Carrier 38AKS028-044 dimensions Troubleshooting, Compressor Stops on LOW-PRESSURE Control

Page 21

 

TROUBLESHOOTING

SYMPTOM AND PROBABLE CAUSE

PROBABLE REMEDY

COMPRESSOR DOES NOT RUN

 

 

1. Control circuit breaker tripped

1. Reset control circuit breaker

2. Power line open

2. Reset circuit breaker

3. Oil pressure switch tripped

3. Reset oil pressure switch at unit

4. Safety device tripped

4. Reset control circuit with thermostat

5. Contactor stuck open

5. Replace contactor

6. Loose terminal connection

6. Check connections

7. Improperly wired controls

7. Check and rewire

8. Seized compressor

8. Check motor winding for open or short.

9. Low line voltage

 

Replace compressor, if necessary

9. Check line voltage Ð determine location of

10. Compressor motor defective

 

voltage drop and remedy de®ciency

10. Check motor winding for open or short.

 

 

 

Replace compressor, if necessary

COMPRESSOR STOPS ON LOW-PRESSURE

 

 

CONTROL

 

 

1. Compressor suction shutoff valve partially closed

1. Open valve

2.

Low refrigerant charge

2.

Add refrigerant

3.

Liquid line solenoid valve(s) fails to open

3.

Check liquid line solenoid valve for proper

4.

Liquid line shutoff valve closed

4.

operation. Replace if necessary

Open valve

COMPRESSOR STOPS ON HIGH-PRESSURE

 

 

CONTROL

 

 

1.

Compressor discharge valve partially closed

1.

Open valve or replace if defective

2.

Air in system

2.

Purge and evacuate system

3.

Condenser fan(s) not operating

3.

Check motor wiring and repair or replace if

4.

System is overcharged.

4.

defective

Reclaim charge as needed

UNIT OPERATES TOO LONG OR

 

 

CONTINUOUSLY

 

 

1.

Low refrigerant charge

1.

Add refrigerant

2.

Control contacts fused

2.

Replace control

3.

Air in system

3.

Purge and evacuate system

4.

Partially plugged expansion valve or ®lter drier

4. Clean or replace

SYSTEM IS NOISY

 

 

1.

Piping vibration

1.

Support piping as required

2.

Compressor noisy

2.

Check valve plates for valve noise. Replace

 

 

 

compressor if bearings are worn

COMPRESSOR LOSES OIL

 

 

1.

Leak in system

1.

Repair leak

2.

Crankcase heaters not energized during

2.

Check wiring and relays. Check heater and

3.

shutdown

3.

replace if defective

Improper interconnecting piping design

Check piping for oil return. Replace if

 

 

 

necessary

FROSTED SUCTION LINE

 

 

1.

Expansion valve admitting excess refrigerant

1.

Adjust expansion valve

HOT LIQUID LINE

 

 

1.

Shortage of refrigerant due to leak.

1.

Repair leak and recharge

2.

Expansion valve opens too wide

2.

Adjust expansion valve

FROSTED LIQUID LINE

 

 

1.

Restricted ®lter drier

1. Remove restriction or replace

COMPRESSOR WILL NOT UNLOAD

 

 

1.

Defective unloader

1.

Replace

2.

Defective capacity control solenoid valve

2.

Replace valve

3.

Miswired liquid line solenoid

3.

Rewire correctly

4.

Weak, broken, or wrong valve body spring

4.

Replace spring

COMPRESSOR WILL NOT LOAD

 

 

1.

Miswired capacity control liquid solenoid

1.

Rewire correctly

2.

Defective capacity control solenoid valve

2.

Replace valve

3.

Plugged strainer (high side)

3.

Clean or replace strainer

4.

Stuck or damaged unloader piston or piston

4.

Clean or replace the necessary parts

 

ring(s)

 

 

21

Image 21
Contents Contents Safety ConsiderationsBefore Installation Ð Physical Data Ð SI Ð Physical Data Ð English38AKS Units InstallationCompressor Mounting Ð Refrigerant Piping Sizes Ð 60 Hz Unit Length of Interconnecting PIPING, FT MÐ Refrigerant Piping Sizes Ð 50 Hz 38AKSElectrical Data Length Insulated Wire Size AWG Mm250-75 38AKS028C 38AKS02838AKS034 38AKS034C38AKS044C 2745 1246 38AKS044 2437Equip AFSGND LLS1Llsv BPRTDR Time Delay RelayTran TransformerInitial Check START-UP38AKS028 Charging Chart, 50/60 Hz 38AKS034 Charging Chart, 50/60 Hz 38AKS044 Charging Chart, 50/60 Hz Service Access for Servicing See FigComplete Unit Stoppage 38AKS Unit with Access Panels Removed 06E9265 Compressor Amount06E9275 06E9299Pressure Switch Settings, psig kPa Minimum Outdoor-Air Operating TemperatureFan Cycling Controls Compressor Stops on LOW-PRESSURE Control TroubleshootingPackaged Service Training Preliminary Information Pre-Start-UpRemove and store in job le OIL Level AT 1¤ 8 to 1¤ 3 FULL? Start-Up