced energy consumption and lower utility bills for users. The implementation of variable speed drive technology allows for precise control of airflow and cooling, enabling the units to adapt to varying load requirements seamlessly. This not only enhances comfort levels but also optimizes energy use.

In terms of design, the Carrier 33ZCSECTRM model stands out with its compact footprint, making it ideal for installation in tight spaces. It features a robust chassis made from high-quality materials that ensure durability and resistance to harsh outdoor conditions. Additionally, the unit is equipped with sound-dampening technology, resulting in quieter operation compared to many traditional systems.

The 33ZCVAVTRM model takes versatility to the next level by incorporating advanced Variable Air Volume (VAV) technology. This allows for customized airflow delivery, ensuring that different areas of a building can be conditioned to meet specific comfort needs. The VAV system helps maintain optimal indoor air quality by continuously monitoring and adjusting airflows based on real-time demand.

Each model also features advanced controls which integrate seamlessly with building management systems. This connectivity provides users with powerful tools for monitoring system performance, enabling predictive maintenance and improving overall operational efficiency.

Moreover, the Carrier 33ZC series employs environmentally friendly refrigerants, which aligns with global sustainability goals. The use of these refrigerants contributes to a lower carbon footprint while still delivering exceptional cooling capacity.

Overall, the Carrier 33ZCFANTRM, 33ZCSECTRM, and 33ZCVAVTRM models epitomize Carrier's innovative spirit, combining cutting-edge technology with superior performance features. These units are well-suited to meet the rigorous demands of diverse commercial applications, promoting both comfort and efficiency in today's dynamic work environments. As businesses evolve, the need for reliable, efficient, and adaptable HVAC solutions becomes paramount, and these Carrier models stand ready to meet that challenge head-on.