Carrier 50PSW036-360 specifications Wire Low Voltage Connections, Pre-Start-Up

Page 12

L1 L2 L3

Grnd Power Distribution

Block Transformer

Connector

Low Voltage

C Control #1

Contactor -CC1 Contactor -CC2

Connector

Low Voltage

C Control #2

Fig. 8 — Typical Field Wiring

EXTERNAL LOOP POWER CONNECTION — If the unit is to be connected to an external loop pump or flow controller, connect the pump to the loop pump terminal block PB1. The maximum power handling is 4 amps at 240-v. The pumps will automatically cycle as required by the unit.

220-V OPERATION — All 220/240-v units are factory wired for 220-v. The transformers may be switched to 240-v operation (as illustrated on the wiring diagram) by switching the red (220-v) wire with the orange (240-v) wire at the L2 terminal.

380-VOLT OPERATION — All 380/415 volt units are factory wired for 420 volts. The transformers may be switched to 380-volt operation by switching the brown (380 volt) wire with the violet (420 volt) wire at the L1 terminal.

Step 7 — Wire Low Voltage Connections

THERMOSTAT CONNECTIONS

The thermostat should be wired directly to the Aquazone™ control board. See Fig. 4-7.

WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at –1.1 C. In earth loop applications, jumper JW3 should be clipped to change the setting to –12.2 C when using antifreeze in colder earth loop applications. See Fig. 9.

Fig. 9 — Typical Aquazone Control Board

Jumper Locations (Complete C Control Shown)

ACCESSORY CONNECTIONS — The terminal labeled A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This sig- nal operates with the compressor terminal. See Fig. 10. Refer to the specific unit wiring schematic for details.

Terminal Strip

C

Typical

24 VAC Water

Valve

A

Fig. 10 — Typical Aquazone Accessory Wiring

(Deluxe D Control Shown)

NOTE: The A terminal should only be used with 24-v signals, not line voltage signals.

IMPORTANT: Two-compressor units with Complete C or Deluxe D controls wired to terminal A will be turned off if the controls are in lockout mode, even if the other board is in normal operating mode.

WATER SOLENOID VALVES — Water solenoid valves may be used on variable flow systems and ground water instal- lations. A typical well water control valve wiring which can limit waste water in a lockout condition is shown in Fig. 10. A slow closing valve may be required to prevent water hammer. When using a slow closing valve, special wiring conditions need to be considered. The valve takes approximately 60 sec- onds to open (very little water will flow before 45 seconds) and it activates the compressor only after the valve is completely opened by closing its end switch. When wired as shown, the valve will have the following operating characteristics:

1.Remain open during a lockout.

2.Draw approximately 25 to 35-va through the “Y” signal of the thermostat.

IMPORTANT: This can overheat the anticipators of electromechanical thermostats. Only use relay based electronic thermostats.

PRE-START-UP

System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:

1.Voltage is within the utilization range specifications of the unit compressor and fan motor, and voltage is balanced for 3-phase units.

2.Fuses, breakers and wire are correct size.

3.Low voltage wiring is complete.

4.Piping and system flushing is complete.

5.Air is purged from closed loop system.

6.System is balanced as required. Monitor if necessary.

7.Isolation valves are open.

8.Water control valves or loop pumps are wired.

9.Transformer switched to lower voltage tap if necessary.

10.Service/access panels are in place.

11.Control field-selected settings are correct.

12

Image 12
Contents Contents Safety ConsiderationsInstallation General50PSW Unit Physical Data Electric Access Plugs Overall Cabinet50PSW HWG Unit Size50PSW180,360 Unit Teflon* tape thread sealant is recommended to minimize Water Quality Guidelines Condition Closed Open Loop and Recirculating WellRECIRCULATING† Wire Electrical Connections 50PSW Electrical DataMIN/MAX RLA LRA QTY FLA FP1 FP2JW1 LEDAstat CompDTS HpwsAlarm Relay Contacts Motor Switch Compressor Field Wiring Terminal Block Compressor ContactorHot Water Generator Field Line Voltage Wiring Jumper Wire for Alarm Field Low Voltage WiringTypical Aquazone 50PSW360 Deluxe D Control Wiring, 3-Phase Wire Low Voltage Connections PRE-START-UPComplete C Control Jumper Settings See Fig Deluxe D Control Jumper Settings See FigDIP Switch Block S2 Accessory 1 Relay Options Accessory DIP Switch Position Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UPOperating Limits See Table Unit Start-UpHeat Exchanger Pressure Drop Unit SizeOperation Units with Aquazone Complete C ControlUnits with Aquazone Deluxe D Control System TestComplete C Control LED Code Fault Descriptions LED Status Description Alarm Relay OperationLED Fault Description Code Aquazone Deluxe D Control LED IndicaService Description Status LED Test LEDESD Troubleshooting Refrigerant ChargingFP1 and FP2 Thermistor Location Troubleshooting Fault Heating Cooling Possible Cause SolutionCopyright 2010 Carrier Corporation 50PSW START-UP Checklist II. START-UPHeating and Cooling Cycle Analysis Description Heating CoolingCLG HTG

50PSW036-360 specifications

The Carrier 50PSW036-360 is a highly efficient and reliable rooftop unit designed for commercial applications. It combines advanced technologies and innovative features to provide optimal indoor comfort while ensuring energy savings and ease of operation. Its robust construction and numerous functionalities make the 50PSW036-360 an ideal choice for various building types, from retail spaces to office complexes.

One of the main features of the Carrier 50PSW036-360 is its efficient cooling and heating capabilities. It employs state-of-the-art scroll compressors, which deliver consistent performance and lower noise levels while consuming less energy compared to conventional compressors. This translates into significant energy savings, making it a cost-effective solution for businesses aiming to reduce their operational expenses.

The unit is equipped with a range of advanced technologies, including Carrier’s EcoBlue™ technology, which optimizes airflow and enhances energy efficiency. This technology helps achieve higher SEER (Seasonal Energy Efficiency Ratio) ratings, allowing users to benefit from lower utility bills without sacrificing comfort. Additionally, the unit comes with smart control options, enabling users to easily manage and monitor temperature settings, fan speeds, and energy consumption through intuitive interfaces.

The Carrier 50PSW036-360 also emphasizes versatility and adaptability. It has a compact design that makes it easy to install on rooftops, while its extensive selection of options, such as electric heat and economizers, allows it to be configured to meet various application requirements. Its advanced filtration system ensures high indoor air quality by removing dust, allergens, and other pollutants, which is essential for maintaining a healthy indoor environment.

Durability is another characteristic that sets the Carrier 50PSW036-360 apart. The unit is constructed using high-quality materials designed to withstand the rigors of outdoor environments. This ensures longevity and reliability, making it an excellent long-term investment for businesses.

In summary, the Carrier 50PSW036-360 is a top-of-the-line rooftop unit, ideal for commercial applications. Its blend of energy efficiency, advanced technologies, and robust construction makes it a preferred choice for maintaining optimal indoor climate conditions. With its versatility, durability, and ease of use, this system ensures comfort for occupants while helping businesses achieve their sustainability goals.