Carrier 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM specifications Ppm parts per million

Page 42

Override — The Override parameter is used to configure the number of hours and minutes the override will be in effect. The user initiates override by pressing the override button on the space temperature sensor. This will cause the schedule to enter into the Occupied mode. If global scheduling is used, all zones using the global schedule will enter Occupied mode. Pushing the override button during Occupied mode will have no effect.

If the occupancy override is due to end after the start of the next occupancy period, the mode will transition from occupan- cy override to occupied without becoming unoccupied, and the occupancy override timer will be reset.

NOTE: If using the tenant billing function, the override hours set point must be configured between 1 and 3 hours.

Override:

Units

Hours: Minutes

 

Range

00:00 to 24:00

 

Default Value

00:00

Broadcast Acknowledger — This configuration defines if the zone controller will be used to acknowledge broadcast messag- es on the CCN bus. One broadcast acknowledger is required per bus, including secondary busses created by the use of a bridge.

Broadcast

 

Acknowledger: Range

No/Yes

Default Value

No

Set Point Group Number — The Set Point Group Number is used to define the current zone controller as a part of a group of zone controllers which share the same set points. All zone con- trollers with the same Set Point Group Number will have the same set points. The set points are broadcast to the group by the zone controller defined by the Global Set Point Master config- uration. A value of 0 is a local schedule. Values 1 to 16 are used for global scheduling.

Set Point

 

Group Number: Range

0 to 16

Default Value

0

Global Set Point Master — This configuration defines if the current zone controller will broadcast its set point values to the other zone controllers which are made part of the same group by configuring the Set Point Group Number.

Global Set Point

 

 

Master:

Range

No/Yes

 

Default Value

No

Maximum Offset Adjustment — This configuration deter- mines the maximum amount that the set point will be biased (up or down), by adjusting the slide bar on the space tempera- ture sensor (if installed).

Maximum Offset

 

 

Adjustment:

Units

delta F (delta C)

 

Range

0 to 15

 

Default Value

2

Control Options — The Control Options configuration deter- mines whether the zone controller will use a humidity sensor or an indoor air quality sensor. A configuration of 0 means no sensors are used. A configuration of 1 means a Humidity Sen- sor is used. A configuration of 2 means an IAQ Sensor is used.

Control Options: Range

0 to 2

Default Value

0

Humidity Control — These configuration values define the calculation parameters for determining the airflow needed to correct a high humidity problem in the space. The Maximum Output Value is measured in percentage of nominal terminal cfm.

Proportional

 

 

Gain:

Range

0.0 to 9.9

 

Default Value

1.5

Integral Gain:

Range

0.00 to 9.99

 

Default Value

0.30

Maximum Output

 

 

Value:

Range

0.0 to 100.0% (max cool

 

 

cfm)

 

Default Value

100.0

Indoor Air Quality Control — These configuration values de- fine the calculation parameters for determining the airflow needed to correct a high incidence of air pollution contami- nants in the space, such as CO2. The Maximum Output Value is measured in percentage of nominal terminal cfm.

Proportional Gain:Range

0.00 to 9.99

 

Default Value

0.10

Integral Gain:

Range

0.00 to 9.99

 

Default Value

0.03

Maximum Output

 

 

Value:

Range

0.0 to 100.0% (max cool

 

 

cfm)

 

Default Value

100.0

IAQ Sensor Low Voltage — This configuration defines the lowest voltage which should be read from the air quality sensor.

IAQ Sensor

 

 

Low Voltage:

Range

00.0 to 10.0

 

Default Value

0.0

IAQ Sensor High Voltage — This configuration defines the highest voltage which should be read from the air quality sen- sor.

IAQ Sensor

 

 

High Voltage:

Range

00.0 to 10.0

 

Default Value

10.0

IAQ Low Reference — This configuration defines the value in parts per million which correlate to the low voltage reading from the air quality sensor.

IAQ Low

 

 

Reference:

Units

ppm (parts per million)

 

Range

0 to 5000

 

Default Value

0

IAQ High Reference — This configuration defines the value in parts per million which correlate to the high voltage reading from the air quality sensor.

IAQ High

 

 

Reference:

Units

ppm (parts per million)

 

Range

0 to 5000

 

Default Value

2000

SECONDARY DAMPER SERVICE CONFIGURATION SCREEN — The Secondary Damper Service Configuration screen is used to configure the secondary damper settings. See Table 12.

Zone Pressure Control — The Zone Pressure Control config- uration determines whether the primary and secondary control- lers will be configured for zone pressure control.

Zone Pressure

 

 

Control:

Range

Dsable/Enable

 

Default Value

Dsable

Dual Duct Type — The Dual Duct Type setting configures the secondary controller for the correct dual duct type. A value of 0 configures the type to None. A value of 1 configures the type to Second Inlet (Hot Deck). A value of 2 configures the duct to Total Probe (terminal outlet).

Dual Duct Type: Range

0 to 2

Default Value

0

800

42

Image 42
Contents Installation, Start-Up Configuration Instructions General Typical Carrier Linkage System → Zone Controller Physical Details 33ZCFANTRM Shown HF23BJ042→ VAV Fan Terminal Zone Controller → Single Duct Air Terminal Zone ControllerZone Controller Damper Configuration Low Low Yel Blu Ora Red Wht Com SPT HF23BJ042 PAT Yel → J Zone Controller Wiring Dual Duct Applications Zone Controller Wiring Dual Duct Applications → Install Sensors Airflow Pickup Installation Space Temperature Sensor Wiring Communication Bus Wiring to Zone Controller Primary Air Temperature Sensor Part Number 33ZCSENPAT → Supply Air Temperature Probe Part No Zcsensat Locations Indoor Air Quality CO2 Sensor→ Indoor Air Quality Sensor Wiring Ventilation Rated Based on CO2 Set PointRecommended Cables Color Code RecommendationsHumidity Sensor Wiring → Remote Occupancy Wiring → Typical Water Valve and Sensor Installation Communication Bus WiringInitial Operation and Test Perform the following Configuration → Points Display ScreenDefault Value Display range Network Access Read/Write → Alarm Limit Configuration ScreenPPM → Linkage Coordinator Configuration Screen = low, 3 = high Occupancy Schedule Information Screen Airflow Service Configuration Screen → Set Point ScreenRange Default Value Terminal Service Configuration Screen RndszClockwise Rotation Range Default Value Normal Options Service Configuration ScreenPpm parts per million Secondary Damper Service Configuration Screen SrndszCOOLING, Heating → Linkage Maintenance Screen Occupancy Maintenance Screen Commissioning Mode Display Range → Zone Air Balance/Commissioning Table → Zone Maintenance Table Read/Write Page Copyright 1999 Carrier Corporation

33ZCSECTRM, 33ZCVAVTRM, 33ZCFANTRM specifications

The Carrier 33ZCFANTRM, 33ZCSECTRM, and 33ZCVAVTRM are advanced air conditioning units designed for commercial and light industrial applications. These models represent Carrier's commitment to innovation and energy efficiency, offering unbeatable performance while ensuring minimal environmental impact.

One of the main features of the Carrier 33ZCFANTRM series is its outstanding energy efficiency. These units are designed to meet or exceed Energy Efficiency Ratio (EER) standards, which translates to reduced energy consumption and lower utility bills for users. The implementation of variable speed drive technology allows for precise control of airflow and cooling, enabling the units to adapt to varying load requirements seamlessly. This not only enhances comfort levels but also optimizes energy use.

In terms of design, the Carrier 33ZCSECTRM model stands out with its compact footprint, making it ideal for installation in tight spaces. It features a robust chassis made from high-quality materials that ensure durability and resistance to harsh outdoor conditions. Additionally, the unit is equipped with sound-dampening technology, resulting in quieter operation compared to many traditional systems.

The 33ZCVAVTRM model takes versatility to the next level by incorporating advanced Variable Air Volume (VAV) technology. This allows for customized airflow delivery, ensuring that different areas of a building can be conditioned to meet specific comfort needs. The VAV system helps maintain optimal indoor air quality by continuously monitoring and adjusting airflows based on real-time demand.

Each model also features advanced controls which integrate seamlessly with building management systems. This connectivity provides users with powerful tools for monitoring system performance, enabling predictive maintenance and improving overall operational efficiency.

Moreover, the Carrier 33ZC series employs environmentally friendly refrigerants, which aligns with global sustainability goals. The use of these refrigerants contributes to a lower carbon footprint while still delivering exceptional cooling capacity.

Overall, the Carrier 33ZCFANTRM, 33ZCSECTRM, and 33ZCVAVTRM models epitomize Carrier's innovative spirit, combining cutting-edge technology with superior performance features. These units are well-suited to meet the rigorous demands of diverse commercial applications, promoting both comfort and efficiency in today's dynamic work environments. As businesses evolve, the need for reliable, efficient, and adaptable HVAC solutions becomes paramount, and these Carrier models stand ready to meet that challenge head-on.