Carrier 38AKS028-044 dimensions Complete Unit Stoppage, Service, Access for Servicing See Fig

Page 17

FOR SERVICING ONLY Ð To speed up the 5-minute anti- short cycle, a temporary jumper may be placed between ter- minals T1 and T6 of the control module.

This jumper must be removed after servicing is com- plete. Failure to remove this jumper is considered abu- sive treatment and will void the Carrier warranty.

Bypass Relay (BPR) Ð All units are equipped with a BPR located in the control section of the control box. See Fig. 9A or 9B. The function of the BPR is to provide a 2-minute bypass of the LPS at start-up, and to energize the unload- er(s) at start-up to provide unloaded compressor starting. Two minutes after the compressor starts, the BPR completes its function and is no longer active in the control circuit until the next restart of the unit.

Time-Delay Relay (TDR) (50 Hz Only) Ð This solid- state delay-on-make relay is factory set for a 1-second delay. The number 1 dip switch is set to the ON position, and all the other dip switches are set to the OFF position. Once the control relay (CR) is energized, the compressor contactor C1 is powered, and the ®rst set of compressor windings is en- ergized. After the 1-second time delay, contactor C1A is pow- ered and the second set of compressor windings is energized (part-wind start).

Sequence of Operation Ð When space thermostat calls for cooling, the no. 1 condenser fan and compressor start after CM initial time delay of 3 (12/±1) seconds. If an optional air¯ow switch is used, compressor and no. 1 con- denser fan will not start until sufficient indoor air¯ow has closed the switch. After 3 seconds the compressor starts and the liquid line solenoid valve for solenoid drop control opens. The crankcase heater is deenergized. If the head pressure reaches 260 psig (1792 kPa) the second condenser fan starts. Fan no. 3 (38AKS044 only) starts if outdoor ambient air rises above 80 F (26.7 C).

If cooling demand is low, suction pressure at the com- pressor drops. As the pressure drops, the compressor un- loads 2 banks of cylinders as required. If cooling demand is high and 2-stage operation is used, the second stage of the thermostat activates the capacity control liquid line solenoid which activates the second stage evaporator coil. The com- pressor cylinders load or unload in response to compressor suction pressure to meet evaporator load.

Two minutes after compressor starts, the BPR timer is deen- ergized and the LPS bypass is deactivated. If the LPS trips during the ®rst 2 minutes of operation, the compressor will remain operational. If the LPS trips after 2 minutes, the com- pressor operation is interrupted, and the compressor cannot restart until the 5-minute CM anti-short cycle timer expires.

As the space cooling load is satis®ed, the second stage of the thermostat opens, and closes the ®eld-supplied capacity control liquid line solenoid valve to deactivate the second stage coil. The compressor adjusts the number of active cyl- inders to meet the new load. When the space temperature is satis®ed, the ®rst stage of the thermostat opens and the con- trol relay and the BPR open. This closes the solenoid drop control valve. The compressor stops and the crankcase heater is energized, preventing refrigerant from migrating to the com- pressor during the off cycle (solenoid drop refrigerant con- trol). The CM anti-short cycling timer is energized and runs for approximately 5 minutes. During this time, the compres- sor is not able to restart.

Complete Unit Stoppage

CAUSES Ð Interruption of supplied power, compressor over- temperature protection, or open HPS causes compressor stoppage.

RESTART Ð The unit recycles and restarts automatically under the CM when power is restored. Stoppage by HPS, or compressor circuit breaker requires manual resetting of the control circuit. To restart the CM timer when HPS is tripped, it is necessary to interrupt power to the unit, restarting the CM logic. It is necessary to manually reset the compressor circuit breaker at the unit.

If LPS is not closed within 2 minutes after compressor starts, the compressor locks out and the outdoor fans con- tinue to run. It stays locked out for 5 minutes until the CM anti-short cycle timer expires. After 5 minutes, the LPS is bypassed by the BPR (winter start control). It remains jum- pered for 2 minutes. Because the LPS is jumpered, the com- pressor restarts and runs for the 2-minute time period. At the end of this 2 minutes, if the LPS has still not closed, the compressor is again locked out. The outdoor fans continue to run as long as there is a call for cooling. Automatic reset of the LPS causes the CM to recycle so that the compressor can start.

If sufficient compressor oil pressure has not been built within 2 minutes after the compressor starts, the unit is completely deenergized until the oil pressure switch is manually reset at the unit.

If unit or circuit stoppage occurs more than once due to any safety device, the trouble should be corrected be- fore any attempt to restart.

SERVICE

Turn off all power to unit before proceeding.

Access for Servicing (See Fig. 13)

COMPRESSOR SECTION Ð The compressor compart- ment has 2 side access panels and one front door for ser- vicing, providing access to compressor, all components of the refrigerant system, electrical controls, and control box. After opening front door there is an inner cover that must be removed for access to control box (except 208/230-v and 460-v units).

OIL PRESSURE SAFETY SWITCH Ð Switch is manually reset, and accessed by removing the side access panel on the left side of the unit (as viewed from the compressor end). See Fig. 13. The OPS is found in the compressor junction box. Open the compressor circuit breaker prior to removing the compressor junction box cover in order to access the OPS. The liquid line service valve can be found behind the side access door on the right side of the unit (as viewed from the compressor end).

CONDENSER SECTION Ð Condenser fan motors and fans can be serviced by removal of outlet grilles or side panels. If a fan motor is serviced, be sure the wire fan guard is in place over each fan before starting unit. See Fig. 14 for proper fan adjustment. Tighten fan hub securely on motor shaft with setscrew which bears against the key. Be sure to replace Per- magum and rubber cap over end of motor shaft to protect against moisture causing fan to rust on shaft.

17

Image 17
Contents Before Installation ContentsSafety Considerations Ð Physical Data Ð SI Ð Physical Data Ð English38AKS Units InstallationCompressor Mounting Ð Refrigerant Piping Sizes Ð 60 Hz Unit Length of Interconnecting PIPING, FT MÐ Refrigerant Piping Sizes Ð 50 Hz 38AKSElectrical Data 50-75 Length Insulated Wire Size AWGMm2 38AKS028C 38AKS02838AKS034 38AKS034C38AKS044C 2745 1246 38AKS044 2437Equip AFSGND LLS1Llsv BPRTDR Time Delay RelayTran TransformerInitial Check START-UP38AKS028 Charging Chart, 50/60 Hz 38AKS034 Charging Chart, 50/60 Hz 38AKS044 Charging Chart, 50/60 Hz Complete Unit Stoppage ServiceAccess for Servicing See Fig 38AKS Unit with Access Panels Removed 06E9265 Compressor Amount06E9275 06E9299Fan Cycling Controls Pressure Switch Settings, psig kPaMinimum Outdoor-Air Operating Temperature Compressor Stops on LOW-PRESSURE Control TroubleshootingPackaged Service Training Remove and store in job le Preliminary InformationPre-Start-Up OIL Level AT 1¤ 8 to 1¤ 3 FULL? Start-Up